5/16
Breadcrumb
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
5.C
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
Tank
5.D
[6-01]
R/W
0~10°C, step: 1°C
0°C
5.E
R/O
0: 2-points
1: Slope-Offset
User settings
└─
Quiet
7.4.1
R/W
0: OFF
1: Manual
2: Automatic
7.4.3
R/W
0: Quiet
1: More Quiet
2: Most Quiet
└─
Electricity price
7.5.1
R/W
0,00~990/kWh
1/kWh
7.5.2
R/W
0,00~990/kWh
1/kWh
7.5.3
R/W
0,00~990/kWh
1/kWh
User settings
7.6
R/W
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─
Configuration wizard
└─
System
9.1.3.2
[E-03]
R/W
0: no heater (*7)
2: 3V (*4)
3: 6V (*5)
4: 9W (*6)
9.1.3.3
[E-05]
[E-06]
[E-07]
R/O
Integrated'
9.1.3.4
[4-06]
R/W
0: Manual
1: Automatic
2: Auto SH reduced/ DHW ON
3: Auto SH reduced/ DHW OFF
4: Auto SH normal/ DHW OFF
9.1.3.5
[7-02]
R/W
0: Single zone
1: Dual zone
9.1.3.6
[E-0D]
R/W
0: No
1: Yes
9.1.3.7
[6-02]
R/W
0~10kW, step: 0,2kW
0kW
9.1.3.8
[C-02]
R/W
0: Off
1: Direct (SH)
2: Indirect (DHW) (*3)
3: Indirect (DHW + SH)
9.2.4
[D-07]
R/W
0: No
1: Yes (DHW)
2: Yes (DHW + SH)
└─
Backup heater
9.1.4.1
[5-0D]
R/W
0: 230V, 1~ (*4, *5, *7)
2: 400V, 3~ (*6)
9.1.4.2
[4-0A]
R/W (*5,
*6, *7)
R/O (*4)
0: 1 (*4, *7)
1: 1/1+2 (*5, *6)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.1.4.3
[6-03]
R/O
0~10kW, step: 0,2kW
0kW
2kW (*5)
3kW (*4, *6, *7)
9.1.4.4
[6-04]
R/W (*5,
*6)
R/O (*4,
*7)
0~10kW, step: 0,2kW
0kW (*4)
3kW (*7)
4kW (*5)
6kW (*6)
└─
Main zone
9.1.5.1
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.5.2
[C-07]
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
9.1.5.3
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
9.1.5.4
R/W
0: No
1: Yes
9.1.5.5
R/W
0: 2-points
1: Slope-Offset
9.1.6
[1-00]
R/W
-40~5°C, step: 1°C
-15°C
Low ambient temp. for DHW WD curve.
Margin
WD curve type
mode
Level
High
Medium
Low
Gas price
BUH type
Domestic hot water
Emergency
Number of zones
Glycol Filled system
BSH capacity
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Bivalent
Solar
Emitter type
Control
Setpoint mode
Schedule
WD curve type
Low ambient temp. for LWT main zone heating WD curve.
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA*3V_(*7) *EKECBUA*6V_(*8) *EKECBUA*9W_(*9) BUH less_
(*10) 16P
4P681797-1 - 2022.01