EWWD440~850AAYNNO**
Packaged water-cooled water chillers
4PW25558-1B

Installation and operation manual

9

4.

Prevent from getting mixed air into the system

Install the air purge valves at proper positions so that the air
purge of the entire equipment system is possible.
Operation of units with air mixed may lead to deterioration in
performance, actuation of protective devices, or damage of
heat exchanger tubes.

Pay attention to the flow velocity inside the water system,
position of the expansion tank, and to the position of air
purges along the piping, so that cavitations do not occur.

This machine is designed on the precondition that circulating
water is used. Use of once-through water may lead to
damage of the heat exchanger tubes due to dissolved
oxygen or free carbonate in chiller water (hot water) systems.

When using the unit in a heat recovery application, additional
care must be taken that water flow rate does not get
excessive. In the same application, a deaeration treatment
unit must be installed.

Do not allow aeration along the cooling water system as
shown in the following diagram.
Aerating water causes the dissolved oxygen to increase, and
pollutants in the atmosphere condensed in the water cause
the water to become corrosive.

5.

Observing the operation range of the unit

Observe the maximum operating water pressure of the unit.

Pay attention so that the cooling water inlet temperature
reaches 25°C or more.
When you use the unit during intermediate season and
winter season, control the cooling water supply water
temperature by using a thermostat for the cooling water inlet
and a 3-way mixing valve.

Pull-down time of this machine (time required for cooling from
ordinary temperature to reach the recommended operating
range) is within 1 hour under no load condition.
Make sure to prevent the water flow from becoming to high.

To  assure proper operation of the unit a minimum water
volume is required in the system and the water flow through
the evaporator must be within the operation range as
specified in 

Table 2

Table 2: Minimum water volume

When it is impossible to secure the minimum holding water
quantity, increase of thermo differential value is required. For
how to change the differential value, see 

"Settings screen" on

page 14

  and 

"Target temperature and low load stop related

settings screen" on page 22

.

6.

Prevent corrosion of water piping and of the unit interior

Do not install the earth of the electric equipment to the water
piping. Corrosion due to electric corrosion may occur.

If piping is to be put underground, be extremely careful and
take dust preventive measures.

Avoid execution of piping in such a way that a draft line is
formed inside the condenser or evaporator while the unit is
operating or stops.

In case of semi hermetic chilled water system with a thermal
storage tank, perform periodic replacement of water and
cleaning and inspection of the bottom of the thermal storage
tank (once every 1 or 2 years).
A new concrete heat storage tank will give off ions, and it is
not seldom that pH of the heat storage tank water rises
above 10. If pH rises above the standard, the rate at which
copper corrodes increases. The water must be changed
before the pH reaches that level. 
If a heat storage tank is used for a prolonged period,
springing and leaking of water could occur due to cracks in
the heat storage tank. Water leaks pose no serious problem
for water quality, but if seawater or dirty underground water
springs, it could cause an outbreak of microorganisms in the
water of the heat storage tank, thus producing slime in the
system. It could also cause calcium carbonate to adhere.

Make sure to perform periodic water quality inspections,
especially as to water quality of the cooling water. Insufficient
water quality may result not only in performance deterioration
of the unit but also in damage to the heat exchanger tubes.

7.

Freeze-up protection

The complete water circuit, inclusive all piping, must be
insulated to prevent condensation and reduction of the
cooling capacity.

Protect the water piping against water freezing during winter
period (e.g. by using glycol solution or heatertape).

8.

Preventing excessive increase of chilled water and condenser
water temperature

1

Discharge pipe

2

Inlet pipe

Model

Minimum water 

volume (l)

Water quantity inside the 

evaporator (l)

EWWD440

2660

105

EWWD600

3710

110

EWWD850

5020

157

1

2

2

1

CAUTION

Use chilled (hot) water/cooling water that
complies with the water quality standard as in
chapter 

"Water quality specifications" on page 8

.

Deterioration of water quality may lead to water
leakage and damage to the heat exchanger tubes.

CAUTION

Do not confuse the connection of outlet and
inlet of the water piping.

Do not confuse the inlet and outlet of the
chilled water and connection position of the
condenser water.

Normal operation may get impossible.

It may lead to breakdown including freezing
fracture of heat exchanger tubes.

The water pressure should not exceed the maximum
working pressure of 10 bar.

NOTE

Provide adequate safeguards in the water circuit
to make sure that the water pressure will never
exceed the maximum allowable working pressure.

Summary of Contents for EWWD440AAYNNO series

Page 1: ...INSTALLATION AND OPERATION MANUAL EWWD440AAYNNO EWWD600AAYNNO EWWD850AAYNNO Packaged water cooled water chillers...

Page 2: ...03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere...

Page 3: ...ue 36 Thank you for purchasing this Daikin air conditioner SAFETY CONSIDERATIONS For your safety and that of others observe the precautions listed here after at all time There are two types of precaut...

Page 4: ...ould result in a lack of oxygen in the latter case Make sure there is enough service space If the space is not enough maintenance work cannot be carried out safely and could result in any injuries Pre...

Page 5: ...am above Have the lifting beam 1 and 4 wire ropes prepared 2 Make sure that wire ropes are longer than 5 m Be sure to lift the unit horizontally levelled The unit is shipped with transport stays under...

Page 6: ...r 2 Evaporator 17 Condenser entering water temperature sensor 3 Condenser 18 Air purge evaporator 4 Switchbox 19 Water drain evaporator 5 Air purge condenser 20 Emergency stop 6 Water drain condenser...

Page 7: ...S LP B M1C M2C A 14 B 13 23 1 Compressor 15 Stop valve 2 Service valve 16 Service valve 3 Male connector 17 Suction stop valve 4 Stop valve 18 Stop valve 5 Solenoid valve 19 Filter drier 6 Filter 20...

Page 8: ...relative humidity of 90 or more Mounting this product at places where the temperature variation per hour exceeds 8 C or more is also inappropriate If you use this product in cold climates consideratio...

Page 9: ...the isolation of vibration by using expansion joints immediately near the unit Perform the vibration isolation in function of the installation site This machine comes with vibration isolation pads and...

Page 10: ...nd maintenance provide valves for release to atmosphere drain off valves and valves for chemical cleaning between stopvalves provided in the water piping system and the unit body For drain off valves...

Page 11: ...rrosion due to electric corrosion may occur If piping is to be put underground be extremely careful and take dust preventive measures Avoid execution of piping in such a way that a draft line is forme...

Page 12: ...e display H3P Indication lamp common error remote display H4P H5P Indication lamp compressor error 1 2 remote display H6P Indication lamp condenser water pump run stop H7P Indication lamp chiller wate...

Page 13: ...tor yellow green to the earthing terminal PE Interconnection cables Voltage free contacts The controller is provided with some voltage free contacts to indicate the status of the unit These voltage fr...

Page 14: ...tion is performed during 30 minutes In case of errors History screen Predictive maintenance history Alarm screen Alarm screen Alarm history Menu screen Operational data history in case of unit errors...

Page 15: ...hic panel display shuts off automatically if no operation is made to the graphic panel display since 30 minutes Touching any part of the screen while the graphic panel display is shut off makes the sc...

Page 16: ...y means of operation and stop buttons on the door of the switch box select this button 1 When LOCAL is selected select the operation mode with these buttons Buttons are disabled when REMOTE is selecte...

Page 17: ...s correct before touching the ENT button 5 Touch the CLOSE button to close the keypad Repeat steps 1 5 to change other settings History screen In this screen you can consult the alarm history and pred...

Page 18: ...screen 5 Select OPE DATA WHEN ERROR OCCURRED from the HISTORY screen 6 Record the listed 6 minutes data 7 Return to the MENU screen 8 Select the ALARM screen from the MENU screen 9 Return to the above...

Page 19: ...hine label Make sure that the frequency is within 2 of the value stated in machine label The voltage imbalance level among 3 phases must be within 2 of the rated voltage In order to avoid compressor d...

Page 20: ...Checking the unit body Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPERATION All stopvalves except those for charging of refrigerant or oil must be opened prior to start...

Page 21: ...ing full load operation Normally select 2UNITS 2 In this field you need to set the compressor that starts first after power up of the unit 1 is the left side viewed compressor from the front of the sw...

Page 22: ...NOTE This is the screen of models with 2 temperature setting option In the screen for standard models the field for cooling mode selection does not appear Selection must be made while the unit is stop...

Page 23: ...function that allows the compressor to suspend its operation automatically when the chiller water outlet temperature has lowered beyond a certain limit When the chiller water temperature rises the op...

Page 24: ...Cooling of the compressor motor is performed by suction refrigerant gas However if the compressor repeats Run Stop frequently the cooling effect of the suction refrigerant gas decreases and the motor...

Page 25: ...sor operation current to a predetermined current value instead of to the Maximum Load Amps of the compressors Set the demand value relative to the reference current value on the graphic panel display...

Page 26: ...this model setting of 2 target temperatures is available on condition that switching of target temperatures of the unit is available We distinguish target temperature for thermal storage mode and for...

Page 27: ...et temperature for chilled water 2 When thermal storage mode is selected the setpoint in SET TEMP IN HEAT STORAGE COOLING is the target temperature for chilled water NOTE Mode change is not available...

Page 28: ...st is under ON OFF limiting Opening 1 opening 2 0 Cooling water pump operation command ON Hot water pump operation command ON YES NO Pump interlock ON YES Compressor to start first operation ON This i...

Page 29: ...error 2 If the interlock contact does not turn ON within 180 seconds after the pump operation command is output from the unit 88WEX 88WCX the pump interlock error is confirmed unit error 3 For ensurin...

Page 30: ...mal stop request Abnormal stop To low load stop Residual set time 360 seconds elapsed Chilled water pump operation command OFF Cooling water hot water pump operation command OFF Stop due to normal sto...

Page 31: ...ut and the operation command is destroyed If contacts disconnect for 5 seconds in a row during normal operation to the same unit error is confirmed OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON 1 3 2 4 5...

Page 32: ...nd refrigerant piping Doing so could result in skin burning Do not attempt to run the compressor by pushing the magnetic contactor with your finger Doing so could result in electrical shock or fire 1...

Page 33: ...eginning mixing of air into the system may occur Perform on air purge at regular intervals Perform cleaning of the inside of the condenser and evaporator when needed Depending on operation conditions...

Page 34: ...is low and preliminary electrification time to the unit is short abnormal sound may occur at first time start of the compressors If abnormal sound lasts for 5 seconds or more after starting of compre...

Page 35: ...phic panel display Especially if you cause the unit to stop by STOP button on the switch box during remote operation selection in control screen shifts from REMOTE to LOCAL automatically so be careful...

Page 36: ...e When operating condition falls outside of recommended operation range in some cases capacity control load may have been adjusted for the protection of unit forcedly Discharge superheat level is low...

Page 37: ...TIVATION Disorder of sensor alone Inadequate insertion of PLC connection connector Disconnection or short circuit of chilled water outlet temperature sensor 1 Discharge gas 1 or 2 high temperature err...

Page 38: ...bonate gas and oxygen in open systems HOW TO CONTINUE Fill out the brief operation instructions form and fix it visibly near the operating site of the refrigeration system NOTES Item Details Power sup...

Page 39: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 40: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25558 1B...

Reviews: