SiUS071735EB
Trial Operation
Trial Operation and Field Settings
122
With Wireless Remote Controller (BRC082A43)
1. Press
button and select the COOL or HEAT operation.
2. Press
button twice.
“
TEST
”
is displayed.
3. Press
button within 10 seconds, and the test operation starts.
Monitor the operation of the indoor unit for a minimum of 10 minutes. During test operation, the
indoor unit will continue to cool/heat regardless of the temperature setpoint and room
temperature.
In the case of above-mentioned procedures (1) and (2) in reverse order, test operation can
start as well.
Test operation will stop automatically after 15 ~ 30 minutes. To stop the operation, press
button.
Some of the functions cannot be used in the test operation mode.
Test Items
Test items
Symptom
Indoor and outdoor units are installed securely.
Fall, vibration, noise
Is the outdoor unit fully installed?
No operation or burn damage
No refrigerant gas leaks.
Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Water leakage
Draining line is properly installed.
Water leakage
Does the power supply voltage correspond to that
shown on the name plate?
No operation or burn damage
Only specified wires are used for all wiring, and all
wires are connected correctly.
No operation or burn damage
System is properly grounded.
Electrical leakage
Is wiring size according to specifications?
No operation or burn damage
Is something blocking the air outlet or inlet of either
the indoor or outdoor units?
Incomplete cooling/heating function
Are refrigerant piping length and additional
refrigerant charge noted down?
The refrigerant charge in the system is not clear
Pipes and wires are connected to the
corresponding connection ports/terminal blocks for
the connected unit.
No cooling/heating
Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives wireless remote
control commands.
No operation
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...