Installation manual

16

EWAQ+EWYQ005~007ACV3P

Packaged air-cooled water chillers and

packaged reversible air to water heat pumps

4PW33165-1D

Error codes

When a safety device is activated, the digital controller LED will be
flashing, and an error code will be displayed. 

A list of all errors and corrective actions can be found in the table
below.

Reset the safety by turning the unit OFF and back ON (by pushing
digital controller ON/OFF button 2 times). In case this procedure for
resetting the safety is not successful, contact your local Daikin dealer.

Error 

code

Failure cause

Corrective action

80

Inlet water temperature 
thermistor error (inlet water 
thermistor broken)

Contact your local Daikin dealer.

81

Outlet water temperature 
thermistor failure (outlet water 
temperature sensor broken)

Contact your local Daikin dealer.

89

Water heat exchanger freeze-up 
failure (due water flow too low)

Refer to error code 

7H

.

Water heat exchanger freeze-up 
failure (due to refrigerant 
shortage)

Contact your local Daikin dealer.

7H

Flow failure (water flow too low 
or no water flow at all, minimum 
required water flow is 9 l/min)

• Check that all shut off valves 

of the water circuit are 
completely open.

• Check if the water filter needs 

cleaning.

• For heat pump models: make 

sure that the unit is working 
within its operating range

- ambient temperature 

>–15°C 

- water temperature >30°C.

Also refer to 

"Initial start-up at 

low ambient temperatures" on 
page 7

.

• Make sure there is no air in 

the system (purge air).

• Check on the manometer that 

there is sufficient water 
pressure. The water pressure 
must be >0.3 bar (water is 
cold), >>0.3 bar (water is hot).

• Check that the pump speed 

setting is on the highest 
speed (III).

• Make sure that the expansion 

vessel is not broken.

• Check that the resistance in 

the water circuit is not too high 
for the pump (refer to 

"Setting 

the pump speed" on page 11

).

A1

A1P PCB defective 
(in accessible switch box)

Contact your local Daikin dealer.

A5

Too low outlet water temperature 
(outlet water temperature 
measured by R1T too low)

Refer to error code 

7H

.

C0

Flow switch failure
(flow switch remains closed 
while pump is stopped)

Check that the flow switch is not 
clogged with dirt.

C4

Heat exchanger thermistor 
failure (heat exchanger 
temperature sensor broken)

Contact your local Daikin dealer.

E1

A4P PCB defective
(in non-accessible switch box)

Contact your local Daikin dealer.

E5

Overload activation of 
compressor

Check that the unit is operating 
within its operating range (refer 
to 

"Technical specifications" on 

page 17

).

Contact your local Daikin dealer.

E6

Compressor start-up failure

Contact your local Daikin dealer.

E7

Fan lock failure (fan is locked)

Check if the fan is not obstructed 
by dirt. If the fan is not 
obstructed, contact your local 
Daikin dealer.

E8

Overcurrent failure

Check that the unit is operating 
within its operating range (refer 
to 

"Technical specifications" on 

page 17

).

EA

Cooling/heating switching failure
(only for heat pump model)

Contact your local Daikin dealer.

F3

Too high discharge temperature
(e.g. due to outdoor coil 
blockage)

Clean the outdoor coil. If the coil 
is clean, contact your local 
Daikin dealer.

F6

Too high condensing pressure 
during cooling (e.g. due to 
outdoor coil blocked by dirt)

Clean the outdoor coil. If the coil 
is clean, contact your local 
Daikin dealer.

Too high condensing pressure 
during cooling (e.g. due to unit 
operating outside its operating 
range)

Check that the unit is operating 
within its operating range (refer 
to 

"Technical specifications" on 

page 17

).

FA

High pressure failure 
(due to unit operating outside its 
operating range)

Check that the unit is operating 
within its operating range (refer 
to 

"Technical specifications" on 

page 17

).

H0

Voltage and current sensor 
failure (sensor broken)

Contact your local Daikin dealer.

H9

Outdoor temperature thermistor 
failure 
(outdoor thermistor is broken)

Contact your local Daikin dealer.

J3

Discharge pipe thermistor failure

Contact your local Daikin dealer.

J6

Outdoor unit heat exchanger 
thermistor broken or 
disconnected

Contact your local Daikin dealer.

L3

Electric component failure

Contact your local Daikin dealer.

L4

Electric component failure

Contact your local Daikin dealer.

L5

Electric component failure

Contact your local Daikin dealer.

P4

Electric component failure

Contact your local Daikin dealer.

U0

Refrigerant failure
(due to refrigerant leak)

Contact your local Daikin dealer.

U2

Main circuit voltage failure

Contact your local Daikin dealer.

U4

Communication error failure

Contact your local Daikin dealer.

U7

Communication error failure

Contact your local Daikin dealer.

UA

Communication error failure

Contact your local Daikin dealer.

Error 

code

Failure cause

Corrective action

Summary of Contents for EWAQ005ACV3P

Page 1: ...INSTALLATION MANUAL EWAQ005ACV3P EWAQ006ACV3P EWAQ007ACV3P EWYQ005ACV3P EWYQ006ACV3P EWYQ007ACV3P Packaged air cooled water chillers and packaged reversible air to water heat pumps...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rg...

Page 3: ...t pump and cooling only versions This chiller range consists of two main versions a heat pump EWYQ version and a cooling only EWAQ version available in 3 standard sizes 5 kW 6 kW and 7 kW Heater tape...

Page 4: ...y operating the user interface When space cooling heating is requested by the room thermostat T the pump will start operating and the unit will switch to cooling mode heating mode The outdoor units wi...

Page 5: ...al power to the unit 3 Heat exchanger 4 Water inlet connection 1 MBSP 5 Water outlet connection 1 MBSP 6 Pump The pump circulates the water in the water circuit 7 Manometer The manometer allows readou...

Page 6: ...operation noise will not be amplified Although the noise produced by the unit during operation is low avoid installation near to places where even low noise levels can be disturbing e g bedroom windo...

Page 7: ...and level of the installation ground so that the unit will not cause any operating vibration or noise after installation 2 Make sure that the unit is installed level 3 Prepare 4 sets of M8 or M10 foun...

Page 8: ...r circuit The total water volume in the water circuit is 100 l In this example no action or adjustment is required Example 2 A heat pump model unit is installed 4 m below the highest point in the wate...

Page 9: ...filled with a weight concentration of glycol as mentioned in the table below Also refer to Checks before start up on page 11 Initial start up at low ambient temperatures Charging the water 1 Connect t...

Page 10: ...inal Protective earth 1 This wiring diagram only applies to the outdoor unit 4 Do not operate the unit by short circuiting protection devices Q1L S1L Field wiring guidelines The field wiring on the un...

Page 11: ...rminals on top of the front part of the digital controller and the terminals inside the unit P1 to 6 P2 to 7 4 Reattach the upper part of the digital controller First begin fitting from the clips at t...

Page 12: ...s available on the user interface UI or handled by the thermostat T space heating or cooling on off o heating cooling changeover heating and cooling schedule timers pr Heating cooling thermostat Remot...

Page 13: ...unit 7 Shut off valves Make sure that the shut off valves are correctly installed and fully open 8 Water pressure Make sure the unit is filled with water and that the water pressure is approximately...

Page 14: ...more than 5 seconds in normal mode s ba pfi and pfj Press these 4 buttons to switch to level 2 3 press again for 5 seconds to switch back to level 1 When level 2 3 is selected the actual permission l...

Page 15: ...9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set...

Page 16: ...carried out at regular intervals If the unit is used for air conditioning application the described checks must be executed at least once a year In case the unit is used for other applications the che...

Page 17: ...ere is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Check that the pump speed setting is on the highest speed III Make sure that the expansion vessel...

Page 18: ...or broken Contact your local Daikin dealer E1 A4P PCB defective in non accessible switch box Contact your local Daikin dealer E5 Overload activation of compressor Check that the unit is operating with...

Page 19: ...ormal 25 kPa high 40 kPa Sound level Sound power 63 dBA 64 dBA 66 dBA 63 dBA 64 dBA 66 dBA Sound pressure at 1 m distance 47 dBA 49 dBA 53 dBA 47 dBA 49 dBA 53 dBA Internal water volume 4 l Nominal wa...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW33165 1D...

Reviews: