background image

EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

Operation manual

16

User password menu

Cooling/heating menu

Tasks of the user settings menu

Entering the user settings menu

The user settings menu is protected by the user password, a 4-digit
number between 

0000

 and 

9999

.

1

Enter the 

USERSETTINGS MENU 

through the main menu

.

  (Refer to

the chapter 

"Main menu" on page 14

).

The controller will request the password.

2

Enter the correct password using the 

and

 h

 keys.

3

Press 

q

 to confirm the password and to enter the user settings

menu.

The controller automatically enters the first screen of the user
settings menu.

To define settings of a certain function:

1

Go to the appropriate screen of the usersettings menu using the

and

 h

 keys.

2

Position the cursor behind the parameter to be modified using
the 

q

 key.

3

Select the appropriate setting using the 

and

 h

 keys.

4

Press 

q

 to confirm the selection.

When the selection has been confirmed, the cursor switches to
the next parameter which can now be modified.

5

Repeat from instruction 2 onwards to modify the other
parameters.

Defining and activating the control mode

The unit is equipped with a thermostat which controls the cooling
capacity of the unit. Two different control modes exist:

manual control mode: the operator controls the capacity himself

MANUAL CONTROL

inlet control mode: uses the evaporator and/or condenser
entering water temperature to control the capacity of the unit -

INLET WATER

When the operator wants to control the capacity himself, he can
activate manual control mode using the 

CONTROL SETTINGS

  screen of

the user settings menu. In this case, he has to define the following
parameters:

MODE

 (present mode): manual control.

C11

C12

C21

C22

C31

C32

  (compressor status of module 1, 2

and 3 in manual mode or capacity limitation value in case the
"capacity limitation remote contact" is enabled): 

ON

 or 

OFF

.

Defining the thermostat settings

When automatic control mode is selected, the unit uses a thermostat
to control the cooling or heating capacity. The maximum number of
thermostat steps are as listed:

However, the thermostat parameters are not fixed and can be
modified via the 

THERMOST. SETTINGS

 screen of the user settings menu.

The default, limit and step values for the thermostat parameters are:

Defining the lead-lag mode

The lead/lag mode determines which module starts up first in case of
a capacity demand.

The lead-lag parameters are:

LEAD-LAG MODE

Automatic: the controller decides whether module 1, module 2,
or module 3 starts up first.
The modules follow the entered order of starting up (see table
below).

LEAD-LAG HOURS

:  In the automatic mode, the number of hours

indicated on the display is the maximum difference between the
running hours of the modules. This value is important for main-
tenance purposes. It should be set high enough so that the
modules do not require maintenance at the same time and that
at least one module can remain constantly active.
The lower and upper limits are 100 and 1000 hours respectively.
The default value is 1000 hours.

Defining the pump control settings

The 

PUMPCONTROL

 screen of the user settings menu allows the user to

define the pump-leadtime and pump-lagtime.

PUMPLEADTIME

:  used to define the time that the pump must run

before the unit can start up.

PUMPLAGTIME

:  used to define the time that the pump keeps

running after the unit has been stopped.

Defining the display settings

The 

DISPLAY SETTINGS

  screen of the user settings menu allows the

user to define the choice of language, time and date.

LANGUAGE

:  used to define the language of the displayed

information of the controller.

TIME

: used to define the present time.

DATE

: used to define the present date.

To  check the status of the change-
able relay output.

To change the user password.

To select cooling or heating mode.

NOTE

To  activate manual control mode, select 

MANUAL

  as

present mode. To deactivate the manual control mode,
select 

INLET WATER

 as present mode.

BW

           CHANG.  REL  OUTPUTS

DO1  REV.VALVE(C/H)  : O

B

                    CHANGE PASSWORD

NEW PASSWORD : 0000

             CONFIRM : 0000

B

                      COOLING/HEATING

MODE :  COOLING (EVAP)

32Hp

4

48Hp

4

64Hp

6

36Hp

4

52Hp

6

68Hp

6

40Hp

4

56Hp

6

72Hp

6

44Hp

4

60Hp

6

Lower limit

Upper limit

Step

Default

STPL (°C)

0.4

2.0

0.1

1.5

STEPDIFFERENCE (°C)

0.2

0.8

0.1

0.5

LOADUP (sec)

15

300

1

180

LOADDOWN (sec)

15

300

1

20

NOTE

A functional diagram showing the thermostat parame-
ters can be found in 

"Annex I" on page 21

.

3 modules

2 modules

first

>

next

>

last

first

>

last

1

2

3

1

2

2

3

1

2

1

3

1

2

NOTE

If a module is de-activated due to a failure, the next
module will start up instead.

Summary of Contents for EWWP045KAW1M

Page 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Page 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Page 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Page 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Page 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Page 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Page 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Page 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Page 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Page 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Page 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Page 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Page 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Page 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Page 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Page 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Page 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Page 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Page 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Page 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Page 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Page 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Page 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Page 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Page 25: ...NOTES NOTES...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Reviews: