10
|
Configuration
Installer reference guide
170
EPRA14~W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
#
Code
Description
[2.5]
[1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating in [2.5]
Heating
WD curve
:
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
T
t
Target leaving water temperature (main zone)
T
a
Outdoor temperature
Set weather-dependent heating in [9.l]
Overview field settings
:
▪
[1-00]: Low outdoor ambient temperature. –
40°C~+5°C
▪
[1-01]: High outdoor ambient temperature.
10°C~25°C
▪
[1-02]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
ambient
temperature.
[9‑01]°C~[9‑00]°C
Note:
This value should be higher than [1‑03]
as for low outdoor temperatures warmer water
is required.
▪
[1-03]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
ambient
temperature.
[9‑01]°C~min(45, [9‑00])°C
Note:
This value should be lower than [1‑02] as
for high outdoor temperatures less warm water
is required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4]=2):