Troubleshooting by Remote Controller
ESIE09-05
160
Troubleshooting
Outdoor Unit
LA
c
Malfunction of power unit
—
LC
c
Malfunction of transmission between inverter and control PC board
P1
c
High voltage of capacitor in main inverter circuit.
System
U0
w
Low pressure drop due to refrigerant shortage or electronic expansion
valve failure
U1
c
Reverse phase / open phase
—
U2
c
Power supply insufficient or instantaneous failure
U3
c
Check operation is not completed.
U4
c
Malfunction of transmission between AHUs and outdoor units
U5
x
Malfunction of transmission between remote controller and AHU
U5
c
Failure of remote controller PC board or setting during control by remote
controller
U7
c
Malfunction of transmission between outdoor units
—
U8
c
Malfunction of transmission between main and sub remote controllers
(malfunction of sub remote controller)
U9
c
Malfunction of transmission between AHU and outdoor unit in the same
system
—
UA
c
Excessive number of AHUs
UC
w
Address duplication of central remote controller
UE
c
Malfunction of transmission between central remote controller and AHU
—
UF
c
System is not set yet
UH
c
Malfunction of system, refrigerant system address undefined
w
: ON
x
: OFF
c
: Blink
Malfunction
code
Operation
lamp
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...