background image

 

Installation and operation manual

18

EWWD440~850AAYNNO**

Packaged water-cooled water chillers

4PW25558-1B

Checking the water system

Pump is filled with water
Fill the water piping, taking into account the minimum water
volume required by the unit. Refer to 

"Table 2: Minimum water

volume" on page 9

.

Perform an air purge at the same time. Purging air is possible by
opening the airpurge valves on top of the condenser and
evaporator.
Operation with insufficient air purge can lead to drop of
performance.

Water pressure is less than the specified value
Check the chilled water side and condenser water side water
pressure.
Check the water pressure not only during normal flow, but also
at pump start.
If water pressure is over the maximum operating water pressure,
it may damage the machine.
In case of a standard model, the maximum operating water
pressure is 1.0 MPa both at chiller water side and condenser
water side.

No water leakage
Make sure that there is no water leakage from flanges or shells.

No mixing of air
Sound like "gobo gobo" while the water flows, or pressure
gauges attached to the equipment oscillate, or while the pump
operating current is unstable, means that air got mixed into the
water system.
Perform an air purge again.
Mixing of air not only makes the unit performance drop, but also
leads to damage of heat exchanger tubes inside the condenser
and evaporator.

Flow rate adjustment has been made
Adjust the flow rate to a proper rate using a flow meter and
adjust the rate in function of the pump characteristics chart.
Too low flow rate not only makes the unit performance drop, but
also leads to damage due to acceleration in adhesion of
contaminant and foreign matters to the heat exchanger tubes.
Excessive flow rate may lead to damage due to corrosion of heat
exchanger tubes.

Make adjustment of water interruption relay (Protective device)
Be sure to make this adjustment. Local adjustment to the head
of equipment is required.

Remove the cover of the water interruption relay to observe the
movement of the internal metal piece contact. Check that the
metal piece contact moves upward when the water flows
and moves downward during water flow failure.
 If the contact
has already moved upward during water flow failure, turn the
adjusting screw clockwise by means of a screwdriver so that the
contact moves as indicated in the drawing. If the contact does
not move upward while water flows, adjust it by turning the
adjusting screw counterclockwise.

Checking the unit body

Open all shut-off valves indicated by a red label: “OPEN THIS
VALVE BEFORE OPERATION”. 
All stopvalves, except those for charging of refrigerant or
oil, must be opened prior to start of the unit. Be sure to
check that they stay opened.

Stopvalves given below are installed.

Oil charge valve and refrigerant charge valve are used under
normally closed condition.

The pressure gauge valve (discharge pressure/suction pressure)
is designed as a 3-way valve taking maintenance of the pressure
sensors into account. Do not fully open these valves but keep
them at an intermediate opening
.

Valves other than described in the 2 points above, are used under
normally opened condition.

Checking the settings on the controller

Prior to putting the unit into operation, change the settings of the
graphic panel display to the details that meet your configuration.
Refer to 

"Operating the graphic panel display" on page 12

 and to

"Functions of this model" on page 21

.

The “SETTING (1/2)” screen represented below is the one of a
model with 2-temperature setting option. In case of the standard
model, the target temperature to be set will be represented with
“SET TEMPERATURE”.

1

Adjusting screw

2

Metal piece contact

3

When water flows

4

During water flow failure

2

1

3

4

Installation position

Stopvalve shape

Comment

Suction piping

Suction stop valve

Important 

Liquid piping (Bottom)

Copper pipe stopvalve 

Important

EWWD440/600: 1 point
EWWD850:

2 points

Condenser top 
(Right and left)

Copper pipe stopvalve (3/8")

2 points, right and left

Condenser top (Center)

Copper pipe stopvalve (3/8")

Copper pipe from 

condenser to compressor

Packless valve (3/8")

2 points,

right and left

Compressor 

discharge chamber 

(Oil discharge valve)

Copper pipe stopvalve (3/8")

2 points, right and left

Use at normally closed 

condition.

Float chamber top

Copper pipe stopvalve (3/8")

Float chamber

Packless valve (5/8")

Evaporator bottom

Copper pipe stopvalve (3/8")

3 points,

right and left

Liquid pipe 

(Refrigerant charge valve)

Copper pipe stopvalve (3/8")

EWWD440/600: 1 point
EWWD850:

2 points

Use at normally closed 

condition.

Copper pipe from 

evaporator to suction pipe

Copper pipe stopvalve (3/8")

Pressure gauge valve

3-way stopvalve for copper 

pipe (3/8")

2 points,

Be sure to use at 

intermediate opening

1

Set the chilled water outlet temperature target value.
The standard model is an outlet temperature control-only 
model.

2

Make settings for the low load stop function.

3

Set the remaining operating time of the pump.
In case of models with 2-temperature setting option, also the 
cooling water pump uses this setting.
The setting valve shall be 360 seconds or more.

4

Make setting of the current demand control.

1

1

2

2

3
4

Summary of Contents for EWWD440AAYNNO series

Page 1: ...INSTALLATION AND OPERATION MANUAL EWWD440AAYNNO EWWD600AAYNNO EWWD850AAYNNO Packaged water cooled water chillers...

Page 2: ...03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere...

Page 3: ...ue 36 Thank you for purchasing this Daikin air conditioner SAFETY CONSIDERATIONS For your safety and that of others observe the precautions listed here after at all time There are two types of precaut...

Page 4: ...ould result in a lack of oxygen in the latter case Make sure there is enough service space If the space is not enough maintenance work cannot be carried out safely and could result in any injuries Pre...

Page 5: ...am above Have the lifting beam 1 and 4 wire ropes prepared 2 Make sure that wire ropes are longer than 5 m Be sure to lift the unit horizontally levelled The unit is shipped with transport stays under...

Page 6: ...r 2 Evaporator 17 Condenser entering water temperature sensor 3 Condenser 18 Air purge evaporator 4 Switchbox 19 Water drain evaporator 5 Air purge condenser 20 Emergency stop 6 Water drain condenser...

Page 7: ...S LP B M1C M2C A 14 B 13 23 1 Compressor 15 Stop valve 2 Service valve 16 Service valve 3 Male connector 17 Suction stop valve 4 Stop valve 18 Stop valve 5 Solenoid valve 19 Filter drier 6 Filter 20...

Page 8: ...relative humidity of 90 or more Mounting this product at places where the temperature variation per hour exceeds 8 C or more is also inappropriate If you use this product in cold climates consideratio...

Page 9: ...the isolation of vibration by using expansion joints immediately near the unit Perform the vibration isolation in function of the installation site This machine comes with vibration isolation pads and...

Page 10: ...nd maintenance provide valves for release to atmosphere drain off valves and valves for chemical cleaning between stopvalves provided in the water piping system and the unit body For drain off valves...

Page 11: ...rrosion due to electric corrosion may occur If piping is to be put underground be extremely careful and take dust preventive measures Avoid execution of piping in such a way that a draft line is forme...

Page 12: ...e display H3P Indication lamp common error remote display H4P H5P Indication lamp compressor error 1 2 remote display H6P Indication lamp condenser water pump run stop H7P Indication lamp chiller wate...

Page 13: ...tor yellow green to the earthing terminal PE Interconnection cables Voltage free contacts The controller is provided with some voltage free contacts to indicate the status of the unit These voltage fr...

Page 14: ...tion is performed during 30 minutes In case of errors History screen Predictive maintenance history Alarm screen Alarm screen Alarm history Menu screen Operational data history in case of unit errors...

Page 15: ...hic panel display shuts off automatically if no operation is made to the graphic panel display since 30 minutes Touching any part of the screen while the graphic panel display is shut off makes the sc...

Page 16: ...y means of operation and stop buttons on the door of the switch box select this button 1 When LOCAL is selected select the operation mode with these buttons Buttons are disabled when REMOTE is selecte...

Page 17: ...s correct before touching the ENT button 5 Touch the CLOSE button to close the keypad Repeat steps 1 5 to change other settings History screen In this screen you can consult the alarm history and pred...

Page 18: ...screen 5 Select OPE DATA WHEN ERROR OCCURRED from the HISTORY screen 6 Record the listed 6 minutes data 7 Return to the MENU screen 8 Select the ALARM screen from the MENU screen 9 Return to the above...

Page 19: ...hine label Make sure that the frequency is within 2 of the value stated in machine label The voltage imbalance level among 3 phases must be within 2 of the rated voltage In order to avoid compressor d...

Page 20: ...Checking the unit body Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPERATION All stopvalves except those for charging of refrigerant or oil must be opened prior to start...

Page 21: ...ing full load operation Normally select 2UNITS 2 In this field you need to set the compressor that starts first after power up of the unit 1 is the left side viewed compressor from the front of the sw...

Page 22: ...NOTE This is the screen of models with 2 temperature setting option In the screen for standard models the field for cooling mode selection does not appear Selection must be made while the unit is stop...

Page 23: ...function that allows the compressor to suspend its operation automatically when the chiller water outlet temperature has lowered beyond a certain limit When the chiller water temperature rises the op...

Page 24: ...Cooling of the compressor motor is performed by suction refrigerant gas However if the compressor repeats Run Stop frequently the cooling effect of the suction refrigerant gas decreases and the motor...

Page 25: ...sor operation current to a predetermined current value instead of to the Maximum Load Amps of the compressors Set the demand value relative to the reference current value on the graphic panel display...

Page 26: ...this model setting of 2 target temperatures is available on condition that switching of target temperatures of the unit is available We distinguish target temperature for thermal storage mode and for...

Page 27: ...et temperature for chilled water 2 When thermal storage mode is selected the setpoint in SET TEMP IN HEAT STORAGE COOLING is the target temperature for chilled water NOTE Mode change is not available...

Page 28: ...st is under ON OFF limiting Opening 1 opening 2 0 Cooling water pump operation command ON Hot water pump operation command ON YES NO Pump interlock ON YES Compressor to start first operation ON This i...

Page 29: ...error 2 If the interlock contact does not turn ON within 180 seconds after the pump operation command is output from the unit 88WEX 88WCX the pump interlock error is confirmed unit error 3 For ensurin...

Page 30: ...mal stop request Abnormal stop To low load stop Residual set time 360 seconds elapsed Chilled water pump operation command OFF Cooling water hot water pump operation command OFF Stop due to normal sto...

Page 31: ...ut and the operation command is destroyed If contacts disconnect for 5 seconds in a row during normal operation to the same unit error is confirmed OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON 1 3 2 4 5...

Page 32: ...nd refrigerant piping Doing so could result in skin burning Do not attempt to run the compressor by pushing the magnetic contactor with your finger Doing so could result in electrical shock or fire 1...

Page 33: ...eginning mixing of air into the system may occur Perform on air purge at regular intervals Perform cleaning of the inside of the condenser and evaporator when needed Depending on operation conditions...

Page 34: ...is low and preliminary electrification time to the unit is short abnormal sound may occur at first time start of the compressors If abnormal sound lasts for 5 seconds or more after starting of compre...

Page 35: ...phic panel display Especially if you cause the unit to stop by STOP button on the switch box during remote operation selection in control screen shifts from REMOTE to LOCAL automatically so be careful...

Page 36: ...e When operating condition falls outside of recommended operation range in some cases capacity control load may have been adjusted for the protection of unit forcedly Discharge superheat level is low...

Page 37: ...TIVATION Disorder of sensor alone Inadequate insertion of PLC connection connector Disconnection or short circuit of chilled water outlet temperature sensor 1 Discharge gas 1 or 2 high temperature err...

Page 38: ...bonate gas and oxygen in open systems HOW TO CONTINUE Fill out the brief operation instructions form and fix it visibly near the operating site of the refrigeration system NOTES Item Details Power sup...

Page 39: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 40: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25558 1B...

Reviews: