background image

EWYT~CZ / EWAT~CZ

DEIMHP0140521_00EN

19

refrigerating 
system

The following precautions should be taken before 
working on the refrigerant circuit:

•  obtain permit for hot work (if required);
•  ensure that no flammable materials are stored in 

the work area and that no ignition sources are 
present anywhere in the work area;

•  ensure that suitable fire extinguishing equipment 

is available;

•  ensure that the work area is 

properly ventilated

 

before working on the refrigerant circuit or befo-
re welding, brazing or soldering work;

•  ensure that the leak detection equipment being 

used is nonsparking, adequately sealed or intrin-
sically safe;

•  ensure that all maintenance staff have been in-

structed.

•  Always perform the following procedure before 

working on the refrigerant circuit:

•  remove refrigerant (specifying residual pressu-

re);

•  purge circuit with 

inert gas

 (e.g. nitrogen);

•  evacuate at a pressure of 0.3 bar (ass.) (or 0.03 

MPa);

•  purge circuit with 

inert gas

 (e.g. nitrogen) again;

•  open the circuit.

If compressors or compressor oils are to be remo-
ved, it should be ensured that it has been evacuated 
to an acceptable level to ensure that there is no flam-
mable refrigerant remaining within the lubricant.

Only refrigerant recovery equipment designed 
for use with flammable refrigerants should be 
employed.

If the national rules or regulations permit the refrige-
rant to be drained, this should be done safely, using 
a hose, for example, through which the refrigerant is 
discharged into the outside atmosphere in a safe 
area. It should be ensured that an inflammable 
explosive refrigerant concentration cannot occur 
near an ignition source or penetrate into a building 
under any circumstance.
In the case of refrigerating systems with an indirect 
system, the heat transfer fluid should be checked for 
the possible presence of refrigerant.
After any repair work, the safety devices, for example 
refrigerant detectors and mechanical ventilation sy-
stems, should be checked and the results recorded.
It should be ensured that any missing or illegible label 
on components of the refrigerant circuit is replaced.
Sources of ignition should not be used when sear-
ching for a refrigerant leak.

7.1. Pressure / temperature table

°C

Bar

°C

Bar

°C

Bar

°C

Bar

28

2.97

2

7.62

24

16.45

50

31.41

26

3.22

0

8.13

26

17.35

52

32.89

24

3.48

2

8.67

28

18.30

54

34.42

22

3.76

4

9.23

30

19.28

56

36.00

20

4.06

6

9.81

32

20.29

58

37.64

18

4.37

8

10.43

34

21.35

60

39.33

16

4.71

10

11.07

36

22.45

62

41.09

14

5.06

12

11.74

38

23.60

64

42.91

12

5.43

14

12.45

40

24.78

66

44.79

10

5.83

16

13.18

42

26.01

68

46.75

8

6.24

18

13.95

44

27.29

70

48.77

6

6.68

20

14.75

46

28.61

72

50.87

4

7.14

22

15.58

48

29.99

74

53.05

Table 9  – 

R32 Pressure/Temperature

7.2. Routine maintenance

This unit must be maintained by qualified technicians. Before 
beginning any work on the system, the personnel shall assure that all 
security precautions have been taken.

Neglecting unit maintenance could degrade all parts of the units 
(coils, compressors, frames, pipes, etc.) with negative effect on 
performances and functionality.

There are two different levels of maintenance, which can be chosen 
according to the type of application (critical/noncritical) or to the 
installation environment (highly aggressive).

Examples of critical applications are process cooling, data centres, 
etc.

Highly Aggressive Environments can be defined as the follows:

•  Industrial environment (with possible concentration of fumes 

result of combustion and chemical process);

•  Coastal environment;
•  Highly polluted urban environment;
•  Rural environment close to of animal excrement and fertili-

zers, and high concentration of exhaust gas from diesel gene-
rators;

•  Desert areas with risk of sandstorms;
•  Combinations of the above.

Table 10 lists all Maintenance activities for standard applications and 
standard environment.

Table 11 lists all Maintenance activities for critical applications or 
highly aggressive environment.

Unit exposed to a highly aggressive environment can face corrosion 
in a shorter time than ones installed on a standard environment. 
Corrosion causes a rapid rusting of the frame core, consequently 
decreases unit structure life time. To avoid that, it is necessary to 
wash periodically the frame surfaces with water and suitable 
detergents.

In case of part of unit frame paint came off, it is important to stop its 
progressive deterioration by repainting the exposed parts using 
proper products. Please contact factory to get the required products 
specifications.

In case of just salt deposits are present, it is enough to rinse the parts 
with fresh water.

7.2.1.  Air Heat Exchanger Maintenance

Routine cleaning of air heat exchanger surfaces is essential to 
maintain proper operation of the unit, avoid corrosion and rusting. 
Elimination of contamination and removal of harmful residues will 
greatly increase the life of the coil and extend the life of the unit.

Remove surface dirt, leaves, fibers, etc. with a vacuum cleaner 
(preferably with a brush or other soft attachment rather than a metal 
tube), compressed air blown from the inside out, and/or a soft bristle 
(not wire!) brush. Do not impact or scrape the coil with the vacuum 
tube, air nozzle, etc.

Use of a water stream, such as a garden hose, against a surface 
loaded coil will drive the fibers and dirt into the coil. This will make 
cleaning efforts more difficult. Surface loaded fibers must be 
completely removed prior to using low velocity clean water rinse.

NOTE

A monthly clean water rinse is recommended for coils 

that are applied in coastal or industrial environments to 

help to remove chlorides, dirt and debris. It is very 

important when rinsing that the water temperature is 

below 55 °C.

Galvanic corrosion of the connection Copper/Aluminum can occurre 
in corrosive atmosphere under the plastic protection; during the 
maintenance operations or periodic cleaning, check the aspect of the 
plastic protection of the copper/aluminum connection. If it is inflated, 
damaged or took off contact the manufacturer representative for 
advice and information.

Summary of Contents for EWAT016CZN-A1

Page 1: ...REV 00 Date 04 2021 Supersedes Installation Maintenance and Operation Manual DEIMHP0140521_00EN Air to water heat pump units with scroll compressors EWYT CZ EWAT CZ...

Page 2: ......

Page 3: ...RESSURE EQUIPMENT 27 12 DISMISSIONAND DISPOSAL 27 List of tables Table 1 Physical properties of R32 refrigerant 5 Table 2 Minimum glycol percentage for low ambient air temperature 11 Table 3 Flow Swit...

Page 4: ...to check possible refrigerant leaks 13 Disable the unit from the mains using the main switch before opening the control panel 14 Check that the unit has been grounded correctly before starting it 15...

Page 5: ...pagation rate is low and nontoxic R32 refrigerant can burn slowly when all the following conditions are present The concentration is between the lower and upper flammability limit LFL UFL Wind velocit...

Page 6: ...it contacts the duct material n Airflow of the emergency mechanical ventilation shall be at least V 0 014 m Where V is air flow in m s m is the amount of refrigerant present in the machine room in kg...

Page 7: ...osphere may damage electrical components 4 MECHANICAL INSTALLATION 4 1 Safety Before installation and commissioning of the machinery the people involved in this activity must have acquired the informa...

Page 8: ...outdoors either on balconies or on the ground provided that the installation area is free of obstacles that could reduce air flow to the condensers coil The unit must be installed on a robust and per...

Page 9: ...y side of the unit must be accessible for postinstallation maintenance operations and vertical air discharge must not be obstructed Figure below shows the minimum space required Figure 4 DUAL unit Whe...

Page 10: ...the main wind direction Frontal wind will disturb the operation of the unit If necessary use a screen to block the wind Ensure that water cannot cause any damage to the location by adding water drains...

Page 11: ...ition The water filter must be installed as close as possible to the unit If the water filter is installed in another part of the water system the Installer must guarantee the cleaning of the water pi...

Page 12: ...Z P H A2 2 43 6 00 Table 4 Operating limits 4 7 3 Preparing and checking the water circuit connection The units have water inputs and outputs for connecting the heat pump to water circuit of the syste...

Page 13: ...300 CO2 Sulphate ion mg SO4 2 l 100 Alkalinity mg CaCO3 l 200 Total Hardness mg CaCO3 l 75 150 Iron mg Fe l 0 2 Ammonium ion mg NH4 l 0 5 Silica mg SiO2 l Chlorine molecular mg Cl2 l 0 5 Note 1 Heat P...

Page 14: ...ater temperature Ref 1 Unit operations in this area require OP 192 HIGH AMBIENT TEMPERATURE KIT Ref 2 Unit operations in this area require the enabling of the Brine version in the controller and the u...

Page 15: ...t to have a water temperature difference of 2 5 K which allows it to operate with the minimum volume mentioned in the previous table However if a smaller temperature differential is set as in the case...

Page 16: ...appropriate antifreeze protection is always maintained Failing to follow the instructions above could result in unit damage 4 ELECTRIC HEATER Option on request A heater tape is instal led on the water...

Page 17: ...d the earth according to IEC 614391 table 1 and 2 and to the local national laws The cables connected to the main switch must be tightened using a pair of keys and respecting the unified clamping valu...

Page 18: ...ompressors must be carried out exclusively by qualified personnel Sharp edges and the surface of the condenser section could cause injury Avoid direct contact and use adequate pro tection device Do no...

Page 19: ...t maintenance could degrade all parts of the units coils compressors frames pipes etc with negative effect on performances and functionality There are two different levels of maintenance which can be...

Page 20: ...trical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and sui tably t...

Page 21: ...X Check the safety valve X Coil section Checking the cleaning of the air heat exchanger Note 6 X Check the cleaning of water heat exchangers Note 6 X Verify that fans are well tightened X Verify coil...

Page 22: ...CZ 7 2 4 Refrigerant circuit scheme Figure 17 Refrigerant circuit P ID diagram for MONO circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LI...

Page 23: ...IMHP0140521_00EN 23 Figure 18 Refrigerant circuit P ID diagram for MONO circuit EWAT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 24: ...24 EWYT CZ EWAT CZ Figure 19 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW...

Page 25: ...nd outlet are indicative Please refer to the machine dimensional diagrams for exact water connections The series is composed by mono one circuit and dual two circuits reversible unit Legend Item Descr...

Page 26: ...raulic circuit Check the oil level in the compressors Chilled Water Yes No N A Piping complete Water System filled and vented Pumps installed operational rotation checked Strainers installed and clean...

Page 27: ...nd III of the classification established by the European Directive 2014 68 EU PED For units belonging to these categories some local regulations require a periodic inspection by an authorized person P...

Page 28: ...Notes...

Page 29: ...y is given for the completeness accuracy reliability of its contents All data and specifications contained therein may be subject to change without notice Refer to the data communicated at the time of...

Page 30: ...DEIMHP0140720_00EN 2021 04 Via Piani di Santa Maria 72 00072 Ariccia Roma Italy Tel 39 06 93 73 11 Fax 39 06 93 74 014 http www daikinapplied eu...

Reviews: