background image

EWYT~CZ / EWAT~CZ

DEIMHP0140521_00EN

11

When operating the unit in a low outdoor ambient 
temperature, be sure to follow the instructions described 
below.

To prevent exposure to wind and snow, install a baffle plate on the air 
side of the outdoor unit: In heavy snowfall areas it is very important to 
select an installation site where the snow will NOT affect the unit. If 
lateral snowfall is possible, make sure that the heat exchanger coil is 
NOT affected by the snow. If necessary, install a snow cover or shed 
and a pedestal.

For instructions on how to install the snow cover, contact your dealer.

When installing the snow cover, do NOT obstruct the air 
flow of the unit.

4.6. Noise and acoustic protection

The unit is a source of noise mainly due to rotation of compressors 
and fans. The noise level for each model size is listed in sales 
documentation. If the unit is correctly installed, operated and 
maintained the noise emission level do not require any special 
protection device to operate continuously close to the unit without 
any risk.

4.7. Water circuit for connection with the unit

4.7.1.  Water piping

Piping must be designed with the lowest number of elbows and the 
lowest number of vertical changes of direction. In this way, installation 
costs are reduced considerably, and system performance is 
improved.

The water system must have:

1. 

Antivibration mountings to reduce transmission of vibrations to 
the structures.

2. 

Isolating valves to isolate the unit from the water system during 
maintenance.

3. 

To protect the unit, the BPHE must be protected against freezing 
by continuous monitoring of the water flow in the BPHE by a flow 
switch. In most cases, on site, the flow switch is set to generate 
an alarm only when the water pump turns off and the water flow 
drops to zero. It is recommended to adjust the flow switch to 
produce a “Water Leakage Alarm” when the water flow reaches 
the minimum value of the flow allowable (see table 1); in this case 
the BPHE is protected against freezing and the flow switch can 
detect the clogging of the water filter.

4. 

Manual or automatic air venting device at the system highest 
point and drain device at the system lowest point.

5. 

Neither the BPHE nor the heat recovery device must be positio-
ned at the system’s highest point.

6. 

A suitable device that can maintain the water system under pres-
sure (expansion tank, etc.).

7. 

Water temperature and pressure indicators to assist the operator 
during service and maintenance.

8. 

A filter or device that can remove particles from the fluid. The use 
of a filter extends the life of the BPHE and pump and helps to 
keep the water system in a better condition. 

The water filter 

must be installed as close as possible to the unit.

 If the water 

filter is installed in another part of the water system, the Installer 
must guarantee the cleaning of the water pipes between the wa-
ter filter and the BPHE. Precautions for correct use:

•  All water components and piping/hydraulic devices outside 

the unit must therefore be protected against freezing.

•  All water components and piping/hydraulic devices must be 

emptied of water during the winter season, unless an ethylene 

glycol mixture in appropriate percentage is added to the wa-
ter circuit.

•  In case of unit substitution, the entire water system must be 

emptied and cleaned before the new unit is installed. Regular 
tests and proper chemical treatment of water are recommen-
ded before starting up the new unit.

•  If glycol is added to the water system as antifreeze protection, 

pay attention to the fact that suction pressure will be lower, 
the unit performance will be lower and water pressure drops 
will be greater. All unitprotection systems, such as antifreeze, 
and lowpressure protection will have to be readjusted.

The maximum glycol percentage is 40% for all the unit.

In the following table are illustrated the minimum glycol percen-
tage for low ambient air temperature

AMBIENT T [°C]

-3

-8

-15

-20

ETHYLENE GLYCOL

10%

20%

30%

40%

PROPYLENE GLYCOL

10%

20%

35%

40%

Table 2  – 

Minimum glycol percentage for low ambient air temperature

Protection of the water circuit is necessary in the winter season, 
even with the unit not in operation.
•  Before insulating water piping, check that there are no leaks. 

The complete hydraulic circuit must be insulated to prevent 
condensation and reduced refrigeration capacity. Protect the 
water pipes from frost during winter (using for example a 
glycol solution or a heating cable).

•  Check that the water pressure does not exceed the design 

pressure of the water side heat exchangers. Install a safety 
valve on the water pipe downstream of the BPHE.

9. 

Select the piping diameter in relation to the required water flow 
and available external static pressure of the pump. See the fol-
lowing table for the recommended water piping diameter.

Unit

Water piping diameter

EWAT/EWYT016~040CZ(N/P/H)-A1

1 ¼”

EWAT/EWYT040~090CZ(N/P/H)-A2

2”

4.7.2.  Flow switch

Flow switch is a standard component fitted to all units. To ensure 
sufficient water flow through the plate exchanger, it is essential that a 
flow switch be installed on the water circuit. It is already installed in 
the standard supply. The purpose of the flow switch is to stop the unit 
in the event of interrupted water flow, thus protecting the BPHE from 
freezing.

This is a palette flow switch appropriate for uninterrupted use 
outdoors (IP65).

The flow switch is set up to intervene when the water flow of the BPHE 
reaches the minimum value of the flow acceptable (see the table 
below).

Summary of Contents for EWAT016CZN-A1

Page 1: ...REV 00 Date 04 2021 Supersedes Installation Maintenance and Operation Manual DEIMHP0140521_00EN Air to water heat pump units with scroll compressors EWYT CZ EWAT CZ...

Page 2: ......

Page 3: ...RESSURE EQUIPMENT 27 12 DISMISSIONAND DISPOSAL 27 List of tables Table 1 Physical properties of R32 refrigerant 5 Table 2 Minimum glycol percentage for low ambient air temperature 11 Table 3 Flow Swit...

Page 4: ...to check possible refrigerant leaks 13 Disable the unit from the mains using the main switch before opening the control panel 14 Check that the unit has been grounded correctly before starting it 15...

Page 5: ...pagation rate is low and nontoxic R32 refrigerant can burn slowly when all the following conditions are present The concentration is between the lower and upper flammability limit LFL UFL Wind velocit...

Page 6: ...it contacts the duct material n Airflow of the emergency mechanical ventilation shall be at least V 0 014 m Where V is air flow in m s m is the amount of refrigerant present in the machine room in kg...

Page 7: ...osphere may damage electrical components 4 MECHANICAL INSTALLATION 4 1 Safety Before installation and commissioning of the machinery the people involved in this activity must have acquired the informa...

Page 8: ...outdoors either on balconies or on the ground provided that the installation area is free of obstacles that could reduce air flow to the condensers coil The unit must be installed on a robust and per...

Page 9: ...y side of the unit must be accessible for postinstallation maintenance operations and vertical air discharge must not be obstructed Figure below shows the minimum space required Figure 4 DUAL unit Whe...

Page 10: ...the main wind direction Frontal wind will disturb the operation of the unit If necessary use a screen to block the wind Ensure that water cannot cause any damage to the location by adding water drains...

Page 11: ...ition The water filter must be installed as close as possible to the unit If the water filter is installed in another part of the water system the Installer must guarantee the cleaning of the water pi...

Page 12: ...Z P H A2 2 43 6 00 Table 4 Operating limits 4 7 3 Preparing and checking the water circuit connection The units have water inputs and outputs for connecting the heat pump to water circuit of the syste...

Page 13: ...300 CO2 Sulphate ion mg SO4 2 l 100 Alkalinity mg CaCO3 l 200 Total Hardness mg CaCO3 l 75 150 Iron mg Fe l 0 2 Ammonium ion mg NH4 l 0 5 Silica mg SiO2 l Chlorine molecular mg Cl2 l 0 5 Note 1 Heat P...

Page 14: ...ater temperature Ref 1 Unit operations in this area require OP 192 HIGH AMBIENT TEMPERATURE KIT Ref 2 Unit operations in this area require the enabling of the Brine version in the controller and the u...

Page 15: ...t to have a water temperature difference of 2 5 K which allows it to operate with the minimum volume mentioned in the previous table However if a smaller temperature differential is set as in the case...

Page 16: ...appropriate antifreeze protection is always maintained Failing to follow the instructions above could result in unit damage 4 ELECTRIC HEATER Option on request A heater tape is instal led on the water...

Page 17: ...d the earth according to IEC 614391 table 1 and 2 and to the local national laws The cables connected to the main switch must be tightened using a pair of keys and respecting the unified clamping valu...

Page 18: ...ompressors must be carried out exclusively by qualified personnel Sharp edges and the surface of the condenser section could cause injury Avoid direct contact and use adequate pro tection device Do no...

Page 19: ...t maintenance could degrade all parts of the units coils compressors frames pipes etc with negative effect on performances and functionality There are two different levels of maintenance which can be...

Page 20: ...trical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and sui tably t...

Page 21: ...X Check the safety valve X Coil section Checking the cleaning of the air heat exchanger Note 6 X Check the cleaning of water heat exchangers Note 6 X Verify that fans are well tightened X Verify coil...

Page 22: ...CZ 7 2 4 Refrigerant circuit scheme Figure 17 Refrigerant circuit P ID diagram for MONO circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LI...

Page 23: ...IMHP0140521_00EN 23 Figure 18 Refrigerant circuit P ID diagram for MONO circuit EWAT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 24: ...24 EWYT CZ EWAT CZ Figure 19 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 25: ...nd outlet are indicative Please refer to the machine dimensional diagrams for exact water connections The series is composed by mono one circuit and dual two circuits reversible unit Legend Item Descr...

Page 26: ...raulic circuit Check the oil level in the compressors Chilled Water Yes No N A Piping complete Water System filled and vented Pumps installed operational rotation checked Strainers installed and clean...

Page 27: ...nd III of the classification established by the European Directive 2014 68 EU PED For units belonging to these categories some local regulations require a periodic inspection by an authorized person P...

Page 28: ...Notes...

Page 29: ...y is given for the completeness accuracy reliability of its contents All data and specifications contained therein may be subject to change without notice Refer to the data communicated at the time of...

Page 30: ...DEIMHP0140720_00EN 2021 04 Via Piani di Santa Maria 72 00072 Ariccia Roma Italy Tel 39 06 93 73 11 Fax 39 06 93 74 014 http www daikinapplied eu...

Reviews: