ESIE09-05
Basic Control
Function
23
2. Basic Control
2.1 Normal Operation
Cooling Operation
Heating Operation
+
Heating operation is not functional at an outdoor air temperature of 24
°
CDB or more.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan
Cooling fan control
⎯
Four way valve
OFF
⎯
Main electronic expansion valve (EV1)
480 pls
⎯
Subcooling electronic expansion valve
(EV3)
PI control
⎯
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan
STEP 7 or 8
⎯
Four way valve
ON
⎯
Main electronic expansion valve (EV1)
PI control
⎯
Subcooling electronic expansion valve
(EV3)
PI control
⎯
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...