Installation manual

12

EWAQ+EWYQ005~007ACV3P

Packaged air-cooled water chillers and

packaged reversible air to water heat pumps

4PW33165-1D

Field settings

The unit should be configured by the installer to match the installation
environment (outdoor climate, etc.) and user expertise. Thereto, a
number of so called field settings are available. These field settings
are accessible and programmable through the digital controller.

Each field setting is assigned a 3-digit number or code, for example
[1-02], which is indicated on the digital controller display. The first
digit [1] indicates the ‘first code’ or field setting group. The second
and third digit [02] together indicate the ‘second code’.

A list of all field settings and default values is given under 

"Field

settings table" on page 13

.  In this same list, we have provided 2

columns to register the date and value of altered field settings at
variance with the default value.

A detailed description of each field setting is given under 

"Detailed

description" on page 12

.

Procedure

To change one or more field settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.

The 

$

 icon (3) will be displayed. The current selected field

setting code is indicated 

;

 (2), with the set value displayed to

the right 

:

 (1).

2

Press the 

bgi

  button to select the appropriate field

setting first code.

3

Press the 

bgj

  button to select the appropriate field

setting second code.

4

Press the 

pfi

  button and 

pfj

  button to change

the set value of the select field setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

Detailed description

[0] User permission level

If required, the digital controller functions available to the user can be
limited by restricting the number of operable buttons. This may
prevent the user from disrupting correct operation of the installation.

Three permission levels are available (see the table below).
Switching between level 1 (default) and level 2/3 is done by pressing
the following 4 buttons at the same time for more than 5 seconds (in
normal mode): 

s

ba

pfi

  and 

pfj

.  Press these 4

buttons to switch to level 2/3, press again for 5 seconds to switch
back to level 1. When level 2/3 is selected, the actual permission level
— either level 2 or level 3 — is determined by the field setting [0-00].

[0-00] User permission level: applicable permission level
number (level 2 or level 3). See the table below.

[1] Weather dependent set point (heat pump models only)

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active, the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift the
target water temperature up or down by a maximum of 5°C. See the
operation manual for more details on weather dependent operation. 

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.

NOTE

Changes made to a specific field setting are only
stored when the 

pr

 button is pressed. Navigating to a

new field setting code or pressing the 

z

  button will

discard the change made.

NOTE

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 13

.

When exiting FIELD SET MODE, “

88

” may be

displayed on the digital controller LCD while the
unit initialises itself.

2

3

1

Button

Permission level

1

2

3

On/off button 

o

operable

operable

operable

Operation changeover 
button 

h

/

c

operable

operable

operable

Sanitary water heating 
button 

w

– Not available –

Sanitary temperature 
adjust buttons 

wbi

wbj

– Not available –

Temperature adjust 
buttons 

bg

i

bg

j

operable

operable

operable

Time adjust buttons

pf

i

pf

j

operable

Programming button 

<

operable

Schedule timer enable/
disable button 

pr

operable

operable

Quiet mode button 

s

operable

Weather dependent 
set point button

ba

operable

Inspection/test 
operation button 

z

operable

Summary of Contents for EWAQ005ACV3P

Page 1: ...INSTALLATION MANUAL EWAQ005ACV3P EWAQ006ACV3P EWAQ007ACV3P EWYQ005ACV3P EWYQ006ACV3P EWYQ007ACV3P Packaged air cooled water chillers and packaged reversible air to water heat pumps...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rg...

Page 3: ...t pump and cooling only versions This chiller range consists of two main versions a heat pump EWYQ version and a cooling only EWAQ version available in 3 standard sizes 5 kW 6 kW and 7 kW Heater tape...

Page 4: ...y operating the user interface When space cooling heating is requested by the room thermostat T the pump will start operating and the unit will switch to cooling mode heating mode The outdoor units wi...

Page 5: ...al power to the unit 3 Heat exchanger 4 Water inlet connection 1 MBSP 5 Water outlet connection 1 MBSP 6 Pump The pump circulates the water in the water circuit 7 Manometer The manometer allows readou...

Page 6: ...operation noise will not be amplified Although the noise produced by the unit during operation is low avoid installation near to places where even low noise levels can be disturbing e g bedroom windo...

Page 7: ...and level of the installation ground so that the unit will not cause any operating vibration or noise after installation 2 Make sure that the unit is installed level 3 Prepare 4 sets of M8 or M10 foun...

Page 8: ...r circuit The total water volume in the water circuit is 100 l In this example no action or adjustment is required Example 2 A heat pump model unit is installed 4 m below the highest point in the wate...

Page 9: ...filled with a weight concentration of glycol as mentioned in the table below Also refer to Checks before start up on page 11 Initial start up at low ambient temperatures Charging the water 1 Connect t...

Page 10: ...inal Protective earth 1 This wiring diagram only applies to the outdoor unit 4 Do not operate the unit by short circuiting protection devices Q1L S1L Field wiring guidelines The field wiring on the un...

Page 11: ...rminals on top of the front part of the digital controller and the terminals inside the unit P1 to 6 P2 to 7 4 Reattach the upper part of the digital controller First begin fitting from the clips at t...

Page 12: ...s available on the user interface UI or handled by the thermostat T space heating or cooling on off o heating cooling changeover heating and cooling schedule timers pr Heating cooling thermostat Remot...

Page 13: ...unit 7 Shut off valves Make sure that the shut off valves are correctly installed and fully open 8 Water pressure Make sure the unit is filled with water and that the water pressure is approximately...

Page 14: ...more than 5 seconds in normal mode s ba pfi and pfj Press these 4 buttons to switch to level 2 3 press again for 5 seconds to switch back to level 1 When level 2 3 is selected the actual permission l...

Page 15: ...9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set...

Page 16: ...carried out at regular intervals If the unit is used for air conditioning application the described checks must be executed at least once a year In case the unit is used for other applications the che...

Page 17: ...ere is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Check that the pump speed setting is on the highest speed III Make sure that the expansion vessel...

Page 18: ...or broken Contact your local Daikin dealer E1 A4P PCB defective in non accessible switch box Contact your local Daikin dealer E5 Overload activation of compressor Check that the unit is operating with...

Page 19: ...ormal 25 kPa high 40 kPa Sound level Sound power 63 dBA 64 dBA 66 dBA 63 dBA 64 dBA 66 dBA Sound pressure at 1 m distance 47 dBA 49 dBA 53 dBA 47 dBA 49 dBA 53 dBA Internal water volume 4 l Nominal wa...