background image

 CAUTION 

• The air supply pipe, the air intake pipe and the fresh air pipe must be covered with a layer of thermal 

insulation, so as to avoid thermal leakage and condensation. Firstly apply liquid nail on the pipes, then  
attach the thermal insulation cotton with a layer of tinfoil. Use the liquid nail cover to fix it. Lastly use tinfoil 
adhesive tape to carefully seal the joints. Other good thermal insulation materials can also be used. 

• The air supply pipes and the air intake pipes shall be fixed to the prefabricated boards of the ceiling by 

using iron supports. The joints of the pipes must be sealed by glue so as to avoid leakage. 

• The design and installation of air pipes must be in conformity with the relevant state engineering criteria. 
• The edge of the air intake pipe must be at least 150mm away from the wall. The air intake must be covered 

with fi lter. 

• Silencing and shock absorption shall be considered in the design and installation of the air pipes. Addition-

ally, the noise source must be far away from where people stay. The air intake shall not be located above 
the place where users stay (offices and rest places, etc.). 

8.7 Installation of Drainage Pipe

 

line

(1) The drainage pipeline shall be installed with an inclining angel of 5 ~ 10°, so as to facilitate the drainage of 

condensate. The joints of the drainage pipeline must be covered by thermal insulation materials to avoid 
generation of exterior condensate. (As shown in Fig. 8.10) 

(2) A drainage outlet is located at both the left and right sides of the indoor unit. After selecting one drainage 

outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid 
leakage, and also use thermal insulation materials to wrap the blocked outlet. 

(3) When shipped out from factory, both the drainage outlets are blocked by rubber plugs. 
(4) When connecting the drainage pipeline with the unit, do not apply excessive force to the pipeline at the  

(5) Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When carrying out 

connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and 
tighten it with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. 

(6) When the laid drainage pipeline is used for multiple units, the common pipe shall be about 100mm lower  

the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose. 

Thermal Insulation 
Materials of  Drainage 
Pipeline 

Drainage Pipeline 

Fig.8.10 Thermal Insulation of Drainage Pipeline

 CAUTION 

The joint of  rainage pipeline must not have leakage. 

d

,

side of the unit. The fixing position of the pipeline shall be near the unit. 

then 

English 

30 

Summary of Contents for FDM24PEV1K

Page 1: ...UNIT English 7 0 14 0kW Unit Model Indoor unit FDM24PEV1K FDM30PEV1K FDM36PEV1K FDM42PEV1K FDM48PEV1K FDYM24PEV1K FDYM30PEV1K FDYM36PEV1K FDYM42PEV1K FDYM48PEV1K Outdoor unit R24PEV1K R30PEV1K R36PEY...

Page 2: ...ust be adopted as signal line or wiring communication of wired controller once the unit is installed in the place where there is electromagnetic interference Make sure communication line is connected...

Page 3: ...ontrol 24 7 4 The head of delivery of the condensate drainage pump 24 VIII INSTALLATION INSTRUCTIONS 25 8 1 Dimensions of Indoor Unit 25 8 2 Dimensions of Outdoor Unit 27 8 3 Precautions on Installati...

Page 4: ...Consult our local dealer about installation work Doing the work yourself may result in water leakage electric shocks or re hazards Consult our local dealer regarding modi cation repair and maintenance...

Page 5: ...ocks or re Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or re Be sure to use only the s...

Page 6: ...ioner at any place where there is a danger of ammable gas leakage In the event of a gas leakage build up of gas near the air conditioner may result in re hazards Do not put ammable containers such as...

Page 7: ...transmitting distance can be shorter than expected in rooms with electronic uorescent lamps inverter or rapid start types Install the indoor unit as far away from uorescent lamps as possible Do not i...

Page 8: ...II DISPLAYING PART Fig 2 1 Outline of wired controller 2 1 LCD Display of Wired Controller Fig 2 2 LCD display English 6...

Page 9: ...e monitoring 13 Turbo Turbo function state 14 Memory Memory state Indoor unit resumes original setting state after power failure and then power recovery 15 Twinkle Flicking when unit is on without ope...

Page 10: ...ver among the functions of air sleep turbo save E heater blow quiet 7 Timer Timer setting 8 On off Turn on off indoor unit 4 Mode and 2 Memory function Press and for 5s under off state of the unit to...

Page 11: ...n wall face and then x it in mounting hole with screws M4X25 4 Insert the 4 core twisted pair into controller s slot through rectangle hole and buckle the front panel and soleplate of controller toget...

Page 12: ...1 indicates off state of the unit after energization The state shown in Fig 5 2 indicates on state of the unit after energization Fig 5 1 Off state of the unit Fig 5 2 On state of the unit 5 2 Mode S...

Page 13: ...erature will be increased or decreased by 1 C every 0 5s In Cooling Dry Fan and Heating mode temperature setting range is 16 30 C In Auto mode the setting temperature is un adjustable As shown in Fig...

Page 14: ...adjust timer on and then press Timer to con rm If Mode button is pressed before pressing Timer button to con rm timer mode will be switched to timer off setting mode In this case LCD displays xx Hour...

Page 15: ...press of or button will make setting time increased or decreased by 0 5hr If press either of them continuously setting time will automatically increase decrease by 0 5hr every 0 5s Note 1 If both time...

Page 16: ...he unit continuously runs for 60min and fresh air valve opens for 48 min 9 The unit continuously runs for 60min and fresh air valve opens for 54 min 10 The unit continuously runs for 60min and fresh a...

Page 17: ...sleep function Press Enter Cancel button to turn off sleep function Press Function button into sleep function Fig 5 8 Sleep setting Sleep ed after power failure and then power recovery There is no sl...

Page 18: ...t be set and T mark won t be displayed 2 Turbo function will be automatically canceled after setting of quiet function 5 10 Save Function Setting Energy Saving Function Energy saving result that the a...

Page 19: ...ction on the unit will forcibly quit auto running mode and change to operation mode After setting of SAVE sleep function will be canceled 2 In save mode if button is pressed or there is not any operat...

Page 20: ...n is on press Function button to con rm or press Enter Cancel button to cancel In this case E HEATER won t be displayed which means E heater is prohibited to be turned on The setting of this function...

Page 21: ...this function Blow function setting is shown in Fig 5 12 Turn on the unit without turning on blow function Press Function button into blow function Press Enter Cancel button to turn on blow function...

Page 22: ...n setting Note 1 During quiet function fan speed is un adjustable 2 When turning on auto quiet function the unit will enter quiet running state according to temperature difference between room tempera...

Page 23: ...ress and buttons at the same time for 5s till the wired controller enters lock state In this case LCD displays After that repress these two buttons at the same time for 5s to quit lock state Under loc...

Page 24: ...ressure protection of system 2 under unit on Error code meaning Fig 6 1 Error code Error E1 High pressure protection of compressor E2 Indoor anti freezing protection E3 Low pressure protection of comp...

Page 25: ...from the two indoor room sensors on the basis of the engineering requirement Refer to the section of wired controller instructions for detailed operation Indoor Room Sensor A Indoor Room Sensor B Fig...

Page 26: ...operation Refer to the section of wired controller instructions for detailed operation Fresh Air Air Intake Pipe Air Supply Pipe Outdoor Fresh Air Before starting up the unit please remove Indoor Sid...

Page 27: ...DYM48PEV1K Drainage Pipe Air Intake I H J E lectric Box G Air Supply B C D E F For Item Model A B C D E F G H I J Liquid Pipe Gas Pipe Drainage Pipe Outer Diameter Wall Thickness FDM24PEV1K FDYM24PEV1...

