background image

EWYT~CZ / EWAT~CZ

DEIMHP0140521_00EN

5

1.2. General description

All EWYT~CZ / EWAT~CZ machines are built in accordance with the 
main European Directives (Machinery Directive, Low Voltage 
Directive, Electromagnetic Compatibility Directive, Pressure 
Equipment Directive.

The unit purchased is a Heat Pump, that is a machine designed to 
cool/heat the water (or a water-glycol mixture) within certain limits 
which will be listed below. The unit operates based on the 
compression, condensation and evaporation of the coolant gas as 
per the Carnot cycle, and is composed mainly of the following parts 
depending on the Mode of Operation.

Cooling or Conditioning Mode:

 

One or more scroll compressors which increase the pressure of 
the refrigerant gas from evaporation pressure to condensation 
pressure.

 

A condenser where the refrigerant gas condenses under high 
pressure and transfers heat to the air.

 

An expansion valve which allows the pressure of condensed li-
quid refrigerant to be reduced from condensation pressure to 
evaporation pressure.

 

An evaporator, where the low-pressure liquid refrigerant evapo-
rates and chills the water.

Heating Mode or Heat Pump:

 

One or more scroll compressors which increase the pressure of 
the refrigerant gas from evaporation pressure to condensation 
pressure.

 

A condenser where the refrigerant gas condenses under high 
pressure and transfers heat to the water.

 

An expansion valve which allows the pressure of condensed li-
quid refrigerant to be reduced from condensation pressure to 
evaporation pressure.

 

An evaporator, where the low-pressure liquid refrigerant evapo-
rates.

 

The operation of the heat exchangers can be inverted using the 
4way valve, with which the use of the heating/cooling unit can be 
seasonally inverted.

All units are fully assembled in the factory and tested before shipping. 
The EWYT~CZ / EWAT~CZ range consists of models with a single 
cooling circuit and models with two cooling circuits.

The machine uses R32 refrigerant fluid suitable for the entire field of 
application of the machine.

The controller is prewired, set up and tested at the factory. Only 
normal field connections such as piping, electrical connections and 
pump interlocks are required, simplifying installation and increasing 
reliability. All safety and operation control systems are installed at the 
factory in the control panel.

The instructions in this manual are applicable to all models in this 
series unless otherwise specified.

1.3. Information about the refrigerant

This product contains R32 refrigerant that has a minimal environmental 
impact, thanks to its low value of Global Warming Potential (GWP). 
According to ISO 817, R32 refrigerant is classified as A2L, which is 
slightly flammable, since the flame propagation rate is low, and 
nontoxic.

R32 refrigerant can burn slowly when all the following conditions are 
present:

 

The concentration is between the lower and upper flammability 
limit (LFL & UFL).

 

Wind velocity<propagation of flame velocity

 

Energy of the ignition source>Minimum ignition energy

But pose no risk under the normal usage conditions for airconditioning 
equipment and work environment.

Safety class (ISO 817)

A2L

PED Group

1

Practical limit (kg/m3)

0.061

ATEL/ ODL (kg/m3)

0.30

LFL (kg/m3) @ 60°C

0.307

Vapor density @25°C, 101.3 kPa (kg/m3)

2.13

Molecular mass

52.0

Boiling point (° C)

-52

GWP (100 yr ITH)

675

GWP (ARS 100 yr ITH)

677

Autoignition temperature (° C)

648

Table 1  – 

Physical properties of R32 refrigerant

1.4. Installation information

The heat pump must be installed in open air or machinery room 
(location classification III).

To ensure location classification III a mechanical vent on the 
secondary circuit(s) must be installed.

Local building codes and safety standards shall be followed; in 
absence of local codes and standards refer to EN 378 3 / ISO 5149-3 
as a guide.

In paragraph “Additional guidelines for safe use of R32” there are 
provided additional information that should be added to the 
requirements of safety standards and building codes.

Additional guidelines for safe use of R32 for equipment located in 
the open air

Units sited in the open air shall be positioned to avoid leaked 
refrigerant flowing into a building or otherwise endangering people 
and property.

The refrigerant shall not be able to flow into any ventilation fresh air 
opening, doorway, trap door or similar opening in the event of a leak. 
Where a shelter is provided for refrigerating equipment sited in the 
open air it shall have natural or forced ventilation.

For units installed outside in a location where a release of refrigerant 
can stagnate e.g. below ground, then the installation shall comply 
with the requirements for gas detection and ventilation of machinery 
rooms.

Additional guidelines for safe use of R32 for equipment located in 
a machinery room

When a machinery room is chosen for the location of the unit it shall 
be in accordance with local and national regulations. The following 
requirements (according to EN 378-3:2016) can be used for the 
assessment.

 

A risk analysis based on the safety principle for a refrigeration 
system (as determined by the manufacturer and including the 
charge and safety classification of the used refrigerant) should 
be conducted to determine if it is necessary to install the heat 
pump in a separate refrigeration machinery room.

 

Machinery rooms should not be used as occupied spaces. The 
building owner or user shall ensure that access is permitted only 
by qualified and trained personnel doing the necessary mainte-
nance to the machinery room or general plant.

 

Machinery rooms shall not be used for storage except for tools, 
spare parts and compressor oil for the installed equipment. Any 

Summary of Contents for EWAT016CZN-A1

Page 1: ...REV 00 Date 04 2021 Supersedes Installation Maintenance and Operation Manual DEIMHP0140521_00EN Air to water heat pump units with scroll compressors EWYT CZ EWAT CZ...

Page 2: ......

Page 3: ...RESSURE EQUIPMENT 27 12 DISMISSIONAND DISPOSAL 27 List of tables Table 1 Physical properties of R32 refrigerant 5 Table 2 Minimum glycol percentage for low ambient air temperature 11 Table 3 Flow Swit...

Page 4: ...to check possible refrigerant leaks 13 Disable the unit from the mains using the main switch before opening the control panel 14 Check that the unit has been grounded correctly before starting it 15...

Page 5: ...pagation rate is low and nontoxic R32 refrigerant can burn slowly when all the following conditions are present The concentration is between the lower and upper flammability limit LFL UFL Wind velocit...

Page 6: ...it contacts the duct material n Airflow of the emergency mechanical ventilation shall be at least V 0 014 m Where V is air flow in m s m is the amount of refrigerant present in the machine room in kg...

Page 7: ...osphere may damage electrical components 4 MECHANICAL INSTALLATION 4 1 Safety Before installation and commissioning of the machinery the people involved in this activity must have acquired the informa...

Page 8: ...outdoors either on balconies or on the ground provided that the installation area is free of obstacles that could reduce air flow to the condensers coil The unit must be installed on a robust and per...

Page 9: ...y side of the unit must be accessible for postinstallation maintenance operations and vertical air discharge must not be obstructed Figure below shows the minimum space required Figure 4 DUAL unit Whe...

Page 10: ...the main wind direction Frontal wind will disturb the operation of the unit If necessary use a screen to block the wind Ensure that water cannot cause any damage to the location by adding water drains...

Page 11: ...ition The water filter must be installed as close as possible to the unit If the water filter is installed in another part of the water system the Installer must guarantee the cleaning of the water pi...

Page 12: ...Z P H A2 2 43 6 00 Table 4 Operating limits 4 7 3 Preparing and checking the water circuit connection The units have water inputs and outputs for connecting the heat pump to water circuit of the syste...

Page 13: ...300 CO2 Sulphate ion mg SO4 2 l 100 Alkalinity mg CaCO3 l 200 Total Hardness mg CaCO3 l 75 150 Iron mg Fe l 0 2 Ammonium ion mg NH4 l 0 5 Silica mg SiO2 l Chlorine molecular mg Cl2 l 0 5 Note 1 Heat P...

Page 14: ...ater temperature Ref 1 Unit operations in this area require OP 192 HIGH AMBIENT TEMPERATURE KIT Ref 2 Unit operations in this area require the enabling of the Brine version in the controller and the u...

Page 15: ...t to have a water temperature difference of 2 5 K which allows it to operate with the minimum volume mentioned in the previous table However if a smaller temperature differential is set as in the case...

Page 16: ...appropriate antifreeze protection is always maintained Failing to follow the instructions above could result in unit damage 4 ELECTRIC HEATER Option on request A heater tape is instal led on the water...

Page 17: ...d the earth according to IEC 614391 table 1 and 2 and to the local national laws The cables connected to the main switch must be tightened using a pair of keys and respecting the unified clamping valu...

Page 18: ...ompressors must be carried out exclusively by qualified personnel Sharp edges and the surface of the condenser section could cause injury Avoid direct contact and use adequate pro tection device Do no...

Page 19: ...t maintenance could degrade all parts of the units coils compressors frames pipes etc with negative effect on performances and functionality There are two different levels of maintenance which can be...

Page 20: ...trical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and sui tably t...

Page 21: ...X Check the safety valve X Coil section Checking the cleaning of the air heat exchanger Note 6 X Check the cleaning of water heat exchangers Note 6 X Verify that fans are well tightened X Verify coil...

Page 22: ...CZ 7 2 4 Refrigerant circuit scheme Figure 17 Refrigerant circuit P ID diagram for MONO circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LI...

Page 23: ...IMHP0140521_00EN 23 Figure 18 Refrigerant circuit P ID diagram for MONO circuit EWAT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 24: ...24 EWYT CZ EWAT CZ Figure 19 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 25: ...nd outlet are indicative Please refer to the machine dimensional diagrams for exact water connections The series is composed by mono one circuit and dual two circuits reversible unit Legend Item Descr...

Page 26: ...raulic circuit Check the oil level in the compressors Chilled Water Yes No N A Piping complete Water System filled and vented Pumps installed operational rotation checked Strainers installed and clean...

Page 27: ...nd III of the classification established by the European Directive 2014 68 EU PED For units belonging to these categories some local regulations require a periodic inspection by an authorized person P...

Page 28: ...Notes...

Page 29: ...y is given for the completeness accuracy reliability of its contents All data and specifications contained therein may be subject to change without notice Refer to the data communicated at the time of...

Page 30: ...DEIMHP0140720_00EN 2021 04 Via Piani di Santa Maria 72 00072 Ariccia Roma Italy Tel 39 06 93 73 11 Fax 39 06 93 74 014 http www daikinapplied eu...

Reviews: