background image

ERAP110~170MBYNN
Air-cooled condensing units
4PW22680-1E

Installation manual

4

4

After completion of procedure step 3, perform an “initial start”
test:

4.1 Start the compressor and wait for the compressor to go through

the star/delta.
Carefully check during start-up:

that compressor is not producing any abnormal noise or
vibration;

that high pressure rises and low pressure drops within 10
seconds after start to evaluate if the compressor is not
operating in reverse due to wrong wiring;

that no safeties are activated.

4.2 Stop the compressor after 10 seconds.

Fine-tuning of refrigerant charge while unit is in operation

5

Use the 3/8” valve on the suction side of the compressor for fine-
tuning of the refrigerant charge and make sure to charge the
refrigerant in its liquid state.

5.1 For fine-tuning of the refrigerant charge, the compressor must

operate at full load (100%).

5.2 Verify the superheat and subcooling:

superheat must be between 3 and 8 K

subcooling must be between 3 and 8 K

5.3 Verify the oil sightglass. Level must be within the sightglass.

5.4 Verify the liquid-line sightglass. It should be sealed and not

indicate moisture in the refrigerant.

5.5 As long as the liquid-line sightglass is not sealed, add refrigerant

in steps of 1 kg and wait until the unit runs in stable conditions.
Repeat the complete procedure step 5 until the liquid-line
sightglass is sealed.
The unit must have the time to stabelize which means that this
charging has to be done in a smooth way.

6

Note down the superheat and subcooling for future reference.

7

Fill out the total refrigerant charge on the unit nameplate and on
the refrigerant charge label supplied with the product.

F

IELD

 

WIRING

Parts table

F1,2,3U .................. Main fuses for the unit
H1P ........................ Indication lamp general operation
H2P ........................ Indication lamp alarm
H3P ........................ Indication lamp operation circuit
L1,2,3 ..................... Main terminals
PE .......................... Main earth terminal
S6S ........................ Changeable input 1
S9L......................... Contact that closes if the fan or pump is working
S10S ...................... Changeable input 2
S11S ...................... Changeable input 3
S12S ...................... Changeable input 4
S13S ...................... Main isolator switch
- - - ......................... Field wiring

Power circuit and cable requirements

1

The electrical power supply to the unit should be arranged so
that it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit.

Connection of the air-cooled condensing unit power supply

1

Using the appropriate cable, connect the power circuit to the L1,
L2 and L3 terminals of the unit.

In case the option "main isolator switch" is installed on the unit,
the power circuit must be connected to the terminals 2, 4 and 6
of the main isolator switch.

2

Connect the earth conductor (yellow/green) to the earthing
terminal PE.

Installation of the thermostat sensor (R4T)

The thermostat sensor is provided with a cable length of 12 m and
can be found rolled up in the switchbox.

In case of a water cooled evaporator, this sensor can be
mounted in a sensor holder on the evaporator.

In case of an air handling unit, this sensor can be mounted in a
sensor holder in the air cooled evaporator water circuit.

Refer also to 

"Annex I" on page 7

 for unit setup examples.

Interconnection cables

Be sure to interlock so, that the compressor will not come into
operation unless the fan is operated. For this purpose 2 spare
terminals are provided in the switch box. Refer to the wiring
diagram supplied with the unit.

Voltage free contacts
The controller is provided with some voltage free contacts to
indicate the status of the unit. These voltage free contacts can
be wired as described on the wiring diagram. The maximum
allowable current is 4 A.

Remote inputs
Besides the voltage free contacts, there are also possibilities to install
remote inputs. They can be installed as shown on the wiring diagram.

Cable for remote digital controller 

(See remote digital

controller in the operation manual)

1

A remote digital controller can be connected to the PCB inside
the unit by means of a 6-ray cable and a connector located on
the rear side of the remote digital controller in case you prefer to
operate the unit from a distance. You are allowed to use a cable
of up 

to  600 metres.

 Specifications of the cable: 6-ray telephone

cable with a maximum cable resistance of 0.1 

/m.

NOTE

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance with
the wiring diagram supplied with the unit and the
instructions given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

NOTE

Verify on the wiring diagram all electrical actions
mentioned above, in order to understand the operation
of the unit more deeply.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

Summary of Contents for ERAP110MBYNN

Page 1: ...ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN INSTALLATION MANUAL Air cooled condensing units...

Page 2: ...ji t no E pou it modul F v souladu s osv d en m G Kategorie rizik H Viz tak n sleduj c strana 15 kako je izlo eno u A i pozitivno ocijenjeno od strane B prema Certifikatu C kako je izlo eno u Datoteci...

Page 3: ...l stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 4: ...BMS Connection MODBUS J BUS BACNET LON Features Stepless capacity control 30 100 Low ambient operation 15 C Liquid line solenoid valve Voltage free contacts general operation pump or fan contact alarm...

Page 5: ...he length of the ropes 1 to be used for lifting are 6 m minimum each 2 The unit is shipped with wooden beams 2 under it these have to be removed before installation UNPACKING AND PLACING THE UNIT 1 Re...

Page 6: ...mmediately when exposed to air Open the liquid stop valve discharge stop valve and suction valve if provided Vacuum the unit and perform a leak test Charging the unit 1 Perform an integral pre start i...

Page 7: ...n each phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Connection of the air cooled condensing unit power supply 1 Using the appropriate c...

Page 8: ...ons the user password is asked by default when resetting a safety This password however can be changed to or to Remote digital controller address To avoid damage to the controllers liquid crystals dur...

Page 9: ...turn the fan pump on or off manually This means that when the unit is off the fan pump can also be turned on at any time to check the pump Defining the BMS settings The BMS parameters allowing communi...

Page 10: ...nted in a holder on the air cooled evaporator The setpoint for the temperature of the cooling battery will change depending on the relative humidity in the room For this purpose a relative humidity se...

Page 11: ...cuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency s...

Page 12: ...4PW22680 1E Copyright Daikin...

Reviews: