7 Installation
Installer reference guide
35
EKCB
EK2CB EKMBU EKMBUHCA9W1
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03
▪ If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent the
invasion of water in the unit and to avoid the drain water dripping
(see the following illustration).
NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate cannot
freeze.
INFORMATION
For information on the available options, contact your
dealer.
NOTICE
Provide at least 300 mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100 mm above the expected level of snow.
7.3.6
To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1
Prepare 2 cables as indicated in the following illustration (field
supply).
2
Place the 2 cables over the outdoor unit.
3
Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4
Attach the cable’s ends. Tighten those ends.
7.4
Mounting the control box
7.4.1
About mounting the control box
7.4.2
Precautions when mounting the control
box
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.4.3
To install the control box
1
Remove the front plate.
2
Hold the back plate against the wall and mark the fixation points
(2 on the top and 2 at the bottom).
NOTICE
Make sure that the marks (2 by 2) are completely level and
that their dimensions correspond to the figure below.
318 mm
310 mm
3
Drill 4 holes and install 4 plugs (suitable for M5).
4
Put the screws in the top plugs and hang the box on the
screws.
5
Put the screws in the bottom plugs.
6
Fix the 4 screws firmly.
INFORMATION
It is possible to connect the user interface to the control
box. For more information, refer to
"7.8.7 To connect the
user interface" on page 41
.
7.5
Mounting the option box
7.5.1
About mounting the option box
7.5.2
Precautions when mounting the option
box
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.5.3
To install the option box
1
Remove the front plate.
2
Hold the back plate against the wall and mark the fixation points
(2 on the top and 2 at the bottom).
Summary of Contents for EK2CB07CAV3