When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knock-out hole.
(See figure 3)
When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knock-out hole from
cutting the wires.
■
Follow the electric wiring diagram for electrical wiring works.
■
Form the wires and fix the cover firmly so that the cover may be
fit in properly.
Precautions on wiring of power supply and inter-unit
wiring
■
Use a round crimp-style terminal for connection to the power
supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following
instruction.
-
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
-
When connecting wires of the same gauge, connect them
according to the below figure.
■
Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.
■
Over-tightening the terminal screws can damage the screws.
■
See the table below for tightening torques for the terminal
screws.
■
Refer to the installation manual attached to the indoor unit for
wiring of indoor unit, etc.
■
Attach an earth leakage circuit breaker and fuse to the power
supply line. (See figure 6)
■
In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.
Specifications of standard wiring components
For V3 models: Equipment complying with EN/IEC 61000-3-12
(1)
The wiring diagram can be found on the inside of the front plate of the
unit.
1
Wire
2
Bush
3
Nut
4
Frame
5
Hose
A
Inside
B
Outside
Tightening torque (N•m)
M4 (X1M)
1.2~1.8
M5 (X1M)
2.0~3.0
M5 (EARTH)
3.0~4.0
1
Earth leakage circuit breaker
2
Fuse
3
Remote controller
1
2 3
1
Round pressure terminal
2
Cut out section
3
Cup washer
ERHQ_V3
ERLQ_V3
ERHQ_W1
ERLQ_W1
Phase and frequency
1N~ 50 Hz
3N~ 50 Hz
Voltage
220~240 V
380~415 V
Recommended field
fuse
32
A
20 A
Minimum circuit
amps
(a)
(a) Stated values are maximum values (see electrical data of combination with
indoor unit for exact values).
28.2 A
28.7 A
13.5 A
14 A
Wire type of wiring
between the units
Minimum cable section of 2.5 mm
2
and applicable for 230 V
NOTE
Select all cables and wire sizes in accordance with
relevant local and national regulations.
After finishing the electrical work, confirm that each electric
part and terminal inside the electric part box is connected
securely.
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and
≤
75 A per phase.