background image

6 Commissioning

Installation manual

20

EHBH/X04+08DA

Daikin Altherma – Low temperature split

4P495266-1 – 2017.06

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

▪ Between  the  indoor  unit  and  the  domestic  hot  water

tank (if applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

Only for tanks with built-in booster heater:

Booster  heater  circuit  breaker

  F2B  (field  supply)  is

turned ON.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The 

air purge

 valve is open (at least 2 turns).

The 

pressure relief valve

 purges water when opened.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"3.2 Preparing water piping" on page 6

.

The 

domestic hot water tank

 is filled completely.

INFORMATION

The  software  is  equipped  with  an  "installer-on-site"  mode
([9.G]:  Disable  protections),  that  disables  automatic
operation  by  the  unit.  At  first  installation,  setting  Disable
protections  is  by  default  set  to  Yes,  meaning  automatic
operation  is  disabled.  All  protective  functions  are  then
disabled. If the user interface home pages are off, the unit
will  NOT  operate  automatically.  To  enable  automatic
operation  and  the  protective  functions,  set  Disable
protections to No.

36 hours after the first power-on, the unit will automatically
set  Disable  protections  to  No,  ending  "installer-on-site"
mode  and  enabling  the  protective  functions.  If  –  after  first
installation  –  the  installer  returns  to  the  site,  the  installer
has to set Disable protections to Yes manually.

6.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"3.2  Preparing  water

piping" on page 6

.

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

6.2.1

To check the minimum flow rate

1

Confirm according to the hydraulic configuration
which space heating loops can be closed due to
mechanical, electronic, or other valves.

2

Close all space heating loops that can be closed
(see previous step).

3

Start the pump test run operation (see 

"6.2.4 To

perform an actuator test run" on page 21

).

4

During pump test run operation, go to Sensors.

5

Select the flow rate information. During test run
operation, the unit can operate below the minimum
required flow rate.

6

Modify the bypass valve setting to reach the
minimum required flow rate + 2 l/min.

Minimum required flow rate during defrost/backup heater
operation

12 l/min

6.2.2

To perform an air purge

1

Set the user permission level to Installer. See 

"To

change the user permission level" on page 13

.

2

Go to [A.3]: Commissioning > Air purge.

Summary of Contents for EHBH04DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHBH04DA6V EHBH08DA6V EHBH08DA9W EHBX04DA6V EHBX08DA6V EHBX08DA9W...

Page 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputam...

Page 3: ...figuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zo...

Page 4: ...5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured from the bottom of the casing to the floor Special requireme...

Page 5: ...of the required opening area must be situated 200 mm from the floor The entire area of the opening must be situated 300 mm from the floor Top opening The area of the top opening must be larger than o...

Page 6: ...Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 g 3 Power supply for backup heater See table below 4 Prefere...

Page 7: ...to the user interface open the lower front panel 1 2 3 2 5 Optional Remove the lower front panel NOTICE If you remove the lower front panel with integrated user interface also disconnect the cables fr...

Page 8: ...unit a b a Refrigerant liquid connection b Refrigerant gas connection 2 Connect the gas stop valve from the outdoor unit to the refrigerant gas connection of the indoor unit 4 4 Connecting the water p...

Page 9: ...n of the heating and cooling capacity If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condens...

Page 10: ...tem to have EITHER preferential kWh rate power supply OR a safety thermostat 4 5 4 To connect the backup heater power supply CAUTION If the indoor unit has a tank with a built in electrical booster he...

Page 11: ...3 6 5 14 13 F1B Overcurrent fuse field supply Recommended fuse for 6V and 9W models 4 pole 20 A curve 400 V tripping class C K1M Contactor in the switch box K5M Safety contactor in the switch box Q1D...

Page 12: ...ble ties to the cable tie mountings 4 5 9 To connect the space cooling heating ON OFF output 1 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illust...

Page 13: ...guration This chapter describes what you have to do and know to configure the system after it is installed NOTICE The explanation about the configuration in this chapter gives you ONLY basic explanati...

Page 14: ...NFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart...

Page 15: ...erature zones During configuration the number of water zones must be set Code Description 4 5 7 02 0 Single zone Only one leaving water temperature zone a a Main LWT zone Code Description 4 5 7 02 1 D...

Page 16: ...ambient temperature Therefore it is important to set this correctly and in accordance with your system layout Code Description 2 7 2 0C 0 Underfloor heating 1 Fancoil unit 2 Radiator The setting of t...

Page 17: ...in zone on page 16 Code Description 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent operation is active the desired tank temperature is determined automati...

Page 18: ...e guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritiz...

Page 19: ...Benefit kWh power supply Allow heater Allow pump 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar...

Page 20: ...alve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 6 The domestic hot water tank is filled compl...

Page 21: ...nces in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed...

Page 22: ...water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigerant O...

Page 23: ...thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Englis...

Page 24: ...ic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translatio...

Page 25: ...Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only...

Page 26: ...corresponds to Aroom 8 m2 H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800...

Page 27: ...es i e when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For inte...

Page 28: ...4P495266 1 2017 06 Copyright 2017 Daikin 4P495266 1 0000000U...

Reviews: