Precautions for New Refrigerant (R-410A)
ESIE09-05
242
Precautions for New Refrigerant (R-410A)
1. Flaring tool
Specifications
•
Dimension A
Differences
•
Change of dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
Flare gauge
Nominal size
1/4
3/8
1/2
5/8
3/4
Tube O.D.
Do
6.35
9.52
12.70
15.88
19.05
Class-2 (R-410A)
9.1
13.2
16.6
19.7
24.0
Class-1 (Conventional)
9.0
13.0
16.2
19.4
23.3
+
0
−
0.4
Unit:mm
A
Dimension A
For class-1: R-407C
For class-2: R-410A
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...