EWWD440~850AAYNNO**
Packaged water-cooled water chillers
4PW25558-1B

Installation and operation manual

23

Namely,

1.

If the operating time of the compressor immediately before stop is
420 seconds or more: ON-OFF limiting time is 180 seconds.

2.

If the operating time of the compressor immediately before stop is
less than 420 seconds: ON-OFF limiting time becomes [600–
operating time of the compressor immediately before stop] seconds.

ON-OFF limiting time immediately after power-up to the control
circuit of the unit becomes 180 seconds.

Do not try to shorten the ON-OFF limiting time by turning the
circuit breaker of the control circuit ON and OFF after stop of the
unit.

Current limiting function

When the condenser water temperature is high or adhesion of
contamination to the inside of the condenser heat exchanger tubes is
large, the operating current of the unit increases.

This function is for optimization of the cooling capacity in relation to
protection of electrical components such as the compressor motor,
even under conditions of high current values.

If the operating current of the individual compressor exceeds the
Maximum Load Amps, this function forcedly performs the capacity
control of the compressor until the operating current reaches the
Maximum Load Amps or less.

If only one compressor out of 2 exceeds the Maximum Load Amps,
the capacity control is performed on the compressor that exceeds the
Maximum Load Amps only.

Because the unit shifts to partial load operation due to working of this
function, the cooling capacity reduces. Abnormal stops however, due
to activation of safety devices such as overcurrent relays, do not
occur and continuous operation of the unit is available. See 

"Figure:

Current limiting function/Current demand function" on page 23

.

Current demand function

For sites where you want to benefit from the capacity of an entire
system (=with several units), it is possible to limit and to control the
operation current of each unit individually.

For automatic capacity control of the entire system, this function
enables you to set the upper limit value of the compressor operation
current to a predetermined current value, instead of to the Maximum
Load Amps of the compressors.

Set the demand value (% relative to the reference current 
value) on the graphic panel display
["MENU" 

 "SETTING" 

 "SETTING (1/2)"]

This function takes effect only when the remote signal for current
demand stays ON. See 

"Figure: Current limiting function/Current

demand function" on page 23

.

Table 3

Figure: Current limiting function/Current demand function

CAUTION

Do not try to shorten the ON-OFF limiting time by
turning the circuit breaker of the control circuit ON and
OFF.

It may lead to abnormal stops due to overheat of the motor.

Reference current value per 

compressor (A)

Model

Hz

Standard

EWWD440

50

  91

EWWD600

50

128

EWWD850

50

173

NOTE

Standard voltage of this model is 400 V. 

Because this model has 2 compressors, the
actual maximum operating current of the unit is
the value in table above x2.

1

Forced load up area (to stabilize the motor cooling)

2

Reference current A1

3

Demand current A2=A1xB (current demand setpoint B (%))

4

Operating current

Automatic capacity control range when current demand function is 
ON

Automatic capacity control range when current demand function is 
OFF

Current limiting function is active

5

The operating current of the compressor increases (before 
activation of the current limiting function or the current demand 
function)

6

The operating current of the compressor increases (after 
activation of the current limiting function or the current demand 
function)

7

Reference current A1 or Demand current A2 (=A1xB)

8

Reference current A1x0.95 or Demand current A2x0.95

9

Operating current per compressor

Automatic capacity control (up/down/stop)

Load up not allowed

Forced load down

NOTE

In the current demand function, setting of the
value between 0 and 100% is available.

For obtaining a state motor cooling, capacity
control only starts when a certain operating
current of compressors is reached (after forced
load up).

For this reason, it is possible that in case of a too
low current demand setpoint B, the actual current
value does not decrease to the level of the
calculated current demand but remains above A2.
Be aware that, depending on the operation
condition, the minimum operating current value
must be 30 to 40% of the current at full load
operation.

0(A)

1

4

B(%)

3

2

5

6

8

7

9

Summary of Contents for EWWD440AAYNNO series

Page 1: ...INSTALLATION AND OPERATION MANUAL EWWD440AAYNNO EWWD600AAYNNO EWWD850AAYNNO Packaged water cooled water chillers...

Page 2: ...03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere...

Page 3: ...ue 36 Thank you for purchasing this Daikin air conditioner SAFETY CONSIDERATIONS For your safety and that of others observe the precautions listed here after at all time There are two types of precaut...

Page 4: ...ould result in a lack of oxygen in the latter case Make sure there is enough service space If the space is not enough maintenance work cannot be carried out safely and could result in any injuries Pre...

Page 5: ...am above Have the lifting beam 1 and 4 wire ropes prepared 2 Make sure that wire ropes are longer than 5 m Be sure to lift the unit horizontally levelled The unit is shipped with transport stays under...

Page 6: ...r 2 Evaporator 17 Condenser entering water temperature sensor 3 Condenser 18 Air purge evaporator 4 Switchbox 19 Water drain evaporator 5 Air purge condenser 20 Emergency stop 6 Water drain condenser...

Page 7: ...S LP B M1C M2C A 14 B 13 23 1 Compressor 15 Stop valve 2 Service valve 16 Service valve 3 Male connector 17 Suction stop valve 4 Stop valve 18 Stop valve 5 Solenoid valve 19 Filter drier 6 Filter 20...

Page 8: ...relative humidity of 90 or more Mounting this product at places where the temperature variation per hour exceeds 8 C or more is also inappropriate If you use this product in cold climates consideratio...

Page 9: ...the isolation of vibration by using expansion joints immediately near the unit Perform the vibration isolation in function of the installation site This machine comes with vibration isolation pads and...

Page 10: ...nd maintenance provide valves for release to atmosphere drain off valves and valves for chemical cleaning between stopvalves provided in the water piping system and the unit body For drain off valves...

Page 11: ...rrosion due to electric corrosion may occur If piping is to be put underground be extremely careful and take dust preventive measures Avoid execution of piping in such a way that a draft line is forme...

Page 12: ...e display H3P Indication lamp common error remote display H4P H5P Indication lamp compressor error 1 2 remote display H6P Indication lamp condenser water pump run stop H7P Indication lamp chiller wate...

Page 13: ...tor yellow green to the earthing terminal PE Interconnection cables Voltage free contacts The controller is provided with some voltage free contacts to indicate the status of the unit These voltage fr...

Page 14: ...tion is performed during 30 minutes In case of errors History screen Predictive maintenance history Alarm screen Alarm screen Alarm history Menu screen Operational data history in case of unit errors...

Page 15: ...hic panel display shuts off automatically if no operation is made to the graphic panel display since 30 minutes Touching any part of the screen while the graphic panel display is shut off makes the sc...

Page 16: ...y means of operation and stop buttons on the door of the switch box select this button 1 When LOCAL is selected select the operation mode with these buttons Buttons are disabled when REMOTE is selecte...

Page 17: ...s correct before touching the ENT button 5 Touch the CLOSE button to close the keypad Repeat steps 1 5 to change other settings History screen In this screen you can consult the alarm history and pred...

Page 18: ...screen 5 Select OPE DATA WHEN ERROR OCCURRED from the HISTORY screen 6 Record the listed 6 minutes data 7 Return to the MENU screen 8 Select the ALARM screen from the MENU screen 9 Return to the above...

Page 19: ...hine label Make sure that the frequency is within 2 of the value stated in machine label The voltage imbalance level among 3 phases must be within 2 of the rated voltage In order to avoid compressor d...

Page 20: ...Checking the unit body Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPERATION All stopvalves except those for charging of refrigerant or oil must be opened prior to start...

Page 21: ...ing full load operation Normally select 2UNITS 2 In this field you need to set the compressor that starts first after power up of the unit 1 is the left side viewed compressor from the front of the sw...

Page 22: ...NOTE This is the screen of models with 2 temperature setting option In the screen for standard models the field for cooling mode selection does not appear Selection must be made while the unit is stop...

Page 23: ...function that allows the compressor to suspend its operation automatically when the chiller water outlet temperature has lowered beyond a certain limit When the chiller water temperature rises the op...

Page 24: ...Cooling of the compressor motor is performed by suction refrigerant gas However if the compressor repeats Run Stop frequently the cooling effect of the suction refrigerant gas decreases and the motor...

Page 25: ...sor operation current to a predetermined current value instead of to the Maximum Load Amps of the compressors Set the demand value relative to the reference current value on the graphic panel display...

Page 26: ...this model setting of 2 target temperatures is available on condition that switching of target temperatures of the unit is available We distinguish target temperature for thermal storage mode and for...

Page 27: ...et temperature for chilled water 2 When thermal storage mode is selected the setpoint in SET TEMP IN HEAT STORAGE COOLING is the target temperature for chilled water NOTE Mode change is not available...

Page 28: ...st is under ON OFF limiting Opening 1 opening 2 0 Cooling water pump operation command ON Hot water pump operation command ON YES NO Pump interlock ON YES Compressor to start first operation ON This i...

Page 29: ...error 2 If the interlock contact does not turn ON within 180 seconds after the pump operation command is output from the unit 88WEX 88WCX the pump interlock error is confirmed unit error 3 For ensurin...

Page 30: ...mal stop request Abnormal stop To low load stop Residual set time 360 seconds elapsed Chilled water pump operation command OFF Cooling water hot water pump operation command OFF Stop due to normal sto...

Page 31: ...ut and the operation command is destroyed If contacts disconnect for 5 seconds in a row during normal operation to the same unit error is confirmed OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON 1 3 2 4 5...

Page 32: ...nd refrigerant piping Doing so could result in skin burning Do not attempt to run the compressor by pushing the magnetic contactor with your finger Doing so could result in electrical shock or fire 1...

Page 33: ...eginning mixing of air into the system may occur Perform on air purge at regular intervals Perform cleaning of the inside of the condenser and evaporator when needed Depending on operation conditions...

Page 34: ...is low and preliminary electrification time to the unit is short abnormal sound may occur at first time start of the compressors If abnormal sound lasts for 5 seconds or more after starting of compre...

Page 35: ...phic panel display Especially if you cause the unit to stop by STOP button on the switch box during remote operation selection in control screen shifts from REMOTE to LOCAL automatically so be careful...

Page 36: ...e When operating condition falls outside of recommended operation range in some cases capacity control load may have been adjusted for the protection of unit forcedly Discharge superheat level is low...

Page 37: ...TIVATION Disorder of sensor alone Inadequate insertion of PLC connection connector Disconnection or short circuit of chilled water outlet temperature sensor 1 Discharge gas 1 or 2 high temperature err...

Page 38: ...bonate gas and oxygen in open systems HOW TO CONTINUE Fill out the brief operation instructions form and fix it visibly near the operating site of the refrigeration system NOTES Item Details Power sup...

Page 39: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 40: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25558 1B...

Reviews: