11-3 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED
• For setting when attaching an optional accessory, refer to the installation manual attached to the optional
accessory.
11-4 WHEN USING WIRELESS REMOTE CONTROLLER
• When using a wireless remote controller, it is necessary to set the wireless remote controller address.
Refer to the installation manual attached to the wireless remote controller.
11-5 SETTING FAN SPEED DURING THERMOSTAT OFF
• Set the fan speed according to the using environment after consultation with your customer.
• When the fan speed is changed, explain the set fan speed to your customer.
Table7
Setting
Mode No.
FIRST
SECOND
CODE No.
CODE No.
Fan operates / stops during thermo OFF
Operates
01
11 (21)
2
(Cooling • heating)
Stops
02
(Extra low)
01
Fan speed during cooling thermostat OFF
12 (22)
Setting
02
(Extra low)
01
Fan speed during heating thermostat OFF
Setting
12 (22)
3
02
11-6 SETTING FILTER SIGN
• A message to inform the air filter cleaning time will be indicated on the remote controller.
• Set the SECOND CODE No. shown in the Table 8 according to the amount of dust or pollution in
the room.
• Though the indoor unit is equipped with the long life filter, it is necessary to periodically clean the filter
to avoid clogging of the filter. Please also explain the set time to the customer.
• The periodical filter cleaning time can be shortened depending on the environment.
Table8
Contamination
Hours until indication
Mode No.
FIRST
SECOND
CODE No.
CODE No.
Normal
Approx. 2500 hrs
01
0
More contaminated
Approx. 1250 hrs
10 (20)
02
With indication
01
3
No indication*
02
* Use "No indication" setting when cleaning indication is not necessary such as the case of periodical cleaning being
carried out.
11-7 SETTING NUMBER OF THE CONNECTED INDOOR UNITS AS SIMULTANEOUS OPERATION
SYSTEM
• When using in simultaneous operation system mode, change the SECOND CODE No. as shown in
Table 9.
• When using in simultaneous operation system mode, refer to "SIMULTANEOUS OPERATION SYSTEM
INDIVIDUAL SETTING" section to set master and slave units separately.
24
Summary of Contents for FCA71AV16
Page 34: ...33 RZCA71AV16...
Page 35: ...34 RZCA71AV16...
Page 36: ...35...
Page 37: ...36...
Page 38: ...37...
Page 39: ...38 RZCA71AV16...
Page 40: ...39 RZCA71AV16...
Page 41: ...40...
Page 42: ...41...
Page 43: ...42 RZCA71AV16 RZCA71AV16 20 g per meter For Piping Length Exceeding 10 m RZCA71AV16...
Page 44: ...43 45...
Page 45: ...44 RZCA71AV16 RZCA71AV16...
Page 46: ...45 RZCA71AV16 RZCA71AV16 Power Supply 50 Hz 230 V...
Page 47: ...46...
Page 50: ...49...
Page 51: ...50 RZCA71AV16...