background image

EWWD440~850AAYNNO**
Packaged water-cooled water chillers
4PW25558-1B

Installation and operation manual

33

T

ROUBLESHOOTING

This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.

Following cases do not represent an abnormality

Before starting the troubleshooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.

Before contacting your local dealer, read this chapter carefully, it will
save you time and money.

When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no
circumstances safety devices may be bridged or changed to a value
other than the factory setting. If the cause of the problem cannot be
found, call your local dealer.

Symptom 1: Pump and compressor do not start at all

Symptom 2: Pump starts but water does not circulate

Symptom 3: Pump starts but compressor does not start

Symptom 4: Water outlet temperature is extremely low or high

Symptom 5: Compressor stops while operating and does not start 
automatically

Symptom 6: Remote operation is not available

Symptom 7: Although chilled water temperature is high, one side 
compressor only starts

S

YMPTOM

P

OSSIBILE

 

CAUSES

While stop, compressor is hot.
(Chiller electrified)

Because oil heater is electrified to 
warm up compressor for the purpose 
of smoothing starting of unit, this is 
not abnormality.

When the unit is operating under low 
load condition, refrigerant passage 
sound is heard from liquid piping 
section.

This is because a slight quantity of 
refrigerant gas flows from the 
condenser to the evaporator under 
partial load operation. This is not 
abnormality.

When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Power failure

For reason of safety, turn OFF power 
switch once.

Power switch OFF

Turn ON power switch.

Power fuse burned

Replace power fuse.

Defective bridge wiring between unit 
and pump

Check respective bridge wiring of 
pump operation command and 
interlock signal for omission of 
connection and defective contact.

Defective input of operation 
command

Check bridge wiring of remote 
operation command for omission of 
connection and defective 
connection.
When instantaneous signal is used, 
arrange pulse width to be 200 msec 
or more.

"LOCAL"/"REMOTE" of unit Run/
Stop has switched

Make selection "LOCAL" or 
"REMOTE" in "OPERATION" screen 
of the graphic panel display.
Especially if you cause the unit to 
stop by "STOP" button on the switch 
box during remote operation, 
selection in control screen shifts 
from "REMOTE" to "LOCAL" 
automatically, so be careful.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Lack of water quantity of makeup 
water 

Pour makeup water sufficiently. 
(Pumping is not performed unless 
otherwise pump and suction pipe are 
filled with water.)

Pump rotates in reverse direction

Correct the direction of rotation of 
pump. (Make it to clockwise direction 
viewed from motor side).

Valve in piping does not open 
sufficiently

Open valve in piping sufficiently.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Defective interlock signal

Arrange in a manner that the 
interlock signal is returned to the unit 
within 180 seconds after input of 
operation signal to the unit.

ON-OFF limiting

Compressor starts after ON-OFF 
limiting time ends. (See 

"ON-OFF 

limiting function" on page 22

).

Thermo in stop

Compressor starts if thermo is reset. 
(See 

"Low load stop (Thermo off)" 

on page 21

).

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water quantity regulating valve has 
not opened

Open water quantity valve 
moderately.

Input error of target temperature 
setting

Input correct target temperature 
(See 

"Low load stop (Thermo off)" 

on page 21

).

Erroneous input of operation mode 
(Model with 2-temperature setting 
option only)

Stop unit once then input correct 
operation mode (See 

"Operation 

screen" on page 14

).

It takes maximum 1 second from 
time when unit accepts operation 
mode signal to time when mode is 
confirmed. Operation signal and 
mode signal shall be input with time 
difference.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water quantity regulating valve has 
not opened

Open water quantity regulating valve 
moderately.

Differential set point between thermo 
stop and thermo reset is big

Decrease differential set point (See 

"Low load stop (Thermo off)" on 
page 21

).

Compressor individual error is 
occured (Pertinent compressor only 
stops)

Check indication on details of error 
on graphic panel display and then 
contact your dealer.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

Defective input of operation 
command

Check bridge wiring of remote 
operation command for omission of 
connection and defective contact.
When you use instantaneous signal, 
200 msec or more of pulse width is 
required.

"LOCAL"/"REMOTE" of unit Run/
Stop has switched

Make selection "LOCAL" or 
"REMOTE" in "OPERATION" screen 
of the graphic panel display.
Especially if you cause the unit to 
stop by "STOP" button on the switch 
box during remote operation, 
selection in control screen shifts 
from "REMOTE" to "LOCAL" 
automatically, so be careful.

P

OSSIBILE

 

CAUSES

C

ORRECTIVE

 

ACTION

"UNITS TO CONTROL" setting in 
graphic panel display is set to 
"1UNIT".

Change setting in the left to 
"2UNITS". (See 

"Compressor 

starting order rotation function" on 
page 24

)

Summary of Contents for EWWD440AAYNNO series

Page 1: ...INSTALLATION AND OPERATION MANUAL EWWD440AAYNNO EWWD600AAYNNO EWWD850AAYNNO Packaged water cooled water chillers...

Page 2: ...03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere...

Page 3: ...ue 36 Thank you for purchasing this Daikin air conditioner SAFETY CONSIDERATIONS For your safety and that of others observe the precautions listed here after at all time There are two types of precaut...

Page 4: ...ould result in a lack of oxygen in the latter case Make sure there is enough service space If the space is not enough maintenance work cannot be carried out safely and could result in any injuries Pre...

Page 5: ...am above Have the lifting beam 1 and 4 wire ropes prepared 2 Make sure that wire ropes are longer than 5 m Be sure to lift the unit horizontally levelled The unit is shipped with transport stays under...

Page 6: ...r 2 Evaporator 17 Condenser entering water temperature sensor 3 Condenser 18 Air purge evaporator 4 Switchbox 19 Water drain evaporator 5 Air purge condenser 20 Emergency stop 6 Water drain condenser...

Page 7: ...S LP B M1C M2C A 14 B 13 23 1 Compressor 15 Stop valve 2 Service valve 16 Service valve 3 Male connector 17 Suction stop valve 4 Stop valve 18 Stop valve 5 Solenoid valve 19 Filter drier 6 Filter 20...

Page 8: ...relative humidity of 90 or more Mounting this product at places where the temperature variation per hour exceeds 8 C or more is also inappropriate If you use this product in cold climates consideratio...

Page 9: ...the isolation of vibration by using expansion joints immediately near the unit Perform the vibration isolation in function of the installation site This machine comes with vibration isolation pads and...

Page 10: ...nd maintenance provide valves for release to atmosphere drain off valves and valves for chemical cleaning between stopvalves provided in the water piping system and the unit body For drain off valves...

Page 11: ...rrosion due to electric corrosion may occur If piping is to be put underground be extremely careful and take dust preventive measures Avoid execution of piping in such a way that a draft line is forme...

Page 12: ...e display H3P Indication lamp common error remote display H4P H5P Indication lamp compressor error 1 2 remote display H6P Indication lamp condenser water pump run stop H7P Indication lamp chiller wate...

Page 13: ...tor yellow green to the earthing terminal PE Interconnection cables Voltage free contacts The controller is provided with some voltage free contacts to indicate the status of the unit These voltage fr...

Page 14: ...tion is performed during 30 minutes In case of errors History screen Predictive maintenance history Alarm screen Alarm screen Alarm history Menu screen Operational data history in case of unit errors...

Page 15: ...hic panel display shuts off automatically if no operation is made to the graphic panel display since 30 minutes Touching any part of the screen while the graphic panel display is shut off makes the sc...

Page 16: ...y means of operation and stop buttons on the door of the switch box select this button 1 When LOCAL is selected select the operation mode with these buttons Buttons are disabled when REMOTE is selecte...

Page 17: ...s correct before touching the ENT button 5 Touch the CLOSE button to close the keypad Repeat steps 1 5 to change other settings History screen In this screen you can consult the alarm history and pred...

Page 18: ...screen 5 Select OPE DATA WHEN ERROR OCCURRED from the HISTORY screen 6 Record the listed 6 minutes data 7 Return to the MENU screen 8 Select the ALARM screen from the MENU screen 9 Return to the above...

Page 19: ...hine label Make sure that the frequency is within 2 of the value stated in machine label The voltage imbalance level among 3 phases must be within 2 of the rated voltage In order to avoid compressor d...

Page 20: ...Checking the unit body Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPERATION All stopvalves except those for charging of refrigerant or oil must be opened prior to start...

Page 21: ...ing full load operation Normally select 2UNITS 2 In this field you need to set the compressor that starts first after power up of the unit 1 is the left side viewed compressor from the front of the sw...

Page 22: ...NOTE This is the screen of models with 2 temperature setting option In the screen for standard models the field for cooling mode selection does not appear Selection must be made while the unit is stop...

Page 23: ...function that allows the compressor to suspend its operation automatically when the chiller water outlet temperature has lowered beyond a certain limit When the chiller water temperature rises the op...

Page 24: ...Cooling of the compressor motor is performed by suction refrigerant gas However if the compressor repeats Run Stop frequently the cooling effect of the suction refrigerant gas decreases and the motor...

Page 25: ...sor operation current to a predetermined current value instead of to the Maximum Load Amps of the compressors Set the demand value relative to the reference current value on the graphic panel display...

Page 26: ...this model setting of 2 target temperatures is available on condition that switching of target temperatures of the unit is available We distinguish target temperature for thermal storage mode and for...

Page 27: ...et temperature for chilled water 2 When thermal storage mode is selected the setpoint in SET TEMP IN HEAT STORAGE COOLING is the target temperature for chilled water NOTE Mode change is not available...

Page 28: ...st is under ON OFF limiting Opening 1 opening 2 0 Cooling water pump operation command ON Hot water pump operation command ON YES NO Pump interlock ON YES Compressor to start first operation ON This i...

Page 29: ...error 2 If the interlock contact does not turn ON within 180 seconds after the pump operation command is output from the unit 88WEX 88WCX the pump interlock error is confirmed unit error 3 For ensurin...

Page 30: ...mal stop request Abnormal stop To low load stop Residual set time 360 seconds elapsed Chilled water pump operation command OFF Cooling water hot water pump operation command OFF Stop due to normal sto...

Page 31: ...ut and the operation command is destroyed If contacts disconnect for 5 seconds in a row during normal operation to the same unit error is confirmed OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON 1 3 2 4 5...

Page 32: ...nd refrigerant piping Doing so could result in skin burning Do not attempt to run the compressor by pushing the magnetic contactor with your finger Doing so could result in electrical shock or fire 1...

Page 33: ...eginning mixing of air into the system may occur Perform on air purge at regular intervals Perform cleaning of the inside of the condenser and evaporator when needed Depending on operation conditions...

Page 34: ...is low and preliminary electrification time to the unit is short abnormal sound may occur at first time start of the compressors If abnormal sound lasts for 5 seconds or more after starting of compre...

Page 35: ...phic panel display Especially if you cause the unit to stop by STOP button on the switch box during remote operation selection in control screen shifts from REMOTE to LOCAL automatically so be careful...

Page 36: ...e When operating condition falls outside of recommended operation range in some cases capacity control load may have been adjusted for the protection of unit forcedly Discharge superheat level is low...

Page 37: ...TIVATION Disorder of sensor alone Inadequate insertion of PLC connection connector Disconnection or short circuit of chilled water outlet temperature sensor 1 Discharge gas 1 or 2 high temperature err...

Page 38: ...bonate gas and oxygen in open systems HOW TO CONTINUE Fill out the brief operation instructions form and fix it visibly near the operating site of the refrigeration system NOTES Item Details Power sup...

Page 39: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 40: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25558 1B...

Reviews: