Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.8
[8-09]
R/W
[9-01]~[9-00], step: 1°C
45°C
A.8
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
40°C
A.8
[8-0B]
13
A.8
[8-0C]
10
A.8
[8-0D]
16
A.8
[9-00]
R/W
37~55°C, step: 1°C
55°C
A.8
[9-01]
R/W
15~37°C, step: 1°C
25°C
A.8
[9-02]
R/W
18~22°C, step: 1°C
22°C
A.8
[9-03]
R/W
5~18°C, step: 1°C
5°C
A.8
[9-04]
R/W
1~4°C, step: 1°C
1°C
A.8
[9-05]
R/W
15~37°C, step: 1°C
25°C
A.8
[9-06]
R/W
37~55°C, step: 1°C
55°C
A.8
[9-07]
R/W
5~18°C, step: 1°C
5°C
A.8
[9-08]
R/W
18~22°C, step: 1°C
22°C
A.8
[9-09]
R/W
3~10°C, step: 1°C
5°C
A.8
[9-0A]
R/W
3~10°C, step: 1°C
5°C
A.8
[9-0B]
R/W
0: Quick
1: Slow
A.8
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
A.8
[9-0D]
R/W
0~8, step:1
0 : 100%
1~4 : 80~50%
5~8 : 80~50%
6
A.8
[9-0E]
6
A.8
[A-00]
0
A.8
[A-01]
0
A.8
[A-02]
0
A.8
[A-03]
0
A.8
[A-04]
0
A.8
[B-00]
0
A.8
[B-01]
0
A.8
[B-02]
0
A.8
[B-03]
0
A.8
[B-04]
0
A.8
[C-00]
0
A.8
[C-01]
0
A.8
[C-02]
R/W
0: No
1: Bivalent
2: -
3: -
A.8
[C-03]
R/W
-25~25°C, step: 1°C
0°C
A.8
[C-04]
R/W
2~10°C, step: 1°C
3°C
A.8
[C-05]
R/W
1: Thermo ON/OFF
2: C/H request
A.8
[C-06]
R/W
0~2
0: -
1: Thermo ON/OFF
A.8
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.8
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.8
[C-09]
R/W
0: Normally open
1: Normally closed
A.8
[C-0A]
0
A.8
[C-0C]
R/W
0~7
0
A.8
[C-0D]
R/W
0~7
0
A.8
[C-0E]
R/W
0~7
0
A.8
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.8
[D-01]
R/W
0: No
1: Active open
2: Active closed
A.8
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. shunt
A.8
[D-03]
R/W
0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C)
2: Enabled, shift 4°C (from -2 to 2°C)
3: Enabled, shift 2°C (from -4 to 4°C)
4: Enabled, shift 4°C (from -4 to 4°C)
A.8
[D-04]
R/W
0: No
1: Yes
A.8
[D-05]
R/W
0: Forced off
1: As normal
A.8
[D-07]
0
A.8
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
--
--
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling?
What is the maximum desired LWT for add. zone in cooling?
What is the desired delta T in heating?
What is the desired delta T in cooling?
What emitter type is connected to the main LWT zone?
Room temperature hysteresis.
Pump speed limitation
--
--
--
--
--
--
--
--
--
--
--
--
--
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
High electricity price decimal (Do not use)
Medium electricity price decimal (Do not use)
Low electricity price decimal (Do not use)
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is the option box used for PCC ?
Is the pump allowed to run if prefer. kWh rate PS is cut?
--
Is an external kWh meter used for power measurement?
(*1) *B*_(*2) *D*
4P405542-1 - 2015.03