Water temperature sensors

Two temperature sensors determine the water inlet temperature
(13a) and water outlet temperature (13b).

14

Digital controller cable intake

15

Power supply intake

16

OP10 heater tape (optional, not illustrated)

The heater tape is wrapped around the pipework and protects
the evaporator and water circuit in the unit from freezing at cold
outdoor temperatures.

Safety devices

17

Flow switch 

The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against
damage. In case the minimum required flow is not achieved, the
unit will be shut down.

18

Pressure relief valve

The pressure relief valve prevents excessive water pressure in
the water circuit (

3 bar).

Switch box components

19

Cable tie mountings

The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.

20

Terminal block

The terminal block allows easy connection of field wiring.

I

NSTALLATION

 

OF

 

THE

 

UNIT

Selecting the installation location

General guidelines

The unit is designed to be installed in an outdoor location.

Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.

Although the noise produced by the unit during operation is low,
avoid installation near to places where even low noise levels can
be disturbing (e.g., bedroom windows, terraces).

Choose a location where the hot air discharged from the unit will
not cause a nuisance.

There must be sufficient space for air passage and no
obstructions around the air intake and the air exhaust (see

"Installing near a wall or obstacle" on page 4

).

The site must be free from the possibility of flammable gas
leakage in a nearby place.

Install the unit and power cords at least 3 m away from television
and radio sets. This is to prevent interference to images and
sounds.

In coastal areas or other places with salty atmosphere,
corrosion may shorten the life of the unit. Prevent direct
exposure to winds coming from the sea.

Since drain flows out of the unit, do not place anything under the
unit which must be kept away from moisture.

Installing near a wall or obstacle

Where a wall or other obstacle is in the path of the unit’s air
intake or exhaust airflow, the distances as indicated on the
figures below need to be respected.

The wall height on the exhaust side should be 1200 mm or less.

20

19

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

Side view

Top view

>100

>350

1200

>50

>100

>350

Summary of Contents for EWAQ005ACV3P

Page 1: ...INSTALLATION MANUAL EWAQ005ACV3P EWAQ006ACV3P EWAQ007ACV3P EWYQ005ACV3P EWYQ006ACV3P EWYQ007ACV3P Packaged air cooled water chillers and packaged reversible air to water heat pumps...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rg...

Page 3: ...t pump and cooling only versions This chiller range consists of two main versions a heat pump EWYQ version and a cooling only EWAQ version available in 3 standard sizes 5 kW 6 kW and 7 kW Heater tape...

Page 4: ...y operating the user interface When space cooling heating is requested by the room thermostat T the pump will start operating and the unit will switch to cooling mode heating mode The outdoor units wi...

Page 5: ...al power to the unit 3 Heat exchanger 4 Water inlet connection 1 MBSP 5 Water outlet connection 1 MBSP 6 Pump The pump circulates the water in the water circuit 7 Manometer The manometer allows readou...

Page 6: ...operation noise will not be amplified Although the noise produced by the unit during operation is low avoid installation near to places where even low noise levels can be disturbing e g bedroom windo...

Page 7: ...and level of the installation ground so that the unit will not cause any operating vibration or noise after installation 2 Make sure that the unit is installed level 3 Prepare 4 sets of M8 or M10 foun...

Page 8: ...r circuit The total water volume in the water circuit is 100 l In this example no action or adjustment is required Example 2 A heat pump model unit is installed 4 m below the highest point in the wate...

Page 9: ...filled with a weight concentration of glycol as mentioned in the table below Also refer to Checks before start up on page 11 Initial start up at low ambient temperatures Charging the water 1 Connect t...

Page 10: ...inal Protective earth 1 This wiring diagram only applies to the outdoor unit 4 Do not operate the unit by short circuiting protection devices Q1L S1L Field wiring guidelines The field wiring on the un...

Page 11: ...rminals on top of the front part of the digital controller and the terminals inside the unit P1 to 6 P2 to 7 4 Reattach the upper part of the digital controller First begin fitting from the clips at t...

Page 12: ...s available on the user interface UI or handled by the thermostat T space heating or cooling on off o heating cooling changeover heating and cooling schedule timers pr Heating cooling thermostat Remot...

Page 13: ...unit 7 Shut off valves Make sure that the shut off valves are correctly installed and fully open 8 Water pressure Make sure the unit is filled with water and that the water pressure is approximately...

Page 14: ...more than 5 seconds in normal mode s ba pfi and pfj Press these 4 buttons to switch to level 2 3 press again for 5 seconds to switch back to level 1 When level 2 3 is selected the actual permission l...

Page 15: ...9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set...

Page 16: ...carried out at regular intervals If the unit is used for air conditioning application the described checks must be executed at least once a year In case the unit is used for other applications the che...

Page 17: ...ere is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Check that the pump speed setting is on the highest speed III Make sure that the expansion vessel...

Page 18: ...or broken Contact your local Daikin dealer E1 A4P PCB defective in non accessible switch box Contact your local Daikin dealer E5 Overload activation of compressor Check that the unit is operating with...

Page 19: ...ormal 25 kPa high 40 kPa Sound level Sound power 63 dBA 64 dBA 66 dBA 63 dBA 64 dBA 66 dBA Sound pressure at 1 m distance 47 dBA 49 dBA 53 dBA 47 dBA 49 dBA 53 dBA Internal water volume 4 l Nominal wa...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW33165 1D...

Reviews: