Installation manual

5

ERAP110~170MBYNN

Air-cooled condensing units

4PW22680-1E

2

If you operate the digital controller from a distance with a cable
as specified above, close the hole in the switch box cover with
the supplied polycarbonate plate.

Setting the adresses on the remote digital controller

When a remote digital controller is used, the adress has to be set by
means of DIP-switches according to the drawing below:

Where to find the DIP-switches of the remote digital controller

B

EFORE

 

STARTING

I do confirm having executed and checked all the above
mentioned items.

Keep for future reference.

C

USTOMIZATION

 

IN

 

THE

 

SERVICE

 

MENU

To change a setting in the service menu:

1

Enter the usersettings menu as indicated in the operation
manual and press the 

h

 key to go to the last screen to enter the

service menu (this is only possible if the unit is off).

2

Enter the correct password using the 

h

  and 

g

  keys. The

password can be found in the service manual.

3

Press 

q

 to confirm the password and enter the service menu.

4

Go to the screen which contains the parameter to be modified by
using the 

h

 and 

g

 keys.

5

Position the cursor behind the parameter to be modified using
the 

q

 key.

6

Select the appropriate setting using the 

h

 and 

g

 keys.

7

Press 

q

 to confirm the modification. When the modification has

been confirmed, the cursor switches to the next parameter
which can now be configured.

8

Place the cursor in the top left corner of the screen when you
are finished changing the parameters on this screen.

9

Repeat from instruction 4 onwards to modify other parameters.

Setting of the minimum temperature

It is possible to change the minimum allowed temperature
(

 

) in the service menu.

In case of a water cooled evaporator:

Make sure that sufficient glycol is added to the water system
according to the table.

Make sure that the low pressure safety is lowered according to
the table.

Setting the password for safety reset

To  avoid resetting of safeties by unqualified persons, the user
password is asked by default when resetting a safety.

This password however can be changed to 

 

 or to

.

Remote digital controller address

To  avoid damage to the controllers liquid crystals during
winter time, do not shut off the main power supply.

NOTE

After connecting the unit to the evaporating air unit, the
unit should not be started, not even for a very short
period of time, before the following pre-commissioning
checklist is filled out completely.

tick 

 

when 

checked

standard steps to go through before starting the unit

1

Check for external damage.

2

Open all shut-off valves indicated by a red label: "OPEN THIS 
VALVE BEFORE OPERATION". (Open the liquid line, discharge 
and suction (if provided) stop valves completely.)

3

Install main fuses, earth leak detector and mainswitch.

Recommended fuses: aM according to IEC standard 269-2.

Refer to the wiring diagram for size.

4

Supply the main voltage and check if it is within the allowable 
±10% limits of the nameplate rating.

The electrical main power supply should be arranged so, that 
it can be switched on or off independently of the electrical 
supply to other items of the plant and equipment in general.

Refer to the wiring diagram, terminals L1, L2 and L3.

5

Connect the air- or waterflow contact, so that the unit can only 
come in operation when the fan or pump is running and the air- 
waterflow is sufficient.

6

Check the oil level in the compressors.

7

Connect the optional field wiring for remote indication.

NOTE

It is necessary to read the operation manual
delivered with the unit before operating the unit. It
will contribute to understand the operation of the
unit and its electronic controller.

Close all switch box doors after installation of the unit.

Date

Sign

1 2 3 4 5 6

OFF

All customized settings must be done by a licensed
technician.

minimum outlet water (

 

)

2°C

0°C

–5°C

–10°C

Weight of ethylene glycol

(%)

10

20

30

40

Weight of propylene glycol (%)

15

25

35

40

Low pressure setting

(bar)

1.3

1.1

0.6

0.2

Improper setting of the minimum outlet water temperature
can result in severe damage of the equipment.

NOTE

Since inadequate resetting of safeties can damage the
machine, it is advised to keep the default setting of

 

.

Summary of Contents for ERAP110MBYNN

Page 1: ...ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN INSTALLATION MANUAL Air cooled condensing units...

Page 2: ...ji t no E pou it modul F v souladu s osv d en m G Kategorie rizik H Viz tak n sleduj c strana 15 kako je izlo eno u A i pozitivno ocijenjeno od strane B prema Certifikatu C kako je izlo eno u Datoteci...

Page 3: ...l stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin...

Page 4: ...BMS Connection MODBUS J BUS BACNET LON Features Stepless capacity control 30 100 Low ambient operation 15 C Liquid line solenoid valve Voltage free contacts general operation pump or fan contact alarm...

Page 5: ...he length of the ropes 1 to be used for lifting are 6 m minimum each 2 The unit is shipped with wooden beams 2 under it these have to be removed before installation UNPACKING AND PLACING THE UNIT 1 Re...

Page 6: ...mmediately when exposed to air Open the liquid stop valve discharge stop valve and suction valve if provided Vacuum the unit and perform a leak test Charging the unit 1 Perform an integral pre start i...

Page 7: ...n each phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Connection of the air cooled condensing unit power supply 1 Using the appropriate c...

Page 8: ...ons the user password is asked by default when resetting a safety This password however can be changed to or to Remote digital controller address To avoid damage to the controllers liquid crystals dur...

Page 9: ...turn the fan pump on or off manually This means that when the unit is off the fan pump can also be turned on at any time to check the pump Defining the BMS settings The BMS parameters allowing communi...

Page 10: ...nted in a holder on the air cooled evaporator The setpoint for the temperature of the cooling battery will change depending on the relative humidity in the room For this purpose a relative humidity se...

Page 11: ...cuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency s...

Page 12: ...4PW22680 1E Copyright Daikin...