11. FIELD SETTING
<<Refer to also the installation manual attached to the outdoor unit.>>
-it
CAUTION-----------------------
Before carrying out field setting, check the items mentioned in the clause 2
"1. Items to be checked
after completion of work"
on page 4.
• Check if all the installation and piping works for the air conditioner are completed.
• Check if the control box lids of the air conditioner are closed.
< FIELD SETTING FOR WIRED REMOTE>
<<After turn on the power supply, carry out field setting from the remote controller according to the
installation state.>>
• Carry out setting at 3 places, "Mode No.", "FIRST CODE No." and "SECOND CODE No.".
The settings shown by
"I I"
in the table indicate those when shipped from the factory.
• The method of setting procedure and operation is shown in the installation manual attached to the remote
controller.
(Note) Though setting of "Mode No." is carried out as a group, if you intend to carry out individual setting
by each indoor unit or confirmation after setting, carry out setting with the Mode No. shown in the
parenthesis ( ).
• In case of remote control, for changeover of input to FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the field setting mode with the remote controller.
[2] Select Mode No. "12".
[3] Set the FIRST CODE No. to "1".
[4-1] For FORCE OFF, set the SECOND CODE No. to "01".
[4-2] For ON/OFF OPERATION, set the SECOND CODE No. to "02".
(It is set to FORCE OFF when shipped from the factory.)
• Ask your customer to keep the manual attached to the remote controller together with the operation
manual.
• Do not carry out settings other than those shown in the table.
NOTE:
For wireless remote field setting kindly refer the Remote manual.
11-1 SETTING CEILING HEIGHT
• Set the SECOND CODE No. according to the ceiling height as shown in the
Table 6.
Table6
�
I
Standard • All round outlet
Cl
·a;
High ceiling 1
.c
Cl
·a;
High ceiling 2
0
Note:
FCA-AV
16
s.2.7
2.7- 3
3 - 3.5
1. "Mode No." setting is done in a batch for the group.
Mode No.
FIRST
Note) 1
CODE No.
13
(23)
0
SECOND
CODE No.
01
02
03
To make or confirm settings for an individual unit, set the internal mode number in parentheses.
2. The figure of the ceiling height is for the all round outlet.
For the settings for four-direction (part of corner closed off), three-direction and two-direction outlets,
see the installation manual and technical guide supplied with the separately sold closure material kit.
11-2 SETTING AIR DISCHARGE DIRECTION
• Refer to the installation manual attached to the sealing material of air discharge outlet sold separately
and engineering data book, for ceiling height settings for four-direction (part of corner closed off) and
three-direction.
(The SECOND CODE No. is factory set to "01" (all round outlet) before shipping.)
23
71
type
Summary of Contents for FCA71AV16
Page 34: ...33 RZCA71AV16...
Page 35: ...34 RZCA71AV16...
Page 36: ...35...
Page 37: ...36...
Page 38: ...37...
Page 39: ...38 RZCA71AV16...
Page 40: ...39 RZCA71AV16...
Page 41: ...40...
Page 42: ...41...
Page 43: ...42 RZCA71AV16 RZCA71AV16 20 g per meter For Piping Length Exceeding 10 m RZCA71AV16...
Page 44: ...43 45...
Page 45: ...44 RZCA71AV16 RZCA71AV16...
Page 46: ...45 RZCA71AV16 RZCA71AV16 Power Supply 50 Hz 230 V...
Page 47: ...46...
Page 50: ...49...
Page 51: ...50 RZCA71AV16...