Operation manual

11

EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

Selecting local or remote on/off control

User parameter 

h7

  in combination with the remote on/off switch

(installed by the customer) allows the user to switch the unit on
without using the 

I

 or 

Y

 key on the controller.

When user parameter 

h7

 is set to 

0

 (= No), the unit can only be

switched on by means of the 

I

 or 

Y

 key on the controller.

When user parameter 

h7

  is set to 

1

  (= Yes), the unit can be

switched on by means of the remote on/off switch and the 

I

 or

Y

 key on the controller.

To select local or remote on/off control, proceed as follows:

1

Enter the list of user parameters.

Parameter code 

:d

 appears on the display.

2

Select parameter code 

h7

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

 key to switch to the parameter value.

4

Select the appropriate setting using the 

A

 and/or 

Z

 key.

5

Press the 

R

 key to return to the list of parameter codes.

6

To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

7

To  save the modifications, press the 

E

  key.  To  cancel the

modifications wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of user

parameters without saving the modifications. The inlet water
temperature reappears on the display.

Locking the controller keyboard

Once user parameter 

h9

 is set to 

0

, the following advanced features

can no longer be carried out by means of the controller:

modifying direct and user parameters (parameters can be
displayed but not modified),

selecting cooling or heating mode,

resetting the timers.

When user parameter 

h9

 is set to 

1

, the above-described advanced

features can be carried out using the controller.

To lock or unlock the controller keyboard, proceed as follows:

1

Enter the list of user parameters.

Parameter code 

:d

 appears on the display.

2

Select parameter code

 

 

h9

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

 key to switch to the parameter value.

4

Select the appropriate setting using the 

A

 and/or 

Z

 key.

5

Press the 

R

 key to return to the list of parameter codes.

6

To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

7

To  save the modifications, press the 

E

  key.  To  cancel the

modifications wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of user

parameters without saving the modifications. The inlet water
temperature reappears on the display.

Defining the unit's serial address

To  control the unit from a supervisory system, an address card
(optional module) should be installed in the unit. The unit's serial
address required for communication with the supervisory system is
defined by parameter 

ha

.  The default, limit and step values for the

serial address are:

Default value

1

 

Limit values

1

  to 

16

Step value

1

To define the unit's serial address, proceed as follows:

1

Enter the list of user parameters.

Parameter code 

:d

 appears on the display.

2

Select parameter code 

ha

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

 key to switch to the parameter value.

4

Select the appropriate setting using the 

A

 and/or 

Z

 key.

5

Press the 

R

 key to return to the list of parameter codes.

6

To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

7

To  save the modifications, press the 

E

  key.  To  cancel the

modifications wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.

8

In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of user

parameters without saving the modifications. The inlet water
temperature reappears on the display.

Key on the controller

Remote On/off switch

UNIT RESULT

ON

ON

ON

ON

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

Summary of Contents for EWWP045KAW1M

Page 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Page 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Page 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Page 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Page 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Page 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Page 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Page 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Page 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Page 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Page 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Page 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Page 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Page 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Page 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Page 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Page 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Page 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Page 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Page 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Page 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Page 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Page 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Page 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Page 25: ...NOTES NOTES...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Reviews: