5 Configuration

Installation manual

18

EHBH/X04+08DA

Daikin Altherma – Low temperature split

4P495266-1 – 2017.06

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank > Heat up mode > Reheat only.

Comfort setpoint

#

Code

Description

[5.3]

[6-0A]

Only applicable when domestic hot water
preparation is Schedule only or Schedule
+ reheat. When programming the
schedule, you can make use of the
comfort setpoint as a preset value. When
you later want to change the storage
setpoint, you only have to do it in one
place.

The tank will heat up until the 

storage

comfort temperature

 has been

reached. It is the desired temperature
when a storage comfort action is
scheduled.

Additionally, a storage stop can be
programmed. This feature puts a stop to
tank heating even if the setpoint has
NOT been reached. Only program a
storage stop when tank heating is
absolutely undesirable.

Eco setpoint

#

Code

Description

[5.4]

[6-0B]

The 

storage economic temperature

denotes the lower desired tank
temperature. It is the desired
temperature when a storage economic
action is scheduled (preferably during
day).

Reheat setpoint

#

Code

Description

[5.5]

[6-0C]

Desired  reheat  tank  temperature

,

used:

▪ in Reheat only mode or Sc

reheat 

mode: 

the 

guaranteed

minimum tank temperature is set by
the  Reheat  setpoint  minus  the
reheat  hysteresis.  If  the  tank
temperature drops below this value,
the tank is heated up.

▪ during  storage  comfort,  to  prioritize

the  domestic  hot  water  preparation.
When  the  tank  temperature  rises
above this value, domestic hot water
preparation  and  space  heating/
cooling are executed sequentially.

5.3

Settings menu

You can set additional settings using the main menu screen and its
submenus. The most important settings are presented here.

5.3.1

Main zone

Thermostat type

Only applicable in external room thermostat control.

NOTICE

If  an  external  room  thermostat  is  used,  the  external  room
thermostat will control the room frost protection. However,
the  room  frost  protection  is  only  possible  if  the  leaving
water  temperature  control  on  the  unit's  user  interface  is
turned ON.

#

Code

Description

[2.A]

[C–05]

External room thermostat type for the
main zone:

▪ 1:  1  contact:  The  used  external  room

thermostat  can  only  send  a  thermo
ON/OFF  condition.  There  is  no
separation between heating or cooling
demand.

▪ 2: 2 contacts: The used external room

thermostat  can  send  a  separate
heating/cooling 

thermo 

ON/OFF

condition.

5.3.2

Additional zone

Thermostat type

Only  applicable  in  external  room  thermostat  control.  For  more  info
about the functionality, see 

"5.3.1 Main zone" on page 18

.

#

Code

Description

[3.A]

[C–06]

External room thermostat type for the
additional zone:

▪ 1: 1 contact

▪ 2: 2 contacts

5.3.3

Information

Dealer information

The installer can fill in his contact number here.

#

Code

Description

[8.3]

N/A

Number that users can call in case of
problems.

Summary of Contents for EHBH04DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHBH04DA6V EHBH08DA6V EHBH08DA9W EHBX04DA6V EHBX08DA6V EHBX08DA9W...

Page 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputam...

Page 3: ...figuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zo...

Page 4: ...5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured from the bottom of the casing to the floor Special requireme...

Page 5: ...of the required opening area must be situated 200 mm from the floor The entire area of the opening must be situated 300 mm from the floor Top opening The area of the top opening must be larger than o...

Page 6: ...Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 g 3 Power supply for backup heater See table below 4 Prefere...

Page 7: ...to the user interface open the lower front panel 1 2 3 2 5 Optional Remove the lower front panel NOTICE If you remove the lower front panel with integrated user interface also disconnect the cables fr...

Page 8: ...unit a b a Refrigerant liquid connection b Refrigerant gas connection 2 Connect the gas stop valve from the outdoor unit to the refrigerant gas connection of the indoor unit 4 4 Connecting the water p...

Page 9: ...n of the heating and cooling capacity If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condens...

Page 10: ...tem to have EITHER preferential kWh rate power supply OR a safety thermostat 4 5 4 To connect the backup heater power supply CAUTION If the indoor unit has a tank with a built in electrical booster he...

Page 11: ...3 6 5 14 13 F1B Overcurrent fuse field supply Recommended fuse for 6V and 9W models 4 pole 20 A curve 400 V tripping class C K1M Contactor in the switch box K5M Safety contactor in the switch box Q1D...

Page 12: ...ble ties to the cable tie mountings 4 5 9 To connect the space cooling heating ON OFF output 1 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illust...

Page 13: ...guration This chapter describes what you have to do and know to configure the system after it is installed NOTICE The explanation about the configuration in this chapter gives you ONLY basic explanati...

Page 14: ...NFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart...

Page 15: ...erature zones During configuration the number of water zones must be set Code Description 4 5 7 02 0 Single zone Only one leaving water temperature zone a a Main LWT zone Code Description 4 5 7 02 1 D...

Page 16: ...ambient temperature Therefore it is important to set this correctly and in accordance with your system layout Code Description 2 7 2 0C 0 Underfloor heating 1 Fancoil unit 2 Radiator The setting of t...

Page 17: ...in zone on page 16 Code Description 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent operation is active the desired tank temperature is determined automati...

Page 18: ...e guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritiz...

Page 19: ...Benefit kWh power supply Allow heater Allow pump 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar...

Page 20: ...alve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 6 The domestic hot water tank is filled compl...

Page 21: ...nces in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed...

Page 22: ...water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigerant O...

Page 23: ...thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Englis...

Page 24: ...ic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translatio...

Page 25: ...Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only...

Page 26: ...corresponds to Aroom 8 m2 H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800...

Page 27: ...es i e when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For inte...

Page 28: ...4P495266 1 2017 06 Copyright 2017 Daikin 4P495266 1 0000000U...

Reviews: