Advanced features of the digital controller
This chapter gives an overview of the direct parameters and user
parameters provided by the controller. In the following chapter, you
will learn how you can set up and configure the unit using these
parameters.
Overview of the direct and user parameters
The list of direct parameters is accessible by pressing the
B
key
for approximately 5 seconds. Refer also to "How to consult and
modify the direct parameters" on page 8.
Parameter
group
Parameter
code
Description
Default
value
Min
Max
Units
Read/
Write
User/
Direct
Modbus
Address
Parameter
type
(*)
(*)
D=digital, A=analog, I=integer.
-/-
/23
Measurement unit
0
=°C
1
=°F
0
0
1
R/W
U
5
D
-a-
No user or direct parameters accessible
-b-
b01
Evaporator inlet water temperature
0.1°C
R
D
102
A
b02
Evaporator outlet water temperature
0.1°C
R
D
103
A
b03
When cooling mode is active: inlet
water temperature of the condenser.
When heating mode is active: inlet
water temperature of the evaporator.
0.1°C
R
D
104
A
-c-
c07
Time delay between pump startup and
compressor startup
15
0
999
1 sec
R/W
U
238
I
c08
Time threshold between the unit
shutdown and the pump shutdown
0
0
150
1 min
R/W
U
239
I
c10
Total running hours of compressor 1
x100 hours
R
D
122
A
c11
Total running hours of compressor 2
x100 hours
R
D
123
A
c14
Maintenance threshold for
maintenance warning (
c10
and
c11
)
0
0
100
x100 hours
R/W
U
241
I
c15
Total running hours of pump
x100 hours
R
D
126
A
-d-
No user or direct parameters accessible
-f-
No user or direct parameters accessible
-h-
h06
To activate remote cool/heat control
0
=not active
1
=active
(only in case
p09
=9)
0
0
1
R/W
U
14
D
h07
To activate remote on/off control
0
=not active
1
=active
(only in case
p34
=23)
0
0
1
R/W
U
15
D
h09
To lock the controller keyboard
0
=lock
1
=unlock
1
0
1
R/W
U
16
D
h10
Serial address for BMS connection
1
1
200
R/W
U
256
I
h23
To select address card connection
0
=remote user interface connection
1
=MODBUS connection
0
0
1
R/W
U
11
D
-p-
p09
Changeable digital input selection
S7S
0
=no function
9
=remote cool/heat (only active in
combination with
h06
)
13
=remote dual setpoint
DO NOT SELECT OTHER VALUES
9
0
27
R/W
U
277
I
p34
Changeable digital input selection
S9S
0
=no function
13
=remote dual setpoint
23
=remote on/off (only active in
combination with
h07
)
DO NOT SELECT OTHER VALUES
23
0
27
R/W
U
329
I
-r-
r01
Cooling setpoint
12.0
8.0
(†)
(†) –2.0 and –7.0 only applicable for units with glycol applications.
25.0
0.1°C
R/W
D
41
A
r02
Cooling difference
3.0
0.3
19.9
0.1°C
R/W
D
42
A
r03
Heating setpoint
30.0
15.0
50.0
0.1°C
R/W
D
43
A
r04
Heating difference
3.0
0.3
19.9
0.1°C
R/W
D
44
A
r21
Cooling setpoint 2
(‡)
(‡) Used in case dual setpoint is enabled in
p09
or
p34
and dual setpoint digital input is closed.
12.0
8.0
(†)
25.0
0.1°C
R/W
D
55
A
r22
Heating setpoint 2
(‡)
30.0
15.0
50.0
0.1°C
R/W
D
56
A
-t-
No user or direct parameters accessible
f-r
h99
Software release version
R
D
208
I
4PW61666-1A.book Page 10 Friday, May 25, 2012 3:09 PM
EWLQ014
~
064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
10
Summary of Contents for EWLQ014KBW1N
Page 120: ...1 2 3 4 5 6 7 8 9 1 2 3 L1 L2 L3 4 LED 1 2 EWLQ 6 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 121: ...LED EWLQ014 064KBW1N D EOMHP01108 17EU 7...
Page 133: ...7 4 R401A GWP 1 2090 1 GWP 9 EWLQ014 064KBW1N D EOMHP01108 17EU 19...
Page 134: ...R410A 20 bar 3 C 20 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 159: ...EWLQ014 064KBW1N D EOMHP01107 17EU 6 1 2 3 4 5 6 7 Daikin 8 9 1 2 3 L1 L2 L3 N 4 1 2...
Page 160: ...7 EWLQ014 064KBW1N D EOMHP01108 17EU EWLQ...
Page 171: ...5 6 7 4 R410A 1 2090 652 1 4 3 43 4 4 4 5 4 6 4 EWLQ014 064KBW1N D EOMHP01108 17EU 18...
Page 172: ...9 I R410A 20 3 C 19 EWLQ014 064KBW1N D EOMHP01108 17EU...
Page 174: ...D EOMHP01108 17EU...