ERAP110~170MBYNN
Air-cooled condensing units
4PW22680-1E

Installation manual

6

Defining of the changeable digital inputs and outputs

Besides locked digital inputs and outputs there are a number of
changeable digital inputs and outputs of which the function can be
chosen from several possibilities.

Possible functions for changeable digital inputs are:

: no function is appointed to the changeable digital input.

 

: no function is appointed to the changeable digital input,

but the input status can be read in the "input/output" menu.

 

: to remotely switch the unit on or off.

 

: to switch between setpoints.

   

:  to limit the capacity of the unit to the

entered values.

Possible functions for the changeable digital output are:

 

: no function is appointed to the changeable digital

output.

 

: no function is appointed to the changeable digital

output, but the output is closed.

   

:  can be used to steer a second evaporator

pump.

   

: indicates when the unit is working at 100%.

Possible configurations for the changeable analog input are:

: no function is appointed to the changeable analog input.

 

:

 

:

 

:

 

:

This allows the user to define a setpoint in function of an analog input
as mentioned above. Refer to 

"Defining the setpoint signal setting" on

page 6

.

Defining the setpoint signal setting

The setpoint signal is used to change the setpoint by an external
analog input signal on the unit.

Example

Steering the fan/pump manually

There is the possibility to turn the fan/pump on or off manually. This
means that when the unit is off, the fan/pump can also be turned on
at any time to check the pump.

Defining the BMS settings

The BMS parameters allowing communication between the unit and
the supervisory system can be modified with the 

 

 and

the 

 

  screen of the service menu. The BMS

parameters are:

 

 screen:

   

:  if set to 

  (yes), the unit can be

commanded and configured from a supervisory system. If set to

  (no), the supervisory system can only read out values but

cannot modify them.

 

: used to address the PCB.

: indicates the communication protocol. If the optional

gateway is used to connect the units to a supervisory system,
the protocol is 

 

.

 

 screen:

 

: indicates the type of serial connection. The default

is set to 

!"

.

   

: indicates the speed of communication. The default

setting of 

# $%&

 must be used when the optional gateway

is connected.

Defining the thermostat settings

Defining the thermostat settings for inlet and outlet water temperature
of a, b and c can only be set in the service menu.

H

OW

 

TO

 

CONTINUE

After installation and connection of the packaged air-cooled
condensing unit, the complete system should be checked and tested
as described in "Checks before initial start-up" in the operation
manual supplied with the unit.

Fill out the brief operation instructions form and fix it visibly near the
operating site of the refrigeration system.

in setpoints menu

in service menu


Remark

 '

 is only 

available when input 

 (

 

 or 

 

) is selected.

Result

Display in readout menu

A

at 0 V 

 12.0°C

 ( )

B

at 1 V 

 12.0°C + 5.0°C = 17.0°C

 ( *)

+

  (  *)

  (  *)

,- .

 ((

 ' ( ")

B

1 V

A

0 V

To define the thermostat settings of the
inlet and outlet water temperature.

,-  

 (! (" ()

(")

Summary of Contents for ERAP110MBYNN

Page 1: ...ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN INSTALLATION MANUAL Air cooled condensing units...

Page 2: ...ji t no E pou it modul F v souladu s osv d en m G Kategorie rizik H Viz tak n sleduj c strana 15 kako je izlo eno u A i pozitivno ocijenjeno od strane B prema Certifikatu C kako je izlo eno u Datoteci...

Page 3: ...l stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 4: ...BMS Connection MODBUS J BUS BACNET LON Features Stepless capacity control 30 100 Low ambient operation 15 C Liquid line solenoid valve Voltage free contacts general operation pump or fan contact alarm...

Page 5: ...he length of the ropes 1 to be used for lifting are 6 m minimum each 2 The unit is shipped with wooden beams 2 under it these have to be removed before installation UNPACKING AND PLACING THE UNIT 1 Re...

Page 6: ...mmediately when exposed to air Open the liquid stop valve discharge stop valve and suction valve if provided Vacuum the unit and perform a leak test Charging the unit 1 Perform an integral pre start i...

Page 7: ...n each phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Connection of the air cooled condensing unit power supply 1 Using the appropriate c...

Page 8: ...ons the user password is asked by default when resetting a safety This password however can be changed to or to Remote digital controller address To avoid damage to the controllers liquid crystals dur...

Page 9: ...turn the fan pump on or off manually This means that when the unit is off the fan pump can also be turned on at any time to check the pump Defining the BMS settings The BMS parameters allowing communi...

Page 10: ...nted in a holder on the air cooled evaporator The setpoint for the temperature of the cooling battery will change depending on the relative humidity in the room For this purpose a relative humidity se...

Page 11: ...cuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency s...

Page 12: ...4PW22680 1E Copyright Daikin...

Reviews: