Outline of Control
ESIE09-05
38
Function
6. Outline of Control
6.1 Thermostat Sensor in Remote Controller (only for Z-
control)
Temperature is controlled by both the thermostat sensor in remote controller and air suction
thermostat in the AHU. (This is however limited to when the field setting for the thermostat
sensor in remote controller is set to “Use.”)
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
Ex: When cooling
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 30°C (A
→
F):
Body thermostat sensor is used for temperatures from 18°C to 23°C (A
→
C).
Remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C
→
E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E
→
F).
And, assuming suction temperature has changed from 30
°
C to 18
°
C (F
→
A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F
→
D).
Remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D
→
B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B
→
A).
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...