3 User safety instructions

Installation and operation manual

8

EKVDX32~100A2VEB

VRV system air conditioner

4P555815-1A – 2021.08

Step 4

 – determine the total amount of allowable refrigerant charge

in the system based on the above curves.

Step 5

 – the total refrigerant charge in the system must be less than

the  maximum  allowable  total  refrigerant  charge  value  derived  from
step 4. If not:

1

Change the installation. Do one of the following:

▪ Increase the area of smallest room.

▪ Decrease  the  piping  length  by  changing  the  system  layout  (if

practical).

▪ Increase the total floor area of the VAM+EKVDX system.

▪ Add additional countermeasures as described in the applicable

legislation.

2

Repeat all of the above steps.

Example

VRV  system  with  an  EKVDX  and  ceiling  mounted  indoor  units
serving  4  rooms.  The  total  room  area  of  all  4  rooms  is  80  m²,  the
smallest  room  with  an  indoor  unit  has  an  area  of  16  m².  No
underground floor in the building.

▪ To check the maximum allowable charge for the total room area of

80  m²  with  an  EKVDX  unit  in  the  system,  use  curve  (a)  (see 

"

 

2‒1 Example" 

[

4

 8]). 

Result: 

27 kg.

▪ To check the maximum allowable charge, for a room of 16 m² with

a  ceiling  mounted  unit,  see  the  outdoor  unit  manual  section  on
charge limitations. 

Result: 

10.4 kg.

Charge in system

10.4 kg

Factory charge

3.4 kg

Maximum field piping charge

7.0 kg

0

2

4

6

8

10

18

22

12

16

27

14.4

24

28

30

31

10 20

40

60

80

85

100

50

30

70

90

m (kg)

A

tot

 (m

2

)

(a)

(b)

  2‒1 Example

Case 2: VAM+ EKVDX only

Step  1

  –  determine  A

4

:  the  total  area  of  all  the  rooms  which  the

EKVDX unit is discharging air into. See 

"2.1.3 To determine the floor

area"

 [

4

 8].

Step 2

 – (see step 2 of case 1)

Step 3

 – in case the EKVDX:

▪ is  not  discharging  into  any  room  in  the  lowest  underground  floor,

refer to curve (a).

▪ can  discharge  to  a  combination  of  rooms  in  the  lowest

underground floor and other floors, refer to curve (b).

Step 4

 – (see step 4 of case 1)

Step 5

 – (see step 5 of case 1)

Example

VRV system with an EKVDX serving 5 rooms. The total room area is
85 m², the smallest room with a ceiling mounted indoor unit on other
floors has an area of 14 m². There are multiple underground floors in
the building and the smallest room with an indoor unit in the lowest
underground floor has an area of 24 m².

▪ To check the maximum allowable charge for a total room area of

85  m²  with  an  EKVDX  unit  in  the  system,  use  curve  (b)  (see 

"

 

2‒1 Example" 

[

4

 8]). 

Result: 

14.4 kg.

▪ To  check  the  maximum  allowable  charge,  see  the  outdoor  unit

manual for the following calculations:

▪ for a room of 14 m² with a ceiling mounted unit not in the lowest

underground floor. 

Result: 

9.3 kg.

▪ for  the  smallest  room  of  24m²  of  the  lowest  underground  floor

with a wall mounted indoor unit. 

Result: 

8.1 kg.

8.1<9.3<14.4  kg,  therefore  the  maximum  allowable  refrigerant
charge is 8.1 kg (smallest value).

Charge in system

8.1 kg

Factory charge

3.4 kg

Maximum field piping charge

4.7 kg

2.1.3

To determine the floor area

Follow these rules to determine the room area:

▪ Determine  the  room  area  by  projecting  the  walls,  doors  and

partitions to the floor and calculating the enclosed area.

▪ Do not consider spaces connected by only false ceilings, ductwork

or similar connections as a single space.

▪ If  the  partition  between  2  rooms  on  the  same  floor  meets  certain

requirements,  the  rooms  are  considered  as  one  room  and  the
areas  of  the  rooms  may  be  added  up.  This  way  it  is  possible  to
increase  the  room  area  value  used  to  calculate  the  maximum
allowed charge.

When  considering  the  smallest  single  room  (for  other  indoor  units
only,  NOT  for  EKVDX),  one  of  the  following  2  requirements  MUST
be followed:

▪ Rooms  on  the  same  floor  that  are  connected  with  a  permanent

opening  that  extends  to  the  floor  and  is  intended  for  people  to
walk through can be considered as one room.

▪ Rooms  on  the  same  floor  connected  with  openings  that  fulfil

certain requirements (see the installation and operation manual of
the  outdoor  unit)  can  be  considered  as  a  single  room.  The
opening  must  consist  out  of  at  least  2  parts  to  allow  for  air
circulation.

For the user

3

User safety instructions

Always observe the following safety instructions and regulations.

3.1

General

WARNING

If you are NOT sure how to operate the
unit, contact your installer.

Summary of Contents for EKVDX100A2VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Page 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Page 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Page 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Page 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Page 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Page 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Page 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Page 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Page 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Page 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Page 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Page 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Page 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Page 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Page 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Page 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Page 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Page 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Page 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Page 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Page 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Page 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Page 26: ......

Page 27: ......

Page 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: