3/8
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.2.1.B
R/W
0: At unit
1: In room
A.2.1.C
[E-0D]
Glycol present
R/W
0: No
1: Yes
└─
Options
A.2.2.A
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. shunt
A.2.2.B
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
└──────────────────
Control box
A.2.2.E.1
[E-03]
R/W
0: No BUH
1: 1 step
2: 2 steps
A.2.2.E.2
[5-0D]
R/W
0~5
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
A.2.2.E.3
[D-01]
R/W
0: No
1: Active open
2: Active closed
A.2.2.E.4
[E-05]
R/W
0: No
1: Yes
A.2.2.E.5
[C-05]
R/W
1: Thermo ON/OFF
2: C/H request
A.2.2.E.6
[C-06]
R/W
0~2
1: Thermo ON/OFF
└──────────────────
Option box
A.2.2.F.1
[C-02]
R/W
0: No
1: Bivalent
2: -
3: -
A.2.2.F.2
[C-09]
R/W
0: Normally open
1: Normally closed
A.2.2.F.3
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.F.4
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.F.5
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.2.2.F.6
[D-04]
R/W
0: No
1: Yes
└─
Capacities
A.2.3.1
[6-02]
R/W
0~10kW, step: 0,2kW
3
kW
A.2.3.2
[6-03]
R/W
0~10kW, step: 0,2kW
3kW
A.2.3.3
[6-04]
R/W
0~10kW, step: 0,2kW
0kW
Space operation
└─
LWT settings
└──────────────────
Main
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.1.2.1
[9-01]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.1.2.2
[9-00]
Temperature range
Maximum temp (heating)
R/W
37~55°C, step: 1°C
55°C
A.3.1.1.2.3
[9-03]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.1.2.4
[9-02]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.7
[9-0B]
R/W
0: Quick
1: Slow
└──────────────────
Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~55°C, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
└──────────────────
Delta T source
A.3.1.3.1
[9-09]
R/W
3~10°C, step: 1°C
5°C
A.3.1.3.2
[9-0A]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
16°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.1.3
[3-09]
Room temp. range
Minimum temp (cooling)
R/W
15~25°C, step: A.3.2.4
15°C
A.3.2.1.4
[3-08]
Room temp. range
Maximum temp (cooling)
R/W
25~35°C, step: A.3.2.4
35°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
User interface location
DHW pump
External sensor
Booster heater
BUH: step 1
BUH: step 2
LWT setpoint mode
Modulated LWT
Emitter type
LWT setpoint mode
Heating
Cooling
Room temp. offset
Backup heater steps
BUH type
Preferential kWh rate
DHW operation
Contact type main
Contact type add.
Ext. backup heat src
Alarm output
External kWh meter 1
External kWh meter 2
External sensor
PCC by digital inputs
(*1) *B*_(*2) *D*
4P405542-1 - 2015.03