SiUS071735EB
Trial Operation
Trial Operation and Field Settings
120
3. Trial Operation
Outline
Trial operation should be carried out in either cooling or heating operation.
1. Measure the supply voltage and make sure that it is within the specified range.
2. In COOL operation, select the lowest programmable temperature;
in HEAT operation, select the highest programmable temperature.
3. Carry out the trial operation following the instructions in the operation manual to ensure that all
functions and parts, are working properly.
To protect the air conditioner, restart operation is disabled for 3 minutes after the system has
been turned off.
4. After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to
28°C) in COOL operation, 68°F to 75°F (20°C to 24°C) in HEAT operation).
Caution
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct trial
operation accordingly to protect the unit.
Procedure
When operating the air conditioner in cooling operation in winter, or heating operation in summer,
set it to the trial operation mode using the following method.