background image

Operation manual

13

EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

2

Press the 

h

 key to enter the next screen of the readout menu.

This screen of the readout menu provides the following
information on the evaporator:

M1: OUTLWATER

: actual outlet water temperature of module 1.

M2: OUTLWATER

: actual outlet water temperature of module 2.

M3: OUTLWATER

: actual outlet water temperature of module 3.

3

Press the 

h

 key to enter the next screen of the readout menu.

The 

COMPRESSOR STATUS

  screen of the readout menu provides

information concerning the status of the different compressors.

C11

: actual status of compressor 1 of module 1.

C12

: actual status of compressor 2 of module 1.

C21

: actual status of compressor 1 of module 2.

C22

: actual status of compressor 2 of module 2.

C31

: actual status of compressor 1 of module 3.

C32

: actual status of compressor 2 of module 3.

When a circuit is OFF, the following status information may
appear.

SAFETY ACTIVE

:  one of the circuit safety devices is activated

(refer to the chapter 

"Troubleshooting" on page 19

).

(LIMIT)

: the circuit is limited by a remote contact.

TIMERS BUSY

: the actual value of one of the software timers is

not zero (refer to the 

"Timers menu" on page 15

).

CAN STARTUP:

  the circuit is ready to start up when extra

cooling load is needed.

The preceding OFF messages are written down in order of priority. If
one of the timers is busy and one of the safeties is active, the status
information says 

SAFETY ACTIVE

.

4

Press the 

h

 key to enter the next screen of the readout menu.

To consult actual operational information about the total running
hours of the compressors.

Selecting cooling or heating operation

The "cooling/heating" menu allows the user to set the unit in cooling
or heating operation.

The 

COOL/HEAT

  menu provides information concerning the selected

operation mode.

COOLING (EVAP)

:  cooling mode. The two setpoints for inlet

water temperature control of the evaporator can be used.

HEATING (COND)

:  heating mode. The two setpoints for inlet

water temperature control of the condenser can be used.

To define cooling/heating operation, proceed as follows:

1

Enter the cooling/heating menu through the main menu. (Refer
to the chapter 

"Main menu" on page 14

.)

2

Position the cursor behind 

MODE

 using the 

q

 key.

3

Select the appropriate setting using the 

and

 h 

keys.

4

Press 

q

 to confirm.

The cursor returns to the upper left corner of the screen.

Adjusting the temperature setpoint

The unit provides definition and selection of four or two independent
temperature setpoints.

In cooling operation, two setpoints are reserved for inlet control of the
evaporator.

INLSETP 1 E

: inlet water temperature of evaporator, setpoint 1,

INLSETP2 E

: inlet water temperature of evaporator, setpoint 2.

In heating operation, two setpoints are reserved for inlet control of the
condenser.

INLSETP 1 C

: inlet water temperature of condenser, setpoint 1,

INLSETP 2 C

: inlet water temperature of condenser, setpoint 2.

In double thermostat operation, two setpoints are reserved for inlet
control of the evaporator and two others are reserved for inlet control
of the condenser.

INLSETP 1 E

: inlet water temperature of evaporator, setpoint 1,

INLSETP2 E

: inlet water temperature of evaporator, setpoint 2.

INLSETP 1 C

: inlet water temperature of condenser, setpoint 1,

INLSETP 2 C

: inlet water temperature of condenser, setpoint 2.

The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.

If the manual control mode is selected (refer to 

"User settings menu"

on page 14

), none of the above-mentioned setpoints will be active.

To adjust a setpoint, proceed as follows:

1

Enter the setpoints menu through the main menu. (Refer to the
chapter 

"Main menu" on page 14

).

If the user password is disabled for setpoint modifications (refer
to the 

"User settings menu" on page 14

), the controller will

immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the 

and

  h

  keys.  (Refer to the 

"User

password menu" on page 16

). Press 

q

 to confirm the password

and to enter the setpoints menu.

2

Select the setpoint to be adjusted using the 

q

 key.

A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The "

>

" sign indicates the actual active temperature setpoint.

3

Press the 

g

 and 

h

 keys to adjust the temperature setting.

The default, limit and step values for the cooling (evaporator)
and heating (condenser) temperature setpoints are:

4

Press 

q

 to save the adjusted temperature setpoint.

When the setting has been confirmed, the cursor switches to the
next setpoint.

5

To adjust other setpoints, repeat from instruction 2 onwards.

Resetting the unit

The units are equipped with three kinds of safety devices: unit
safeties, module safeties and network safeties.

When a unit safety occurs, all compressors are shut down. The
safeties menu will indicate which safety is activated. The 

COMPRESSOR

STATUS

 screen of the readout menu will indicate 

OFF - SAFETY ACTIVE

for all circuits. The red LED inside the 

p

 key lights up and the buzzer

inside the controller is activated.

When a module safety occurs, the compressors of the corresponding
module are shut down. The 

COMPRESSOR STATUS

  screen of the

readout menu will indicate 

OFF - SAFETY ACTIVE

  for the module

concerned. The red LED inside the 

p

 key lights up and the buzzer

inside the controller is activated.

If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.

IIIIN

N

N

NL

L

L

LS

S

S

SE

E

E

ET

T

T

TP

P

P

P    IIIIN

N

N

N    E

E

E

E

IIIIN

N

N

NL

L

L

LS

S

S

SE

E

E

ET

T

T

TP

P

P

P    IIIIN

N

N

N    C

C

C

C

default value

12°C

30°C

limit values

(a)

(a) For glycol units the lower limit of the cooling temperature setpoint can be 

adapted in the factory. The following values apply:

INLSETP IN E/C

: 5°C, 3°C, –2°C, –7°C

8

 --> 

23°C

15

--> 

50°C

step value

0.1°C

0.1°C

NOTE

Also consult 

"Defining the schedule timer" on page 17

.

Summary of Contents for EWWP045KAW1M

Page 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Page 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Page 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Page 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Page 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Page 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Page 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Page 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Page 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Page 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Page 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Page 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Page 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Page 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Page 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Page 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Page 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Page 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Page 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Page 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Page 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Page 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Page 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Page 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Page 25: ...NOTES NOTES...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Reviews: