Keys provided on the controller:
The function carried out when the user presses one or a combination
of these keys depends on the status of the controller and the unit at
that specific moment.
LEDs provided on the controller and remote interface:
Function during main display (not inside menu)
When selecting a parameter group or parameter, different LEDs
related to the parameter group or parameter are displayed.
Example: The LEDs
F
and
G
are displayed when accessing a
parameter group or when accessing parameters directly.
Direct and user parameters
The digital controller provides direct and user parameters. The direct
parameters are important for the everyday usage of the unit, e.g. to
adjust the temperature setpoint or to consult actual operational
information. The user parameters on the contrary provide advanced
features such as adjusting time delays.
Each parameter is defined by a code and a value. For example: the
parameter used to select local or remote on/off control has code
h07
and value
1
or
0
.
For an overview of the parameters, refer to "Overview of the direct
and user parameters" on page 10.
Working with the units
This chapter deals with the everyday usage of the
EWLQ
units. Here,
you will learn how to perform routine tasks, such as:
■
"Switching the unit on" on page 8 and "Switching the unit off" on
page 8,
■
"Adjusting the cooling temperature setpoint" on page 8,
■
"Consulting actual operational information" on page 9,
■
"Resetting alarms" on page 9,
■
"Resetting warnings" on page 9.
Keys digital
controller
Keys remote
interface
Main display
Sensor readout menu
Parameter selection menu
Parameter setting menu
A
T
—
Press once:
Return
Press once:
Return
Press once:
Cancel and return
B
U
Press for 5 seconds:
To be able to access
DIRECT parameters
—
Press once:
Select parameter group or
parameter
Press once:
Confirm and return
A
+
B
S
Press for 5 seconds:
A
+
B
OR
Press once:
S
To be able to access USER
parameters (after entering
USER password)
—
C
C
Press for 5 seconds:
Switch unit on/off in heating
mode
Press once: Direct access to
readout menu sensor
(
b01
/
b02
/
b03
)
Press once:
Select previous sensor
parameter
Press once:
Select previous parameter
group or parameter
Press once:
Increase value
D
D
Press for 5 seconds:
Switch unit on/off in cooling
mode
Press once: Direct access to
readout menu sensor
(
b01
/
b02
/
b03
)
Press once:
Select next sensor
parameter
Press once:
Select next parameter group
or parameter
Press once:
Decrease value
C
+
D
R
Press for 5 seconds:
Manually alarm reset in the
event of alarm
—
Leds digital controller
Remote
interface
Main display
P
Led (green)
Z
Inlet water temperature.
F
Led (amber)
F
Indicates that heating mode is
active.
G
Led (amber)
G
Indicates that cooling mode is
active.
H
Led (red)
Y
Indicates that the alarm is
active.
L
Led (amber)
L
Indicates the status of the
pump
M
Led (amber)
M
LED, indicates that at least
one compressor is active.
&
Led (amber)
&
LED is on, indicates that
compressor 1 is active.
LED is flashing, indicates
compressor 1 startup request.
é
Led (amber)
é
LED is on, indicates that
compressor 2 is active.
LED is flashing, indicates
compressor 2 startup request.
NOTE
Temperature readout tolerance: ±1°C.
Legibility of the numeric display may decrease in direct
sunlight.
4PW61666-1A.book Page 7 Friday, May 25, 2012 3:09 PM
Operation manual
7
EWLQ
014
~
064KBW1N
Condenserless water-cooled water chillers
DEOMHP0110817EU
Summary of Contents for EWLQ014KBW1N
Page 120: ...1 2 3 4 5 6 7 8 9 1 2 3 L1 L2 L3 4 LED 1 2 EWLQ 6 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 121: ...LED EWLQ014 064KBW1N D EOMHP01108 17EU 7...
Page 133: ...7 4 R401A GWP 1 2090 1 GWP 9 EWLQ014 064KBW1N D EOMHP01108 17EU 19...
Page 134: ...R410A 20 bar 3 C 20 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 159: ...EWLQ014 064KBW1N D EOMHP01107 17EU 6 1 2 3 4 5 6 7 Daikin 8 9 1 2 3 L1 L2 L3 N 4 1 2...
Page 160: ...7 EWLQ014 064KBW1N D EOMHP01108 17EU EWLQ...
Page 171: ...5 6 7 4 R410A 1 2090 652 1 4 3 43 4 4 4 5 4 6 4 EWLQ014 064KBW1N D EOMHP01108 17EU 18...
Page 172: ...9 I R410A 20 3 C 19 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 174: ...D EOMHP01108 17EU...