ESIE09-05
Combination Table
General Information
5
2. Combination Table
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity.
Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K, air temperature = 27°C DB /
19°C WB.
Note:
If conflicting result occurs, capacity selection has priority over volume.
Control box
Expansion valve kit
Outdoor unit
EKEQDCBV3 EKEQFCBV3
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
single
phase
ERQ100
P
P
P
P
P
P
-
ERQ125
P
P
P
P
P
P
P
ERQ140
P
P
-
P
P
P
P
Allowed heat exchanger volume (dm
3
) Allowed heat exchanger capacity (kW)
EKEXV class
Minimum
Maximum
Minimum
Maximum
63
1.66
2.08
6.3
7.8
80
2.09
2.64
7.9
9.9
100
2.65
3.3
10
12.3
125
3.31
4.12
12.4
15.4
140
4.13
4.62
15.5
17.6