Page 28: ...Unit Nut with Washer Nut Spring Washer 250 250 Fig 8 2 or FDM24PEV1K FDYM24PEV1K FDM30PEV1K FDYM30PEV1K FDM36PEV1K FDYM36PEV1K FDM42PEV1K FDYM42PEV1K FDM48PEV1K FDYM48PEV1K WARNING The height of inst...

Page 29: ...that the air discharged by outdoor unit will not return and that suf cient space for repair shall be provided around the machine 2 The installation site must have good ventilation so that the outdoor...

Page 30: ...t source leakage of in ammable gas or smoke 6 The indoor unit is of ceiling mount indoor unit is hidden inside the ceiling 7 The indoor and outdoor units the power cable and the connecting electrical...

Page 31: ...it is installed it is required to check the level of the whole unit The unit must be placed horizontally but the condensate pipe shall be installed obliquely so as to facilitate the drainage of conden...

Page 32: ...itate the drainage of condensate The joints of the drainage pipeline must be covered by thermal insulation materials to avoid generation of exterior condensate As shown in Fig 8 10 2 A drainage outlet...

Page 33: ...f 6 0 MPa 3 The longer the pipe the lower the cooling effect and the heating effect 8 10 Connection of 1 Align the ared end of the copper pipe with the center of the thread joint Manually tighten the...

Page 34: ...immediately and tighten the bonnet 8 Fully open the spools of the liquid valve and the gas valve refer to Fig 8 12 9 Tighten the caps of valves Then use soap water or leakage detector to check if ther...

Page 35: ...ial to block the hole in the wall so as to prevent rain and wind from entering the room 8 12 Position and Method of Installing Wired Controller 1 One end of the controlling wire of the wired controlle...

Page 36: ...Description Wall Surface Bottom Plate of Wired Controller Screw M4X10 Front panel of Wired Controller 8 13 Connection of Signal Line of Wired Controller 1 Open the cover of the electric box of the in...

Page 37: ...conditioning unit 3 Use crimping pliers to connect a terminal matching the size of the screw at the end of the multiple twisted wires 4 Put the screw through the terminal of the multiple twisted wire...

Page 38: ...r line and the electric box connecting line between the indoor unit and Use cable fastener to bundle and x the cable the outdoor unit 2 In case the unit is installed in a place vulnerable by electroma...

Page 39: ...FDYM48PEV1K RY48PEY1K Outdoor Unit L1 L2 L3 N 2 3 L N 1 2 2 3 Indoor Unit 1 2 breaker breaker L1 L2 L3 N PE L N PE Power 380 415V 3N 50Hz Power 220 240V 50Hz 1 Power cord 5 4mm H07RN F 2 Power cord 3...

Page 40: ...415 3 50 20 4 0 4 0 RY42PEY1K R42PEY1K 380 415 3 50 4 0 4 0 RY48PEY1K R48PEY1K 380 415 3 50 4 0 4 0 Indoor Unit Duct Type Model Power Supply V Ph Hz Capability of Air Switch Minimum Sectional Area of...

Page 41: ...nt temperature is lower than 7 C Control line is abnormal The indoor fan does not start under the heating mode 1 2 3 4 The installation site of the tube sensor is not proper Tube sensor is not correct...

Page 42: ...stall at a place strong enough to support the weight of air conditioner unit If not the air condi tioner unit might fall down and cause human injury or death To ensure proper drainage the drainage pip...

Page 43: ...corresponding to standard external static pressure The parameters are subject to change with the improvement of products in which case the values on nameplate shall prevail WARNING This appliance is n...

Page 44: ...DOOR UNIT FDYM24PEV1K FDYM30PEV1K FDYM36PEV1K FDYM42PEV1K FDYM48PEV1K OUTDOOR UNIT RY24PEV1K RY30PEV1K RY36PEY1K RY42PEY1K RY48PEY1K RATED VOLTAGE V 220 240 220 240 380 415 380 415 380 415 RATED FREQU...

Reviews: