background image

8 Troubleshooting

Installation and operation manual

14

EKVDX32~100A2VEB

VRV system air conditioner

4P555815-1A – 2021.08

INFORMATION

Lifetime  of  the  sensor  is  10  years.  The  user  interface
displays  error  "

CH-05

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-02

"  after  the  end  of  the

sensor lifetime. For more information refer to the reference
guide of the user interface and contact your dealer.

INFORMATION

To stop alarm of the user interface see the reference guide
of the user interface.

INFORMATION

The minimum airflow during normal operation or during the
refrigerant leakage detection is always >240 m

3

/h.

In case detection occurs when the unit is on standby:

▪ User  interface  displays  error  "

A0-11

",  emits  alarm  sound  and

status indicator is blinking.

▪ The  fan  of  the  heat  reclaim  ventilation  unit  begins  rotating  at

ultra high speed.

▪ Contact your dealer immediately. For more information, see the

installation manual of the outdoor unit.

Airflow rate threshold levels

Airflow  rates  too  low  imply  a  safety  concern  in  case  there  is  R32
leakage.  Therefore,  when  the  R32  safety  settings  are  active,  three
airflow rate threshold levels are taken into account.

Level

Airflow rate

System response

Action required

1

Lower than normal User interface displays error

"

A6-30"

.

Auto recovery: no action required.
The error disappears.

If not, contact your dealer to
check for a dirty air filter, leakage
in ducting, …

2

Too low

User interface displays error
"

A6-29" 

or

 "UJ-38"

.

VAM and EKVDX both shut
down.

Contact your dealer to:

clean the filter.

check the installation for loose
ducting, closed dampers,…

reset the user interface (also
possible by user).

3

Below critical

airflow threshold

User interface displays error
"

A6-28" 

or

 "UJ-37"

.

In case there is a leak, it will
be detected but because
airflow is below the legal limit,
the system will automatically
start refrigerant recovery
operation to store all
refrigerant into the outdoor
unit. When recovery is
finished, the system unit goes
in locked status. Service is
needed to repair and re-
activate the system. Refer to
the service manual for more
information.

Contact your dealer to repair and
re-activate the system. Refer to
the service manual for more
information.

7.2

To clean the air outlet

WARNING

Do  NOT  let  the  indoor  unit  get  wet. 

Possible

consequence: 

Electrical shock or fire.

Clean with a soft cloth. If it is difficult to remove stains, use water or
a neutral detergent.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
circuit breaker or a residual current
device frequently actuates or the ON/
OFF switch does NOT function properly.

Turn OFF all main power
supply switches to the
unit.

If water leaks from the unit.

Stop operation.

The operation switch does NOT function
properly.

Turn OFF the power
supply.

If the user interface displays 

.

Notify your installer and
report the error code. To
display an error code see
the reference guide of the
user interface.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

INFORMATION

Refer  to  the  reference  guide  located  on 

http://

www.daikineurope.com/support-and-manuals/product-
information/

 for more troubleshooting tips.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

WARNING

Stop  operation  and  shut  OFF  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause  breakage,  electrical  shock  or  fire.  Contact  your
dealer.

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Summary of Contents for EKVDX100A2VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Page 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Page 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Page 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Page 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Page 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Page 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Page 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Page 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Page 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Page 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Page 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Page 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Page 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Page 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Page 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Page 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Page 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Page 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Page 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Page 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Page 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Page 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Page 26: ......

Page 27: ......

Page 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: