background image

EWYT~CZ / EWAT~CZ

DEIMHP0140521_00EN

15

4.12. Operating stability and minimum water content in 

the system

For the correct functioning of the machines it is important to guarantee 
a minimum water content inside the system, avoiding an excessive 
number of compressor startups and stops. In fact, every time the 
compressor starts working, an excessive amount of oil from the 
compressor enters the circulation in the refrigerant circuit and at the 
same time there is an increase in the temperature of the compressor 
stator, generated by the inrush current of the starting. In order to 
prevent damage to the compressor, the control system will therefore 
permit no more than 10 startups per hour. The plant where the unit is 
installed must therefore ensure that the overall water content allows 
constant operation of the unit and consequently also greater 
environmental comfort.

As a general indication the water content should not be less than the 
values in the following table:

HeatPump

Suggested

L/kW

Min water 

content [L]

EWYT016CZ(N/P/H)-A1

5.7

90

EWYT021CZ(N/P/H)-A1

5.0

100

EWYT025CZ(N/P/H)-A1

4.4

110

EWYT032CZ(N/P/H)-A1

4.9

160

EWYT040CZ(N/P/H)-A1

4.6

180

EWYT040CZ(N/P/H)-A2

3.0

120

EWYT050CZ(N/P/H)-A2

2.6

130

EWYT064CZ(N/P/H)-A2

2.7

170

EWYT090CZ(N/P/H)-A2

2.7

230

CoolingOnly

Suggested

L/kW

Min water 

content [L]

EWAT016CZ(N/P/H)-A1

3.7

58

EWAT021CZ(N/P/H)-A1

2.8

58

EWAT025CZ(N/P/H)-A1

2.3

58

EWAT032CZ(N/P/H)-A1

2.8

90

EWAT040CZ(N/P/H)-A1

2.3

90

EWAT040CZ(N/P/H)-A2

1.5

60

EWAT050CZ(N/P/H)-A2

1.2

60

EWAT064CZ(N/P/H)-A2

1.1

73

EWAT090CZ(N/P/H)-A2

1.0

90

Table 7  – 

Minimum water content in the system

NOTE

Extra water may be required in critical processes or in 

spaces with a high thermal load.

The difference in startup temperature may vary from 1 to 5 K. This has 
an impact on the minimum water volume required when the unit is 
functioning in cooling mode. The unit is preset for a startup 
temperature difference of 2.5 K.

The Thermo ON condition is shown below:

EWT > Se startup ∆T

Default

Max

Min

startup ∆T (K)

2.5

5

1

By default, the unit is set to have a water temperature difference of 2.5 
K which allows it to operate with the minimum volume mentioned in 
the previous table. However, if a smaller temperature differential is 
set, as in the case of process cooling applications where temperature 
fluctuations must be avoided, a larger minimum water volume will be 
required.

To ensure proper operation of the unit when changing the value of 
setting, the minimum water volume has to be corrected. If this volume 
exceeds the range allowed in the unit, an additional expansion vessel 
or a buffer tank must be installed in the field piping.

Minimum water volume correction factor

A water volume correction factor “a” is introduced on the basis of the 
difference in startup temperature “b”, the function of which is:

a · d = 2,5

0

0,5

1

1,5

2

2,5

3

0

1

2

3

4

5

6

a  Min volume correction factor

b Delta T Startup (K)

Minimum water volume correction factor

Figure 15  – 

Minimum water volume correction factor

Example:

To illustrate the impact on the system when modifying the setting, we 
will consider a unit with a minimum allowable water volume of 58 L. 
Assuming that the setting is changed from Delta T 2.5K (default) to 
1.5K. The correction factor to be applied is 

a = 

2,5

1,5

 = 1,67

, and so to 

calculate the minimum water content in the system for a 25 kW unit, in 
cooling mode, all we need to do is multiple the default minimum 
volume by this correction factor to obtain the new minimum 
volume, 97l.

4.13. Calibrating the expansion vessel

The expansion vessel’s starting pressure depends on the difference 
between the level at which the unit is installed and the highest point in 
the water circuit, and is calculated as follows:

P

i

=0.3+(H/10) (bar)

•  P

i

  Initial pressure

•  H 

 Difference between the level at which the unit is installed 
and the highest point in the circuit

A unit with an onboard pump has a 12 liters expansion vessel with an 
initial pressure of 1 bar.

Maximum water volume

Refer to the graph below to determine the maximum water volume in 
order to calibrate the expansion vessel:

0

0

0,5

1

1,5

2

2,5

3

50

33

100

150

200

250

300

350

400

450

500

550

600

a

b

A

F

E

D

B

C

Figure 16  – 

Initial expansion vessel pressure on the basis of 

maximum water volume

a

 

Initial pressure of the expansion vessel [bar]

Summary of Contents for EWAT016CZN-A1

Page 1: ...REV 00 Date 04 2021 Supersedes Installation Maintenance and Operation Manual DEIMHP0140521_00EN Air to water heat pump units with scroll compressors EWYT CZ EWAT CZ...

Page 2: ......

Page 3: ...RESSURE EQUIPMENT 27 12 DISMISSIONAND DISPOSAL 27 List of tables Table 1 Physical properties of R32 refrigerant 5 Table 2 Minimum glycol percentage for low ambient air temperature 11 Table 3 Flow Swit...

Page 4: ...to check possible refrigerant leaks 13 Disable the unit from the mains using the main switch before opening the control panel 14 Check that the unit has been grounded correctly before starting it 15...

Page 5: ...pagation rate is low and nontoxic R32 refrigerant can burn slowly when all the following conditions are present The concentration is between the lower and upper flammability limit LFL UFL Wind velocit...

Page 6: ...it contacts the duct material n Airflow of the emergency mechanical ventilation shall be at least V 0 014 m Where V is air flow in m s m is the amount of refrigerant present in the machine room in kg...

Page 7: ...osphere may damage electrical components 4 MECHANICAL INSTALLATION 4 1 Safety Before installation and commissioning of the machinery the people involved in this activity must have acquired the informa...

Page 8: ...outdoors either on balconies or on the ground provided that the installation area is free of obstacles that could reduce air flow to the condensers coil The unit must be installed on a robust and per...

Page 9: ...y side of the unit must be accessible for postinstallation maintenance operations and vertical air discharge must not be obstructed Figure below shows the minimum space required Figure 4 DUAL unit Whe...

Page 10: ...the main wind direction Frontal wind will disturb the operation of the unit If necessary use a screen to block the wind Ensure that water cannot cause any damage to the location by adding water drains...

Page 11: ...ition The water filter must be installed as close as possible to the unit If the water filter is installed in another part of the water system the Installer must guarantee the cleaning of the water pi...

Page 12: ...Z P H A2 2 43 6 00 Table 4 Operating limits 4 7 3 Preparing and checking the water circuit connection The units have water inputs and outputs for connecting the heat pump to water circuit of the syste...

Page 13: ...300 CO2 Sulphate ion mg SO4 2 l 100 Alkalinity mg CaCO3 l 200 Total Hardness mg CaCO3 l 75 150 Iron mg Fe l 0 2 Ammonium ion mg NH4 l 0 5 Silica mg SiO2 l Chlorine molecular mg Cl2 l 0 5 Note 1 Heat P...

Page 14: ...ater temperature Ref 1 Unit operations in this area require OP 192 HIGH AMBIENT TEMPERATURE KIT Ref 2 Unit operations in this area require the enabling of the Brine version in the controller and the u...

Page 15: ...t to have a water temperature difference of 2 5 K which allows it to operate with the minimum volume mentioned in the previous table However if a smaller temperature differential is set as in the case...

Page 16: ...appropriate antifreeze protection is always maintained Failing to follow the instructions above could result in unit damage 4 ELECTRIC HEATER Option on request A heater tape is instal led on the water...

Page 17: ...d the earth according to IEC 614391 table 1 and 2 and to the local national laws The cables connected to the main switch must be tightened using a pair of keys and respecting the unified clamping valu...

Page 18: ...ompressors must be carried out exclusively by qualified personnel Sharp edges and the surface of the condenser section could cause injury Avoid direct contact and use adequate pro tection device Do no...

Page 19: ...t maintenance could degrade all parts of the units coils compressors frames pipes etc with negative effect on performances and functionality There are two different levels of maintenance which can be...

Page 20: ...trical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and sui tably t...

Page 21: ...X Check the safety valve X Coil section Checking the cleaning of the air heat exchanger Note 6 X Check the cleaning of water heat exchangers Note 6 X Verify that fans are well tightened X Verify coil...

Page 22: ...CZ 7 2 4 Refrigerant circuit scheme Figure 17 Refrigerant circuit P ID diagram for MONO circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LI...

Page 23: ...IMHP0140521_00EN 23 Figure 18 Refrigerant circuit P ID diagram for MONO circuit EWAT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 24: ...24 EWYT CZ EWAT CZ Figure 19 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 25: ...nd outlet are indicative Please refer to the machine dimensional diagrams for exact water connections The series is composed by mono one circuit and dual two circuits reversible unit Legend Item Descr...

Page 26: ...raulic circuit Check the oil level in the compressors Chilled Water Yes No N A Piping complete Water System filled and vented Pumps installed operational rotation checked Strainers installed and clean...

Page 27: ...nd III of the classification established by the European Directive 2014 68 EU PED For units belonging to these categories some local regulations require a periodic inspection by an authorized person P...

Page 28: ...Notes...

Page 29: ...y is given for the completeness accuracy reliability of its contents All data and specifications contained therein may be subject to change without notice Refer to the data communicated at the time of...

Page 30: ...DEIMHP0140720_00EN 2021 04 Via Piani di Santa Maria 72 00072 Ariccia Roma Italy Tel 39 06 93 73 11 Fax 39 06 93 74 014 http www daikinapplied eu...

Reviews: