16 Commissioning

Installation and operation manual

23

EKVDX32~100A2VEB
VRV system air conditioner
4P555815-1A – 2021.08

16

Commissioning

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

16.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit MUST be closed. Power-up the
unit after it is closed.

General

You  read  the  complete  installation  and  operation
instructions,  as  described  in  the 

installer  and  user

reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

Make  sure 

drain  piping

  is  properly  installed,  insulated

and drainage flows smoothly. Check for water leaks.

Possible consequence: 

Condensate water might drip.

The 

ducting

 is properly installed and insulated.

The 

reducer(s)

 is (are) properly installed and insulated.

The 

refrigerant  pipes

  (gas  and  liquid)  are  installed

correctly and thermally insulated.

There are NO 

refrigerant leaks

.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

VAM and EKVDX combination

ALL field settings related to VAM and EKVDX combination
are  set  correctly.  See 

"15.3  Field  settings"

  [

4

  22]  for  an

overview of the required settings.

User interface connected to EKVDX (not VAM).

P1/P2 connection between HRV-EKVDX is <100 m.

NO  F1/F2  connection  between  VAM  and  EKVDX  (only
P1/P2 connection allowed).

NO group control.

Power  supply  and  electrical  safety  devices  are  shared
between VAM and EKVDX.

Each VAM unit is connected to only ONE EKVDX unit (via
duct and electrical connection). There is NO connection of
the  VAM  to  any  other  indoor  unit,  linkage  or  multiple
EKVDX units.

ALL ducting is insulated on the side of VAM and EKVDX.

16.2

To perform a test run

INFORMATION

▪ Perform the test run according to the instructions in the

outdoor unit manual.

▪ The test run is only completed if there is no malfunction

code displayed on the user interface or the outdoor unit
7‑segment display.

▪ See  the  service  manual  for  the  complete  list  of  error

codes and a detailed troubleshooting guideline for each
error.

NOTICE

Do NOT interrupt the test run.

INFORMATION

During a test run of the system or during maintenance, the
R32  safety  needs  to  be  deactivated.  Refer  to 

"15.2  To

deactivate the R32 safety system"

 [

4

 21].

Set  the  relevant  field  settings  on  EKVDX,  then  on  VAM,  before
performing the test run. See 

"15.3 Field settings"

 [

4

 22].

17

Troubleshooting

17.1

Solving problems based on error
codes

If  the  unit  runs  into  a  problem,  the  user  interface  displays  an  error
code.  It  is  important  to  understand  the  problem  and  to  take
measures before resetting an error code. This should be done by a
licensed installer or by your local dealer.

This chapter gives you an overview of most possible error codes and
their descriptions as they appear on the user interface.

INFORMATION

See the service manual for:

▪ The complete list of error codes

▪ A  more  detailed  troubleshooting  guideline  for  each

error

17.1.1

Error codes: Overview

In case other error codes appear, contact your dealer.

Code

Description

The R32 sensor has detected a refrigerant leak

/

Safety system error (leak detection)

VAM air flow rate dropped below the legal threshold
limit (for R32 application)

VAM air flow approaches legal threshold limit (for R32
application)

VAM warning for air flow rate drop (for R32
application)

R32 sensor malfunction

R32 sensor end of lifetime

Summary of Contents for EKVDX100A2VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Page 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Page 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Page 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Page 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Page 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Page 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Page 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Page 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Page 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Page 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Page 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Page 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Page 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Page 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Page 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Page 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Page 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Page 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Page 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Page 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Page 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Page 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Page 26: ......

Page 27: ......

Page 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: