Installation manual

1

ERAP110~170MBYNN

Air-cooled condensing units

4PW22680-1E

C

ONTENTS

Page

Introduction ....................................................................................... 1

Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 1
Options and features ................................................................................. 1

Operation range ................................................................................ 2

Main components.............................................................................. 2

Selection of location .......................................................................... 2

Inspecting and handling the unit ....................................................... 2

Unpacking and placing the unit ......................................................... 2

Important information regarding the refrigerant used........................ 3

Refrigerant circuit .............................................................................. 3

Sizing and installation of the refrigerant circuit .......................................... 3
Connecting the unit to the refrigerant circuit .............................................. 3
Charging the unit ....................................................................................... 3

Field wiring ........................................................................................ 4

Parts table.................................................................................................. 4
Power circuit and cable requirements ........................................................ 4
Connection of the air-cooled condensing unit power supply ..................... 4
Installation of the thermostat sensor (R4T) ............................................... 4
Interconnection cables............................................................................... 4
Cable for remote digital controller .............................................................. 4

Before starting................................................................................... 5

Customization in the service menu ................................................... 5

How to continue................................................................................. 6

Thank you for purchasing this Daikin air conditioner.

I

NTRODUCTION

The Daikin ERAP110~170MBYNN air-cooled condensing units are
designed for outdoor installation and used for cooling applications
only. The units are available in 3 standard sizes with nominal cooling
capacities of 100, 135 and 160 kW.

The present installation manual describes the procedures for
unpacking, installing and connecting the ERAP units.

Technical specifications

(1)

Electrical specifications

(1)

Options and features

(1)

Options

Suction stop valve

Ampere and voltmeter

Main isolator switch

Dual pressure relief valve on the condenser

Low noise operation

Condenser protection grills

BMS Connection (MODBUS/J-BUS, BACNET, LON)

Features

Stepless capacity control (30%~100%)

Low ambient operation (–15°C)

Liquid line solenoid valve

Voltage free contacts
-

general operation/pump or fan contact

-

alarm

-

operation circuit

Changeable voltage free contacts
-

100% unit signal

-

second evaporator pump

Remote input
-

interlock contacts for e.g. water or airflow

Changeable remote inputs
-

remote start/stop

-

enable/disable capacity limitation

(2)

Multiple language selection

Schedule timer

ERAP110MBYNN
ERAP150MBYNN
ERAP170MBYNN

Air-cooled condensing units

Installation manual

READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE
UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR FILES FOR
FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR
ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-
CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT.
BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT
AND HAVE THEM INSTALLED BY A PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS
CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.

(1) Refer to the operation manual or engineering data book for the complete 

list of specifications, options and features.

Model ERAP

110

150

170

Dimensions HxWxD

(mm)

2160x2340x2238

Weight

(kg)

1326

1440

1516

Connections:

- liquid line 

(inch)

7/8"

- suction line

(mm)

2-1/8"

- pressure relief valveoutlet

(inch)

FNPT 1"

Model ERAP

110

150

170

Power circuit

- Phase

3~

- Frequency

(Hz)

50

- Voltage

(V)

400

- Voltage tolerance

(%)

±10

(2) Can be used for night set back and/or peak power limitation: A kWh-gauge 

is connected to a voltage free contact. If the contact is enabled,the circuit 
will be limited to a preset capacity step.

Summary of Contents for ERAP110MBYNN

Page 1: ...ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN INSTALLATION MANUAL Air cooled condensing units...

Page 2: ...ji t no E pou it modul F v souladu s osv d en m G Kategorie rizik H Viz tak n sleduj c strana 15 kako je izlo eno u A i pozitivno ocijenjeno od strane B prema Certifikatu C kako je izlo eno u Datoteci...

Page 3: ...l stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 4: ...BMS Connection MODBUS J BUS BACNET LON Features Stepless capacity control 30 100 Low ambient operation 15 C Liquid line solenoid valve Voltage free contacts general operation pump or fan contact alarm...

Page 5: ...he length of the ropes 1 to be used for lifting are 6 m minimum each 2 The unit is shipped with wooden beams 2 under it these have to be removed before installation UNPACKING AND PLACING THE UNIT 1 Re...

Page 6: ...mmediately when exposed to air Open the liquid stop valve discharge stop valve and suction valve if provided Vacuum the unit and perform a leak test Charging the unit 1 Perform an integral pre start i...

Page 7: ...n each phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Connection of the air cooled condensing unit power supply 1 Using the appropriate c...

Page 8: ...ons the user password is asked by default when resetting a safety This password however can be changed to or to Remote digital controller address To avoid damage to the controllers liquid crystals dur...

Page 9: ...turn the fan pump on or off manually This means that when the unit is off the fan pump can also be turned on at any time to check the pump Defining the BMS settings The BMS parameters allowing communi...

Page 10: ...nted in a holder on the air cooled evaporator The setpoint for the temperature of the cooling battery will change depending on the relative humidity in the room For this purpose a relative humidity se...

Page 11: ...cuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency s...

Page 12: ...4PW22680 1E Copyright Daikin...