
5 Application guidelines
Installer reference guide
13
EKCB
EK2CB EKMBU EKMBUHCA9W1
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
INFORMATION
In case an external room thermostat is used and room frost
protection needs to be guaranteed in all conditions, then
you have to set auto emergency [A.5.1.2] to 1.
5.2.1
Single room
Under floor heating or radiators – Wired room
thermostat
Setup
B
A
a
b
c
A
Main leaving water temperature zone
B
One single room
a
User interface used as room thermostat
b
Control box
c
Backup heater (option)
▪ The under floor heating or radiators are directly connected to the
outdoor unit – or to the backup heater, if there is one.
▪ The room temperature is controlled by the user interface, that is
connected to control box EKCB07CAV3. Possible installations:
▪ Control box EKCB07CAV3 is installed in the room and the user
interface is used as room thermostat.
▪ Control box EKCB07CAV3 is installed indoors, close to the
outdoor unit + user interface installed in the room and used as
room thermostat.
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
▪
Cost effective
.
You do NOT need an additional external room
thermostat.
▪
Highest comfort and efficiency
. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature (modulation).
This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
▪
Easy
. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…
Under floor heating or radiators – Wireless room
thermostat
Setup
B
A
e
d
a
b
c
A
Main leaving water temperature zone
B
One single room
a
User interface
b
Control box
c
Backup heater (option)
d
Receiver for wireless external room thermostat
e
Wireless external room thermostat
▪ The under floor heating or radiators are directly connected to the
outdoor unit – or to the backup heater, if there is one.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main
zone:
▪ #: [A.2.2.E.5]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition.
Benefits
▪
Wireless
.
The Daikin external room thermostat is available in a
wireless version.
▪
Efficiency
.
Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heat pump system.
Summary of Contents for EK2CB07CAV3
Page 121: ......