8 Technical data
Installation manual
26
EHBH/X04+08DA
Daikin Altherma – Low temperature split
4P495266-1 – 2017.06
8.3
Table 1 – Maximum refrigerant charge allowed in a room: indoor unit
A
room
(m
2
)
Maximum refrigerant charge in a room (m
max
) (kg)
H=1150 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
1
0.25
0.26
0.29
0.31
0.33
0.36
0.38
0.40
2
0.51
0.53
0.58
0.62
0.67
0.71
0.76
0.81
3
0.76
0.79
0.86
0.93
1.00
1.07
1.14
1.21
4
1.01
1.06
1.15
1.24
1.34
1.43
1.52
1.61
5
1.27
1.32
1.44
1.55
1.67
1.78
1.90
2.01
6
1.52
1.59
1.73
1.87
2.00
2.14
2.28
2.42
7
1.66
1.74
1.89
2.04
2.19
2.34
2.49
2.65
8
1.78
1.86
2.02
2.18
2.34
2.50
2.67
2.83
9
1.89
1.97
2.14
2.31
2.49
2.66
2.83
3.00
10
1.99
2.08
2.26
2.44
2.62
2.80
2.98
3.16
INFORMATION
▪ H = Height measured from the bottom of the casing to
the floor.
▪ For intermediate H values (i.e. when H is between two
H values from the table), consider the value that
corresponds to the lower H value from the table. If
H=1450 mm, consider the value that corresponds to
"H=1400 mm".
▪ For intermediate A
room
values (i.e. when A
room
is
between two A
room
values from the table), consider the
value that corresponds to the lower A
room
value from the
table. If A
room
=8.5 m
2
, consider the value that
corresponds to "A
room
=8 m
2
".
H
≥
1150
≥
200
≥
200
≥
500
(mm)
≥450
8.4
Table 2 – Minimum floor area: indoor unit
m
c
(kg)
Minimum floor area (m²)
H=1150 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
1.84
8.57
7.84
6.64
5.92
5.51
5.16
4.84
4.57
1.86
8.76
8.02
6.78
5.98
5.57
5.21
4.90
4.62
1.88
8.95
8.19
6.93
6.05
5.63
5.27
4.95
4.67
1.90
9.14
8.36
7.08
6.11
5.69
5.32
5.00
4.72
INFORMATION
▪ H = Height measured from the bottom of the casing to
the floor.
▪ For intermediate H values (i.e. when H is between two
H values from the table), consider the value that
corresponds to the lower H value from the table. If
H=1450 mm, consider the value that corresponds to
"H=1400 mm".
▪ Systems with total refrigerant charge lower than
1.84 kg are not subjected to any room requirements.
▪ Charges above 1.9 kg are not allowed in the unit.
8.5
Table 3 – Minimum venting opening area for natural ventilation: indoor unit
m
c
m
max
dm=m
c
–m
max
(kg)
Minimum venting opening area (cm
2
)
H=1150 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
1.9
0.1
1.80
538
515
495
477
461
446
433
421
1.9
0.3
1.60
479
458
440
424
410
397
385
374
1.9
0.5
1.40
419
401
385
371
359
347
337
327
1.9
0.7
1.20
359
344
330
318
308
298
289
281
1.9
0.9
1.00
299
287
275
265
256
248
241
234
1.9
1.1
0.80
240
229
220
212
205
199
193
187
1.9
1.3
0.60
180
172
165
159
154
149
145
141
1.9
1.5
0.40
120
115
110
106
103
100
97
94
1.9
1.7
0.20
63
58
55
53
52
50
49
47