2 Specific installer safety instructions

Installation and operation manual

5

EKVDX32~100A2VEB
VRV system air conditioner
4P555815-1A – 2021.08

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

General

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Installation site (see 

"12.1 Preparing the installation

site"

 [

4

 16])

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

Duct installation (see 

"12.2.2 Guidelines when installing the

ducting"

 [

4

 17])

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct.

Refrigerant piping installation (see 

"13 Piping

installation"

 [

4

 18])

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

Electrical installation (see 

"14 Electrical installation"

 [

4

 19])

DANGER: RISK OF ELECTROCUTION

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

Summary of Contents for EKVDX100A2VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Page 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Page 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Page 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Page 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Page 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Page 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Page 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Page 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Page 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Page 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Page 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Page 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Page 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Page 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Page 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Page 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Page 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Page 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Page 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Page 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Page 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Page 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Page 26: ......

Page 27: ......

Page 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: