background image

15 Configuration

Installation and operation manual

21

EKVDX32~100A2VEB
VRV system air conditioner
4P555815-1A – 2021.08

System example

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

N L

c

TO OUT/D

TO IN/D

a

L N

P

2

P

1

L N

P

2

P

1

L

N

b

d

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

N L

c

L

N

b

d

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

N L

c

L

N

e

a

Outdoor unit

b

Heat reclaim ventilation unit (VAM)

c

User interface

d

EKVDX indoor unit

e

Normal VRV indoor unit

14.3

To connect the external outputs

The  applied  current  of  the  external  device  MUST  be  less  or  equal
than 1 A. Install a fuse ≤1 A to protect the internal PCB contact.

If the applied current of the external device is more than 1 A, the use
of a field supplied external relay is mandatory to limit the current in
the internal PCB contact. See the example diagram below:

X1M

(I≤1A)

240 V AC

240 V AC

a

b

c

f

d

e

g

a

Relay PCB output terminal

b

AC power supply for relay

c

Fuse ≤1 A

d

Relay (field supply)

e

Relay PCB

f

AC power supply for external device

g

External device (e.g. external alarm)

In case of R32 refrigerant, the user interface built-in alarm MUST be
15 dB louder than the background noise of the room. If this is not the
case:

1

Mount an external alarm (field supply) in every EKVDX.

2

Connect the external alarm to the relay PCB of each EKVDX or
to the SVS output channel of the outdoor unit.

3

Turn off the user interface built-in alarm if the external alarm is
installed in the same space as the user interface.

Note: 

The refrigerant leakage alarm MUST be set to ON. The user

interface will generate a visible and audible warning sign in case of
R32 refrigerant leakage detection or sensor failure/disconnection.

INFORMATION

Sound  data  about  the  refrigerant  leakage  alarm  are
available  in  the  technical  data  sheet  of  the  user  interface.
E.g. the BRC1H52* controller generates an alarm of 65 dB
(sound  pressure,  measured  at  1  m  distance  from  the
alarm).

14.4

To connect the external input

INFORMATION

For  details  about  the  different  user  interface  modes  and
how  to  set  up,  refer  to  the  installation  and  operation
manual delivered with the user interface.

WARNING

In case of R32 refrigerant, terminal connections T1/T2 are
for  fire  alarm  input  ONLY.  Fire  alarm  has  a  higher  priority
than R32 safety and shuts the entire system down.

T1

T2

X1M

a

a

 Fire alarm

NOTICE

The  user  interface  has  to  be  in  fully  functional  mode  or  in
alarm only mode.

15

Configuration

NOTICE

In  case  an  EKVDX  indoor  unit  is  installed,  extreme
setpoints  can  result  in  constant  thermostat  ON  behaviour.
To prevent this, slightly increase (decrease) the respective
cooling (heating) setpoint.

INFORMATION

In  case  combined  with  EKVDX,  on  VAM,  mode  numbers
17, 18 and 19 CANNOT be used. Use 27, 28, 29.

Field settings via user interface: for EKVDX, choose indoor
unit 0. For VAM, choose indoor unit 1.

15.1

To set the discharge temperature
correction factor

The  setpoint  on  the  user  interface  of  the  EKVDX  is  related  to  the
target  discharge  temperature  (Th4c),  not  to  the  target  room
temperature.  Therefore,  the  measured  air  temperature  is  not  an
accurate  representation  of  the  room  temperature.  Set  a  correction
factor  'c'  to  compensate  for  heat  transfer  in  the  duct  between  the
EKVDX and the room.

Formula:

 'c'=ducting length×

0.10

°C

Example: 

For 10 m of duct: c=1°C.

15.2

To deactivate the R32 safety
system

During a test run of the system and during maintenance, deactivate
the R32 safety system (active by default):

1

Set VAM setting 19(29)‑15-01

2

Set  one  of  the  two  EKVDX  settings:  15(25)‑13-3  (=OFF  for  24
hours) OR 15(25)‑13-1 (=OFF)

After completion of test run or maintenance, activate the R32 safety
system again:

3

Set VAM setting 19(29)‑15-02

4

Set EKVDX setting 15(25)‑13-02

Summary of Contents for EKVDX100A2VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Page 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Page 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Page 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Page 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Page 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Page 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Page 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Page 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Page 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Page 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Page 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Page 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Page 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Page 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Page 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Page 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Page 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Page 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Page 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Page 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Page 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Page 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Page 26: ......

Page 27: ......

Page 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: