ESIE09-05
Special Control
Function
31
3.5 Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator
Operation
Compressor
OFF
Outdoor unit fan
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Four way valve
Keep former condition.
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve (EV3)
0 pls
Hot gas bypass valve (SVP)
OFF
Ending conditions
2 min.