DEIMHP0140521_00EN
10
EWYT~CZ / EWAT~CZ
Figure 5 –
Units installed side by side along their shorter sides, B or D
Case 1
Case 2
Figure 6 –
Units installed side by side along their longer sides
(Case 1 and Case 2)
The minimum distances, reported above, ensure functionality of the
unit in most applications.
4.5. Additional installation site requirements
■
When installing, take strong winds, typhoons or earthquakes into
account, improper installation may result in the unit turning over.
■
Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
■
Be sure that the air inlet of the unit is not positioned towards the
main wind direction. Frontal wind will disturb the operation of the
unit. If necessary, use a screen to block the wind.
■
Ensure that water cannot cause any damage to the location by
adding water drains to the foundation and prevent water traps in
the construction.
Seaside installation.
Make sure the outdoor unit is NOT directly
exposed to sea winds. This is to prevent corrosion caused by high
levels of salt in the air, which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example:
Behind the building (case I).
If the outdoor unit is exposed to direct sea winds, install a Windbreaker
(case II).
• Height of windbreaker ≥1.5×height of outdoor unit
• Mind the service space requirements when installing the win-
dbreaker.
Figure 7 –
Seaside installation of the outdoor unit
Legend:
a
.
Sea wind
b
. Building
c
.
Outdoor unit
d
. Windbreaker