Installation manual

3

EHBH/X04+08DA
Daikin Altherma – Low temperature split
4P495266-1 – 2017.06

Table of contents

1 About the documentation

3

1.1

About this document..................................................................

3

2 About the box

4

2.1

Indoor unit .................................................................................

4

2.1.1

To remove the accessories from the indoor unit.........

4

3 Preparation

4

3.1

Preparing the installation site ....................................................

4

3.1.1

Installation site requirements of the indoor unit ..........

4

3.2

Preparing water piping ..............................................................

6

3.2.1

To check the water volume and flow rate ...................

6

3.3

Preparing electrical wiring .........................................................

6

3.3.1

Overview of electrical connections for external and
internal actuators ........................................................

6

4 Installation

6

4.1

Opening the units ......................................................................

6

4.1.1

To open the indoor unit ...............................................

6

4.2

Mounting the indoor unit............................................................

7

4.2.1

To install the indoor unit..............................................

7

4.3

Connecting the refrigerant piping ..............................................

8

4.3.1

To connect the refrigerant piping to the indoor unit ....

8

4.4

Connecting the water piping......................................................

8

4.4.1

To connect the water piping........................................

8

4.4.2

To connect the drain hose to the drain .......................

9

4.4.3

To fill the water circuit .................................................

9

4.4.4

To fill the domestic hot water tank ..............................

9

4.4.5

To insulate the water piping ........................................

9

4.5

Connecting the electrical wiring.................................................

9

4.5.1

About electrical compliance ........................................

9

4.5.2

To connect the electrical wiring on the indoor unit......

9

4.5.3

To connect the main power supply ............................. 10

4.5.4

To connect the backup heater power supply .............. 10

4.5.5

To connect the shut-off valve...................................... 11

4.5.6

To connect the electrical meters ................................. 11

4.5.7

To connect the domestic hot water pump ................... 12

4.5.8

To connect the alarm output ....................................... 12

4.5.9

To connect the space cooling/heating ON/OFF
output .......................................................................... 12

4.5.10

To connect the changeover to external heat source... 12

4.5.11

To connect the power consumption digital inputs ....... 12

4.5.12

To connect the safety thermostat (normal closed
contact) ....................................................................... 13

4.6

Finishing the indoor unit installation ..........................................

13

4.6.1

To close the indoor unit............................................... 13

5 Configuration

13

5.1

Overview: Configuration ............................................................

13

5.1.1

To access the most used commands ......................... 13

5.2

Configuration wizard..................................................................

14

5.2.1

Configuration wizard: Language ................................. 14

5.2.2

Configuration wizard: Time and date .......................... 14

5.2.3

Configuration wizard: System ..................................... 14

5.2.4

Configuration wizard: Backup heater .......................... 15

5.2.5

Configuration wizard: Main zone................................. 16

5.2.6

Configuration wizard: Additional zone......................... 17

5.2.7

Detailed screen with weather-dependent curve.......... 17

5.2.8

Configuration wizard: Tank ......................................... 17

5.3

Settings menu ...........................................................................

18

5.3.1

Main zone ................................................................... 18

5.3.2

Additional zone ........................................................... 18

5.3.3

Information .................................................................. 18

5.4

Menu structure: Overview installer settings...............................

19

6 Commissioning

20

6.1

Checklist before commissioning ................................................

20

6.2

Checklist during commissioning ................................................. 20

6.2.1

To check the minimum flow rate .................................. 20

6.2.2

To perform an air purge ............................................... 20

6.2.3

To perform an operation test run ................................. 21

6.2.4

To perform an actuator test run ................................... 21

6.2.5

To perform an underfloor heating screed dryout.......... 21

7 Hand-over to the user

21

8 Technical data

22

8.1

Piping diagram: Indoor unit ........................................................ 22

8.2

Wiring diagram: Indoor unit ........................................................ 23

8.3

Table 1 – Maximum refrigerant charge allowed in a room:
indoor unit................................................................................... 26

8.4

Table 2 – Minimum floor area: indoor unit .................................. 26

8.5

Table 3 – Minimum venting opening area for natural
ventilation: indoor unit ................................................................ 26

1

About the documentation

1.1

About this document

Target audience

Authorised installers

Documentation set

This  document  is  part  of  a  documentation  set.  The  complete  set
consists of:

General safety precautions:

▪ Safety instructions that you must read before installing

▪ Format: Paper (in the box of the indoor unit)

Indoor unit installation manual:

▪ Installation instructions

▪ Format: Paper (in the box of the indoor unit)

Outdoor unit installation manual:

▪ Installation instructions

▪ Format: Paper (in the box of the outdoor unit)

Installer reference guide:

▪ Preparation of the installation, good practices, reference data,…

▪ Format:  Digital  files  on 

http://www.daikineurope.com/support-

and-manuals/product-information/

Addendum book for optional equipment:

▪ Additional info about how to install optional equipment

▪ Format:  Paper  (in  the  box  of  the  indoor  unit)  +  Digital  files  on

http://www.daikineurope.com/support-and-manuals/product-
information/

Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.

The original documentation is written in English. All other languages
are translations.

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

Summary of Contents for EHBH04DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EHBH04DA6V EHBH08DA6V EHBH08DA9W EHBX04DA6V EHBX08DA6V EHBX08DA9W...

Page 2: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputam...

Page 3: ...figuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zo...

Page 4: ...5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured from the bottom of the casing to the floor Special requireme...

Page 5: ...of the required opening area must be situated 200 mm from the floor The entire area of the opening must be situated 300 mm from the floor Top opening The area of the top opening must be larger than o...

Page 6: ...Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 g 3 Power supply for backup heater See table below 4 Prefere...

Page 7: ...to the user interface open the lower front panel 1 2 3 2 5 Optional Remove the lower front panel NOTICE If you remove the lower front panel with integrated user interface also disconnect the cables fr...

Page 8: ...unit a b a Refrigerant liquid connection b Refrigerant gas connection 2 Connect the gas stop valve from the outdoor unit to the refrigerant gas connection of the indoor unit 4 4 Connecting the water p...

Page 9: ...n of the heating and cooling capacity If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condens...

Page 10: ...tem to have EITHER preferential kWh rate power supply OR a safety thermostat 4 5 4 To connect the backup heater power supply CAUTION If the indoor unit has a tank with a built in electrical booster he...

Page 11: ...3 6 5 14 13 F1B Overcurrent fuse field supply Recommended fuse for 6V and 9W models 4 pole 20 A curve 400 V tripping class C K1M Contactor in the switch box K5M Safety contactor in the switch box Q1D...

Page 12: ...ble ties to the cable tie mountings 4 5 9 To connect the space cooling heating ON OFF output 1 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illust...

Page 13: ...guration This chapter describes what you have to do and know to configure the system after it is installed NOTICE The explanation about the configuration in this chapter gives you ONLY basic explanati...

Page 14: ...NFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart...

Page 15: ...erature zones During configuration the number of water zones must be set Code Description 4 5 7 02 0 Single zone Only one leaving water temperature zone a a Main LWT zone Code Description 4 5 7 02 1 D...

Page 16: ...ambient temperature Therefore it is important to set this correctly and in accordance with your system layout Code Description 2 7 2 0C 0 Underfloor heating 1 Fancoil unit 2 Radiator The setting of t...

Page 17: ...in zone on page 16 Code Description 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent operation is active the desired tank temperature is determined automati...

Page 18: ...e guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritiz...

Page 19: ...Benefit kWh power supply Allow heater Allow pump 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar...

Page 20: ...alve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 6 The domestic hot water tank is filled compl...

Page 21: ...nces in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed...

Page 22: ...water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigerant O...

Page 23: ...thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Englis...

Page 24: ...ic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translatio...

Page 25: ...Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only...

Page 26: ...corresponds to Aroom 8 m2 H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800...

Page 27: ...es i e when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For inte...

Page 28: ...4P495266 1 2017 06 Copyright 2017 Daikin 4P495266 1 0000000U...

Reviews: