Installation manual

2

EWAQ+EWYQ005~007ACV3P

Packaged air-cooled water chillers and

packaged reversible air to water heat pumps

4PW33165-1D

A

CCESSORIES

T

YPICAL

 

APPLICATION

 

EXAMPLES

These application examples are given for illustration purposes only.

Application 1

Space heating and cooling application (without thermostat).

The digital controller (DC) is installed indoors and allows the user to
turn the unit (1) ON or OFF, to select between cooling and heating
mode (only in case of a heat pump model) and to set the water
temperature. When the unit is turned on, it will provide water at the
set temperature to the fan coil units (FCU1..3).

Application 2

Space cooling and heating application with a room thermostat
suitable for cooling/heating changeover connected to the unit.

Pump operation and space heating and cooling (space cooling
and heating application with a room thermostat suitable for
cooling/heating changeover connected to the unit 
)

According to the season, the customer will select cooling or
heating on the room thermostat (T). This selection is not
possible by operating the user interface.

When space cooling/heating is requested by the room
thermostat (T), the pump will start operating and the unit will
switch to “cooling mode”/”heating mode”. The outdoor units will
start operating to achieve the target leaving cold/hot water
temperature.

The ON/OFF setting of the heating/cooling operation is done by
the room thermostat and cannot be done by the user interface
on the unit.

Installation manual

1

Operation manual

1

Shut-off valve

2

Wiring diagram sticker 
(inside top unit cover)

1

Remote controller kit
(digital controller, 4 fixing screws and 2 plugs)

1

1

Reversible heat pump

7

Bypass valve

2

Plate heat exchanger

FCU1..3

Fan coil unit 
(field supply)

3

Expansion vessel

4

Pump

DC

Digital controller

5

Shut-off valve

RT1..3

Room thermostat 
(field supply)

6

Motorised valve (field supply)

FCU1

M

RT1

FCU2

M

RT2

FCU3

M

RT3

DC

2

3 4

5

1

5

6

7

1

Reversible heat pump

7

Shut-off valve

2

Plate heat exchanger

FCU1..3

Fan coil unit 
(field supply)

3

Expansion vessel

4

Pump

T

Room thermostat or 
room thermostat with 
cooling/heating switch
(field supply)

5

Shut-off valve

6

Collector (field supply)

Make sure to connect the thermostat wires to the correct
terminals (see 

"Connection of the thermostat cable" on

page 10

).

T

6

2

3 4

5

1

7

FCU1

FCU2

FCU3

Summary of Contents for EWAQ005ACV3P

Page 1: ...INSTALLATION MANUAL EWAQ005ACV3P EWAQ006ACV3P EWAQ007ACV3P EWYQ005ACV3P EWYQ006ACV3P EWYQ007ACV3P Packaged air cooled water chillers and packaged reversible air to water heat pumps...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rg...

Page 3: ...t pump and cooling only versions This chiller range consists of two main versions a heat pump EWYQ version and a cooling only EWAQ version available in 3 standard sizes 5 kW 6 kW and 7 kW Heater tape...

Page 4: ...y operating the user interface When space cooling heating is requested by the room thermostat T the pump will start operating and the unit will switch to cooling mode heating mode The outdoor units wi...

Page 5: ...al power to the unit 3 Heat exchanger 4 Water inlet connection 1 MBSP 5 Water outlet connection 1 MBSP 6 Pump The pump circulates the water in the water circuit 7 Manometer The manometer allows readou...

Page 6: ...operation noise will not be amplified Although the noise produced by the unit during operation is low avoid installation near to places where even low noise levels can be disturbing e g bedroom windo...

Page 7: ...and level of the installation ground so that the unit will not cause any operating vibration or noise after installation 2 Make sure that the unit is installed level 3 Prepare 4 sets of M8 or M10 foun...

Page 8: ...r circuit The total water volume in the water circuit is 100 l In this example no action or adjustment is required Example 2 A heat pump model unit is installed 4 m below the highest point in the wate...

Page 9: ...filled with a weight concentration of glycol as mentioned in the table below Also refer to Checks before start up on page 11 Initial start up at low ambient temperatures Charging the water 1 Connect t...

Page 10: ...inal Protective earth 1 This wiring diagram only applies to the outdoor unit 4 Do not operate the unit by short circuiting protection devices Q1L S1L Field wiring guidelines The field wiring on the un...

Page 11: ...rminals on top of the front part of the digital controller and the terminals inside the unit P1 to 6 P2 to 7 4 Reattach the upper part of the digital controller First begin fitting from the clips at t...

Page 12: ...s available on the user interface UI or handled by the thermostat T space heating or cooling on off o heating cooling changeover heating and cooling schedule timers pr Heating cooling thermostat Remot...

Page 13: ...unit 7 Shut off valves Make sure that the shut off valves are correctly installed and fully open 8 Water pressure Make sure the unit is filled with water and that the water pressure is approximately...

Page 14: ...more than 5 seconds in normal mode s ba pfi and pfj Press these 4 buttons to switch to level 2 3 press again for 5 seconds to switch back to level 1 When level 2 3 is selected the actual permission l...

Page 15: ...9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set...

Page 16: ...carried out at regular intervals If the unit is used for air conditioning application the described checks must be executed at least once a year In case the unit is used for other applications the che...

Page 17: ...ere is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Check that the pump speed setting is on the highest speed III Make sure that the expansion vessel...

Page 18: ...or broken Contact your local Daikin dealer E1 A4P PCB defective in non accessible switch box Contact your local Daikin dealer E5 Overload activation of compressor Check that the unit is operating with...

Page 19: ...ormal 25 kPa high 40 kPa Sound level Sound power 63 dBA 64 dBA 66 dBA 63 dBA 64 dBA 66 dBA Sound pressure at 1 m distance 47 dBA 49 dBA 53 dBA 47 dBA 49 dBA 53 dBA Internal water volume 4 l Nominal wa...