background image

ERHQ011~W1 + ERLQ011~W1

Outdoor unit for air to water heat pump

4PW54249-1

Installation manual

2

Make certain that all electrical work is carried out by qualified
personnel according to the local laws and regulations and this
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or fire.

Make sure that all wiring is secure, using the specified wires and
ensuring that external forces do not act on the terminal
connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units, and wiring
the power supply, form the wires so that the frontside panel can
be securely fastened.
If the frontside panel is not in place, overheat of the terminals,
electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work, ventilate the
area immediately.
Toxic gas may be produced if refrigerant gas comes into contact
with fire.

Do not touch the refrigerant pipes during and immediately after
operation as the refrigerant pipes may be hot or cold, depending
on the condition of the refrigerant flowing through the refrigerant
piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant
pipes. To avoid injury, give the pipes time to return to normal
temperature or, if you must touch them, be sure to wear proper
gloves.

After completing the installation work, check to make sure that
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.

When planning to relocate former installed units, you must first
recover the refrigerant after the pump down operation. Refer to
chapter "Pump down operation" on page 11.

Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.

Be sure to install an earth leakage circuit breaker in accordance
with relevant local and national regulations. Failure to do so may
cause electrical shock and fire.

Caution

Earth the unit.
Earthing resistance should be according to national regulations
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire.
Incomplete earthing may cause electric shocks.

Gas pipe.
Ignition or explosion may occur if the gas leaks.

Water pipe.
Hard vinyl tubes are not effective earths.

Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning
bolt.

Install drain piping according to this installation manual to
ensure good drainage, and insulate the pipe to prevent
condensation. See combination table in "Possible options" on
page 3.
Improper drain piping may cause water leakage, and make the
furnitures get wet.

Install the indoor and outdoor units, power wire and connecting
wire at least 1 meter away from televisions or radios to prevent
image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)

Do not rinse the outdoor unit. This may cause electric shocks or
fire.

Do not install the unit in places such as the following:

Where there is mist of mineral oil, oil spray or vapour for
example a kitchen.
Plastic parts may deteriorate, and cause them to fall out or
water to leak.

Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.

Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.

Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled.
Such gases may cause a fire.

Where the air contains high levels of salt such as that near
the ocean.

Where voltage fluctuates a lot, such as that in factories.

In vehicles or vessels.

Where acidic or alkaline vapour is present.

Do not allow a child to mount on the outdoor unit or avoid
placing any object on the unit. Falling or tumbling may result in
injury.

For use of units in applications with temperature alarm settings it
is advised to foresee a delay of 10 minutes for signalling the
alarm in case the alarm temperature is exceeded. The unit may
stop for several minutes during normal operation for "defrosting
the unit", or when in "thermosta-stop" operation.

B

EFORE

 

INSTALLATION

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read "Precautions on refrigerant piping" on page 6 carefully and
follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).

The connected indoor unit must be the EKHBH/X016 unit
designed exclusively for R410A.

Installation

For installation of the indoor unit, refer to the indoor unit
installation manual.

Never operate the unit without the thermistor (R3T, R4T) or
pressure sensors (S1NPH, S1PH), burning of the compressor
may result.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

Since maximum working pressure is 4.0 MPa or 40 bar,
pipes of larger wall thickness may be required. Refer to
paragraph "Selection of piping material" on page 6.

Summary of Contents for ERLQ011BAV3

Page 1: ...STALLATION MANUAL ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1 ERLQ011BAV3 ERLQ014BAV3 ERLQ016BAV3 ERLQ011BAW1 ERLQ014BAW1 ERLQ016BAW1 Outdoor unit for air to water heat pum...

Page 2: ...1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H L A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2...

Page 3: ...prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en u...

Page 4: ...t does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen depletion Be sure to use only the specified accessories and parts for installat...

Page 5: ...ns on page 3 Improper drain piping may cause water leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or...

Page 6: ...rinding works where a lot of dust is created the unit must be covered Do not place any objects or equipment on top of the unit top plate Do not climb sit or stand on top of the unit Be sure that suffi...

Page 7: ...l not affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is not affected by the snow if necessary construct a lateral canopy PRECAUTIONS ON INSTALLATION Check the s...

Page 8: ...REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH A Location of the 2 fixation holes on the front side of the unit B Location of the 2 fixation holes on the rear side of the unit C Wires field supply S...

Page 9: ...ded when passing copper tubes through walls Piping should be mounted so that the flare is not subjected to mechanical stress Flaring guidelines Flares should not be re used New ones should be made in...

Page 10: ...t the operating pressure will be low for example when cooling will be performed while the outside air temperature is low sufficiently seal the flare nut in the stop valve on the gas line with silicon...

Page 11: ...tion Be careful not to let the indoor and outdoor piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as...

Page 12: ...inimum gauge pressure of 0 2 MPa 2 bar Never set the gauge pressure higher than the maximum operation pressure of the unit i e 4 0 MPa 40 bar 2 2 Test for leaks by applying a bubble test solution to a...

Page 13: ...syphon attached or not and position the cylinder accordingly NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official nati...

Page 14: ...ally 5 Once operation stops after 3 to 5 minutes close the liquid stop valve and the gas stop valve 6 The pump down operation is now finished The remote controller may display U4 and the indoor pump m...

Page 15: ...re the wiring in the order shown below 1 Secure the earth wire to the stop valve attachment plate so that it does not slide 2 Secure the earth wire to the stop valve attachment plate one more time alo...

Page 16: ...r unit for wiring of indoor unit etc Attach an earth leakage circuit breaker and fuse to the power supply line See figure 6 In wiring make certain that prescribed wires are used carry out complete con...

Page 17: ...ase protection circuit forced the unit to stop check if all phases are existing If this is the case shut off the power supply to the unit and replace two of three phases Turn on power again and start...

Page 18: ...ntling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation UNIT SPECIFICATIONS Technical specifications Electrica...

Page 19: ...y S1NPH Pressure sensor S1PH Pressure switch high TC Signal transmission circuit for V3 models only V1R Power module for V3 models only V1R V2R Power module for W1 models only V2R V3R Diode module for...

Page 20: ...4PW54249 1 Copyright Daikin...

Reviews: